Instrukcja obsługi Ei Electronics MCP401RC


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Ei Electronics MCP401RC (2 stron) w kategorii przełącznik. Ta instrukcja była pomocna dla 12 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
MCP401RC Manual Call Point
Disconnect the AC mains power supply from the circuit that is to
be used to power the smoke/heat alarms and the MCP401RC.
Install the Smoke/Heat/CO Alarms as per the Installer
Instructions supplied with the alarms.
Select a suitable location where the MCP401RC can be easily
accessed. The unit should not be exposed to dripping or splashing.
Route the wiring (Live, Neutral, Interconnect/Control and Earth)
to the MCP401RC siting location. A minimum 0.75mm
2cable
should be used.
With the 25mm screws provided, fix the mounting box to the wall.
Secure the wall plate to the mounting box using the 35mm
machine screws provided.
SURFACE MOUNTING BOX
SECURITY SCREW
1.5 x 10mm
SCREW (2)
3.5 x 35mm
WALL PLATE
FRONT COVER
OPERATING ELEMENT
SCREW (2)
3.5 x 25mm
Figure 1
Installation & Wiring
1
2
3
4
5
6Figure 2
To additional Ei Alarms
if required
(compatible alarms
listed above)
Figure 3
When the black spot on the front face of the MCP401RC is pressed, an alarm signal will be sent along the
interconnect line and all interconnected alarms will sound. The MCP401RC switch element can be reset using
the plastic key supplied.
PLEASE NOTE: The MCP401RC is designed for use with the following models of Smoke/Heat/CO Alarms
- Ei161RC, 164RC, 166RC, 141, 144, 146, 151TL, 154TL, 156TLH, 261ENRC, 261DENRC.
WARNING: This Manual Call Point should be installed by a qualified electrician in accordance with the
Requirements for Electrical Installations published by the Institute of Electrical Engineers (BS7671 current edition).
A maximum of 4 MCP401RC units can be installed on one system in addition to 12 interconnect alarms.
B16073-R0-MCP401RC-UC-ENG 19/4/07 9:17 AM Page 1
P/N B16073 Rev 0
Testing
It is recommended that the MCP401RC is tested directly after installation and then at least monthly.
Test that the MCP401RC call point triggers the alarm(s) by pressing the black spot on the front cover. A
striped warning indicator should drop down into view on the front face (visible through the clear plastic
window). Check that each alarm in the system is sounding.
Reset the MCP401RC by following the instructions in the Resetting section below. The alarms should stop
sounding.
Now turn off the mains power to the system. Repeat the test above (this checks the rechargeable back-up
in the unit). Reinstate the mains power to the system. The MCP401RC will operate in standby with mains
off for over 6 months. With the Manual Call Point triggered it can give an alarm signal for over 16 hours.
The crossed out wheelie bin symbol that is on your
product indicates that this product should not be disposed
of via the normal household waste stream. Proper
disposal will prevent possible harm to the environment or
to human health. When disposing of this product please
separate it from other waste streams to ensure that it can
be recycled in an environmentally sound manner. For
more details on collection and proper disposal, please
contact your local government ofce or the retailer where
you purchased this product.
Aico Ltd. Mile End Business Park,
Maesbury Rd, Oswestry,
Shropshire, SY10 8NN, U.K.
Tel: 0870 7584000 www.aico.co.uk
Ei Electronics. Shannon, Ireland.
Tel: +353 (0)61 471277 www.eielectronics.com
Connect the wiring as shown in Figures 2 & 3 previously. Note: the Earth connection is for convenient
termination of the earth conductor and is not required for the safety of the unit. The wiring should be
installed securely (e.g. tie wrap together) to prevent a hazard if one becomes detached.
Carefully slide the front cover and circuit board diagonally into the mounting box, top section first (see Figure 4).
Then carefully locate the top of the front cover onto the top of the wall plate and hinge down to snap
securely in place (see Figure 5).
7
1
2
3
Fit the security screw to the call point - the hole for this is on the bottom face of the front cover (see
Figure 6). This is essential for electrical safety as mains is present within the unit.
Reconnect the AC mains power to the circuit and check that the green mains indicator lights on the
Smoke/Heat/CO Alarms are on.
10
11
8
9
Figure 4 Figure 5 Figure 6
To reset the unit, insert the
reset key into the hole in the
bottom of the front cover. The
striped warning indicator
should disappear. With the key
still inserted, twist it anti-
clockwise until the operating
element clicks back into place,
then remove the reset key (see
Figure 7).
Figure 7 Figure 8
2
1
To detach the front cover,
remove the security screw and
insert the reset key into the
bottom of the cover. With the
key firmly inserted, hinge the
bottom of the cover away from
the wall plate/ mounting box
(the reverse motion to fitting).
See Figure 8.
2
1
Resetting Opening Unit / Removal
© Ei Electronics 2007
B16073-R0-MCP401RC-UC-ENG 19/4/07 9:17 AM Page 2


Specyfikacje produktu

Marka: Ei Electronics
Kategoria: przełącznik
Model: MCP401RC

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Ei Electronics MCP401RC, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje przełącznik Ei Electronics

Instrukcje przełącznik

Najnowsze instrukcje dla przełącznik

Netgear

Netgear GS110TPP Instrukcja

15 Października 2024
ZyXEL

ZyXEL SFP-LHX1310-40-D Instrukcja

14 Października 2024
Tripp Lite

Tripp Lite B005-DPUA4 Instrukcja

11 Października 2024
Lancom

Lancom CS-8132F Instrukcja

9 Października 2024
Lancom

Lancom YS-7154CF Instrukcja

9 Października 2024
TP-Link

TP-Link Festa FS328G Instrukcja

9 Października 2024
Totolink

Totolink SW24DM Instrukcja

9 Października 2024
Totolink

Totolink SW1008P Instrukcja

9 Października 2024
Totolink

Totolink SW24G2 Instrukcja

9 Października 2024
Cudy

Cudy FS1006P Instrukcja

9 Października 2024