Instrukcja obsługi Kidde CO120X
Kidde
Detektor dymu
CO120X
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Kidde CO120X (1 stron) w kategorii Detektor dymu. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek
Strona 1/1
C O 1 2 0 X
CARBON MONOXIDE RELAY MODULE
READ INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE INSTALLING.
Electrical Rating: 120V AC 60 HZ 0.08 AMP
Contact Rating: 10 AMPS @ 120 VAC
NON INDUCTIVE
5 AMPS @ 30 VDC
DESCRIPTION:
This module is only activated by a Kidde Carbon Monoxide Alarm interconnect signal.
Compatible with alarm models: KN-COSM-I, KN-COSM-IB, KN-COSM-ICA, KN-COSM-
IBCA, KN-COB-IC, KN-COB-IC-CA, KN-COB-ICB-CA, KN-COP-IC, KN-COP-IC-CA
This relay module can be used to activate auxiliary warning devices such as external bells and
sirens, hallway or stairwell lighting. It provides isolated, (no internal connection to 120 volts AC)
normally open, and normally closed contacts.
Outer packaging is blue, in order to distinguish from Smoke Relay Module, Model SM120X,
which has black outer packaging.
This device will only activate when it receives a CO interconnect signal from a compatible
device. When in the activated mode (as a result of a CO signal), this device will deactivate if it
receives a smoke interconnect signal from a compatible device.
WARNING! Alarm and module wiring must conform to the electrical codes and local codes
in your area. In USA, it includes articles 210 and 300.3(B) of the U.S. National Electrical Code
ANSI/NFPA 70, and NFPA 72. The multiple station interconnect wiring to the alarms must be
run in the same raceway or cable as the AC power wiring. In addition, the resistance of the
interconnect wiring shall be a maximum of 10 ohms.
All wiring should be performed by a licensed electrician. The module should be installed in a
UL listed junction box that has sufficient volume for proper installation. The electrical circuit
used to power the alarms and the module must be a 120 volt AC 60hz circuit which cannot be
turned off by a switch or a ground fault interrupter, it must be on 24 hours a day. Since this
module is 120 volt AC powered, it will not function during an AC power failure, even
if it is being used with models KN-COSM-IB,KN-COSM-IBCA, KN-COB-IC or KN-COP-IC,alarms
which have battery backup power.
IMPORTANT: Whenever alarms and modules are interconnected they must be powered from
a single circuit. When wiring the module remote from the alarm use UL/CSA listed wire as
required by codes in your area. between the firstDo not use mor than 1000 feet of wire e
and last device in the multi station system.
INSTALLATION INSTRUCTIONS:
This module should be installed in a UL listed junction box. All connections should be made by
a qualified electrician in accordance with the requirements of the national electrical code
and/or any other local codes having jurisdiction in your area.
Turn off the main power to the circuit. If you are also installing smoke alarms, heat alarms,
or CO alarms, wire them according to their specific owner’s manual. Refer to the typical
installation diagram (Figure 1) included in this manual for your specific application.
Connections on the CO Relay Module:
Black Wire AC Hot
White Wire AC Neutral
Red Wire Interconnect Signal
Blue Wire Common Contact
Yellow Wire Normally Closed Contact
Orange Wire Normally Open Contact
After all connections are made, place the module inside a UL listed junction box, where the
alarm is installed, or in a remote location and use the appropriate electrical box cover.
CAUTION:The model CO120X should not be used to connect groups of CO alarms to an alarm
panel or to interconnect groups of CO alarms together.
Residential alarms do not latch in the alarm condition and they are self-resetting. If an alarm
connected to a module has the test button pushed or the alarm momentarily activates, it will
activate the module for as long as the unit is in alarm. If more than one alarm is connected to
the module and the module is tied to a control panel there will be no way of knowing which
unit caused the alarm.
The model CO120X module is for use with the following interconnectable models: Carbon
Monoxide Alarms: KN-COB-IC, KN-COB-IC-CA, KN-COB-ICB-CA, KN-COP-IC and KN-COP-IC-
CA, and CO/ Smoke Combo Alarms: KN-COSM-I, KN-COSM-IB, KN-COSM-ICA and
KN-COSM-IBCA, all with red interconnect wires. Each module is equivalent to one interconnect
alarm, reduce the maximum number of interconnect devices by one for each module used. Do
not exceed the total number of devices allowable in the interconnect system, refer to the
individual alarm owners manual for the maximum number of units allowed when
interconnecting. Do not exceed the temperature or humidity limits of +40°F (4.4°C) to 100°F
(37.8°C) (such as garages and unfinished attics) and 85% relative humidity for either the relay
module or the alarms.
NOTE: Only the Carbon Monoxide portion of the: KN-COSM-I, KN-COSM-IB, KN-COSM-ICA
and KN-COSM-IBCA combo alarms will activate this module. If activation is required from the
Smoke Alarm portion of these alarms, use the SM120X module.
ATTENTION: The wiring connecting the module with the external devices is not supervised.
Be sure to test the operation of all the devices controlling the module or controlled by the
module. Devices controlled by the module can be tested by pushing the test button on the
alarms and verifying that the controlled device responds in the desired manner.
ADDITIONAL INSTALLATION INFORMATION: If the desired function is to switch off a device
when the alarms sound, connect the yellow wire (NC) instead of the orange wire (NO) to the
supply side of the device. Be sure not to exceed the relay contact ratings of the module. This
module should not be used to control inductive loads with inrush currents that will exceed the
maximum contact ratings.
