Instrukcja obsługi CyberPower Smart App Sinewave PR2200LCDRT2U
CyberPower
zasilacz UPS
Smart App Sinewave PR2200LCDRT2U
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla CyberPower Smart App Sinewave PR2200LCDRT2U (2 stron) w kategorii zasilacz UPS. Ta instrukcja była pomocna dla 5 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek
Strona 1/2
The LCD displays detailed
information on the UPS status
and current power conditions
to alert you to potential power
problems before the affect
your equipment. Note! All
related UPS information is
based on that you should turn
on the UPS.
Smart App Sinewave Series
PR1000LCDRT2U/PR1000LCDRTXL2U
PR1500LCDRT2U/PR2200LCDRT2U
User’s Manual
K01-0000057-05
This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read
and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install,
or operate.
CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an
outlet that is not grounded. If you need to power-drain this equipment, turn off and unplug the unit.
CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Under no circumstances this unit should be used for medical
applications involving life support equipment and/or patient care.
CAUTION! The battery can power hazardous components inside the unit, even when the AC input power is disconnected.
CAUTION! The UPS should be near the connected equipment and easily accessible.
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive
contaminants. (Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of an electric shock, do not remove the cover, except to service the battery. There are no user serviceable parts
inside, except for the battery.
CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
computer component.
CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from
the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following.
(1) UPS Unit; (1) User's Manual for UPS; (2) Rack mount Brackets; (2) Stands; (2) Skids; (1) Telephone Cable (black); (1) Emergency Power Off
Cable (gray); (1) PowerPanel® Business Edition Software CD; (2) Serial Interface Cable (DB-9); (1) USB A+B type cable; (1) Warranty
Registration Card.
OVERVIEW
The provides automatic PR1000LCDRT2U/PR1000LCDRTXL2U/PR1500LCDRT2U/PR2200LCDRT2U
voltage regulation for inconsistent utility power. The features 2060 Joules, and PR1000LCDRTXL2U
PR1000LCDRT2U / PR1500LCDRT2U/PR2200LCDRT2U features 1874 Joules of surge protection, and
provides battery backup during power outages. The PR1000LCDRT2U/PR1000LCDRTXL2U/
PR1500LCDRT2U/PR2200LCDRT2U ensures consistent power to your computer system and its included
software will automatically save your open files and shutdown your computer system during a utility power
loss.
AUTOMATIC VOLTAGE REGULATOR(AVR)
The can stabiliz the consistent utility power. The utility power PR1000LCDRT2U/PR1000LCDRTXL2U/PR1500LCDRT2U/PR2200LCDRT2U
may be damaging to important data and hardware, but Automatic Voltage Regulation helps the computer not experience dangerous voltage
levels. Automatic Voltage Regulator automatically regulates low or high voltages to keep equipment working at safe AC power levels (110/120V)
without switching to battery. Your equipment can operate normally even meet the power problems, such as, shout brownouts and blackouts. The
unit’s powerful sealed lead-acid batteries will provide power only if the incoming voltage drops below 80V or increases above 150V.
SYSTEM BLOCK DIAGRAM
HARDWARE INSTALLATION GUIDE
1. Battery charge loss may occur during shipping and storage. For the first time the UPS is used, it’s strongly
recommended to charge batteries for at least eight hours is recommended to ensure that the batteries’ maximum
charge capacity. To recharge the batteries, simply make the UPS plugs into an AC outlet.
2. When you use the included software, connect either the serial or the USB cable between the computer and
the corresponding port on the UPS. Note: If the USB port is used, the serial port will be disabled. They cannot be
used simultaneously. The computer with the PowerPanel® Business Edition S/W connects to the USB port or the
Serial port on the UPS. It can control the operating schedule, battery test, outlet, etc. and get information on the
UPS status. However, other computers with PowerPanel® Business Edition S/W can only get UPS status
information via a LAN connection.
3. With the UPS off and unplugged, connect your computer, monitor, and any externally powered data storage
device (Hard drive, Tape drive, etc.) into the outlets. DO NOT plug a laser printer, copier, space heater, vacuum,
paper shredder or other large electrical device into the UPS. The power demands of these devices will overload
and possibly damage the unit.
4. To protect a fax, telephone, modem line or network cable, connect the telephone or network cable from the
wall jack outlet to the jack marked “IN” of the UPS. Then, connect a telephone cable or network cable from the
jack marked “OUT” on the UPS to the modem, computer, telephone, fax machine, or network device.
5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air
conditioner, refrigerator, copier, etc.). Avoid using extension cords.
6. Press the power switch to turn the UPS on. The Power-On indicator light will illuminate. If an overload is
detected, an audible alarm will sound and the UPS will emit one long beep. In order to reset it, turn the unit off
and unplug some equipment from outlets. Make sure your equipment carry a load current within the unit’s safe
range, (refer to the technical specifications), and then turn the unit on.
7. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will
be automatically charging, even when the unit is switched off!
8. To always maintain an optimal battery charge, leave the UPS plugged into an AC outlet at all times.
9. Before storing the UPS for an extended period of time, turn the unit OFF. Then cover it and store it with the
batteries fully charged. Recharge the batteries every three months or so, to ensure good battery capacity and
long battery life; further, this might also prevent damage to the unit from an unlikely battery leakage.