ONE YEAR LIMITED WARRANTY:
Kidde warrants to the Purchaser that the enclosed module will be free of defects in material,
workmanship or design under normal use and service for a period of one year from the date
of purchase. The obligation to Kidde under this warranty is limited to repairing or replacing any
part which we find to be defective in material, or design, free of chargeworkmanship, , to the
customer, upon sending the relay module with proof of date of purchase, postage and return
postage prepaid, to Warranty Service dept. Kidde Safety, 1016 Corporate Park Drive, Mebane,
NC 27302 USA. (1-800-880-6788) This warranty shall not apply to the relay module if it has
been damaged, modified, abused or altered after the date of purchase, or if it fails to operate
due to improper maintenance or inadequate AC electrical power.
The liability of Kidde or any of its parent or subsidiary corporations arising from the sale of this
accessory module or under the terms of this limited warranty shall not in any case exceed the
cost of the replacement of the module and, in no case, shall Kidde or any of its parent or
subsidiary corporations be liable for consequential loss or damages resulting from the failure
of the relay module or for the breach of this or any other warranties, expressed or implied, even
if the loss of damage is caused the company's negligence or fault.
Since some states/provinces do not allow limitations on the duration of an implied warranty or
do not allow the exclusions or limitations of incidental or consequential damages the above
limitations or exclusions may not apply to you. While this warranty gives you specific legal
rights, you may also have other rights, which vary from state to state, or province to province.
The above warranty may not be altered except in writing signed by both parties hereto.
Manual P/N 810-1809 Rev. C
FIGURE 1
FIGURE 1 shows a typical installation of a relay module wired to switch on 120 volt device when the alarms sound. In this conguration the common switch contact (blue wire) is
connected to the 120 volt supply. When the alarms sound the module detects the signal on the interconnect line (red wire) and activates the relay. As a result of this action, the orange
wire (NO) supplies 120 volts to the device.
Specyfikacje produktu
Marka: | Kidde |
Kategoria: | Detektor dymu |
Model: | CO120X |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Kidde CO120X, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Detektor dymu Kidde
10 Grudnia 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
Instrukcje Detektor dymu
- Detektor dymu Stabo
- Detektor dymu Nedis
- Detektor dymu Nexa
- Detektor dymu Marquant
- Detektor dymu Swann
- Detektor dymu Mercury
- Detektor dymu ORNO
- Detektor dymu TFA
- Detektor dymu DSC
- Detektor dymu Trust
- Detektor dymu GLORIA
- Detektor dymu Qolsys
- Detektor dymu Dahua Technology
- Detektor dymu Emos
- Detektor dymu Homematic IP
- Detektor dymu Pyle
- Detektor dymu Bavaria
- Detektor dymu First Alert
- Detektor dymu Abus
- Detektor dymu Elro
- Detektor dymu Olympia
- Detektor dymu Netatmo
- Detektor dymu Schwaiger
- Detektor dymu Hager
- Detektor dymu Denver
- Detektor dymu Yale
- Detektor dymu Busch-Jaeger
- Detektor dymu Fibaro
- Detektor dymu Vivanco
- Detektor dymu EQ-3
- Detektor dymu Alecto
- Detektor dymu X-Sense
- Detektor dymu M-e
- Detektor dymu H-Tronic
- Detektor dymu Smartwares
- Detektor dymu Elgato
- Detektor dymu Sygonix
- Detektor dymu Ajax
- Detektor dymu AngelEye
- Detektor dymu Flamingo
- Detektor dymu Brennenstuhl
- Detektor dymu Eminent
- Detektor dymu KlikaanKlikuit
- Detektor dymu Ei Electronics
- Detektor dymu Steren
- Detektor dymu ESYLUX
- Detektor dymu Malmbergs
- Detektor dymu Nest
- Detektor dymu FireAngel
- Detektor dymu Chacon
- Detektor dymu Konig
- Detektor dymu BRK
- Detektor dymu Gira
- Detektor dymu FireX
- Detektor dymu Fito
- Detektor dymu HQ
- Detektor dymu FirstAlert
- Detektor dymu Popp
- Detektor dymu Satel
- Detektor dymu EQ3
- Detektor dymu Calex
- Detektor dymu Lanberg
- Detektor dymu Mobeye
- Detektor dymu FireHawk
- Detektor dymu Chuango
- Detektor dymu TEF
- Detektor dymu Heatit
- Detektor dymu Fito Profi-line
- Detektor dymu Kogan
- Detektor dymu System Sensor
- Detektor dymu Pyrexx
- Detektor dymu Pristine
- Detektor dymu Cavius
- Detektor dymu Jemay
- Detektor dymu Pentatech
- Detektor dymu Mircom
- Detektor dymu WisuAlarm
- Detektor dymu BRK DICON
- Detektor dymu Cordes
- Detektor dymu STI
- Detektor dymu Deltronic
- Detektor dymu Insafe
- Detektor dymu Gewiss
- Detektor dymu No-Flame
- Detektor dymu Egardia
- Detektor dymu GEV
- Detektor dymu Frient
- Detektor dymu SAVS
Najnowsze instrukcje dla Detektor dymu
14 Października 2024
9 Października 2024
9 Października 2024
8 Października 2024
8 Października 2024
8 Października 2024
8 Października 2024
7 Października 2024
7 Października 2024
7 Października 2024