10. The unit provides one Primary Serial Port (I), Secondary Serial Port (II), and one USB port, (paired with the
Primary Serial Port), to allow connection and communication between the unit and any attached computers. The
Primary Serial Port (I) as well as its paired USB port allow for bi-directional communication among the UPS and
the primary connected computer running the PowerPanel
® Business Edition S/W provided. The UPS can control
the computer’s shutdown in case of an emergency, and at the same time, the computer can monitor the UPS and
alter its various programmable parameters. On the other hand, secondary Serial Port II only allows the UPS to
initiate the connected computer’s graceful auto-shutdown in case of an emergency.
11. EPO (Emergency Power Off) Port:
Use the provided gray cable to connect to a special EPO contact switch. Follow the appropriate circuit diagram
below to wire the cable to your EPO configuration. The EPO remote switch is a switch installed in an outside area,
connected to the unit via an ordinary RJ-11 phone line. In case of an emergency, it can be used to immediately
cut-off power from the UPS.
FRONT / REAR PANEL DESCRIPTION
1 Power Switch.
Master on/off switch for equipment connected to the UPS.
2. Power On Indicator
Indicates that the AC utility input power’s condition is normal and
that the UPS outlets are providing power, free of surges and spikes.
3. LCD Module Display
LCD shows all the UPS information with icons and messages.
4 LCD Display Toggle Button .
Used to select among a variety of information the LCD can display.
5 Battery Backup Protected Outlets .
The unit provides a total of eight outlets with battery backup and
surge protection. They ensure that connected equipment will keep
an uninterrupted operation over a period of time, during a power
failure.
Critical /Non-critical
It is possible to program the unit in a way so that the outlet block
marked as “non-Critical”, (4 ports), will stop the provision of power
to connected equipment after a certain period of time, thus making
more runtime available for the equipment connected on the outlets
marked as “Critical”, (2 ports). In other words, the user can
establish runtime priority for certain connected equipment,
maximizing its “availability” during a prolonged power outage. This
type of control takes place with the use of the provided
PowerPanel® Business Edition S/W.
6 Input Power Cord .
Connect the AC Power cord to a properly wired and grounded
outlet.
7 Output Circuit Breaker.
This circuit breaker serves to provide output overload and fault
protection.
8 Input Circuit Breaker .
This circuit breaker serves to provide input overload and fault
protection.
Contact your dealer or call the number in this manual for information on battery replacement. The part numbers of internal battery are for RBP832
PR1000LCDRT2U/PR1000LCDRTXL2U/PR1500LCDRT2U RBP842 for PR2200LCDRT2U PR1000LCDRTX2U, . For external battery pack of ,
the part number is . BP48V45ART2U
Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of
personnel knowledgeable of batteries and their precautions . Servicing the battery can only be performed by trained personnel.
Replacement of batteries located in an OPERATOR ACCESS AREA.
CAUTION! When replacing batteries, replace with the same number of the following battery: BP7-12(BB) for PR1000LCDRT2U/
PR1500LCDRT2U/ PR1000LCDRTXL2U, PR2200LCDRT2UHR9-12(BB) for
CAUTION! Risk of Energy Hazard, 12 V, maximum 7 Ampere-hour(BP7-12) or 9 Ampere-hour battery(HR9-12). Before replacing batteries,
remove conductive jewelry such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
CAUTION! Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions.
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION! PR1000LCDRTXL2U For model can be provided with a maximum of four extension battery packs.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local
ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock.
Take the following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. Do not lay tools or metal parts on top of battery or any terminals.
4. Wear rubber gloves and boots.
5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit)
.
INPUT voltage meter: This meter measures the AC voltage from the wall outlet. The INPUT voltage readout
is used to identify the input voltage information. This can be used as a diagnostic tool to identify poor-quality
input power. Units are listed in V (Volts). When the UPS connect to any equipment, the AVR can provide a
stable 110/120V power output. In the event of a complete loss of power, severe brownout, or over voltage,
the UPS relies on its internal battery to back up to supply a consistent 110/120V output.
OUTPUT voltage meter: The Output Voltage screen measures, in real time, the AC voltage that the UPS is
providing to your connected equipment via the UPS outlets. Units are listed in V (Volts).
ESTIMATE RUN TIME: The Estimated Runtime Screen displays how many minutes of runtime can be
expected of the UPS if it were to experience a power outage. When runtime becomes shorted, the battery
capacity will decrease; (battery capacity bar indicator will be falling.) Note: The number displayed may be
less than actual runtimes for low loads.
NORMAL icon: This icon illuminates when the UPS is working under normal conditions.
BATTERY icon: When there is a severe brownout or blackout, this icon will appear followed by an alarm,
(two short beeps), indicating that the UPS is now working using its internal batteries. Once the batteries are
run out of power, (over a period of time), a constant alarm will sound. If this happens and main power has not
been restored, it is recommended that you save your files and turn off your equipment manually as soon as
possible.
Automatic Voltage Regulation (AVR) icon: This icon will appear when the unit is automatically regulating
low or high AC input line voltage conditions, without resulting to the use of battery power.
SILENT MODE icon: This icon appearing indicates that the buzzer will not be beeping while in battery operating mode. During Silent mode, the
unit’s alarm does not sound until the Battery Capacity falls to < 20%.
OVER LOAD icon: This icon will appear followed by an alarm, indicating that an overload condition has been reached. To recover from the
overload condition, start unplugging your equipment from the UPS outlets until the icon disappears and the alarm stops.
FAULT icon: When activated indicates a system fault error. Please refer to the troubleshooting table for possible causes and solutions.
BATT. CAPACITY meter: BATT. CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of battery capacity.
LOAD CAPACITY: Load CAPACITY is shown as a bar chart; each segment indicates approximately a 20% of load capacity.
IMPORTANT SAFETY WARNINGS
INSTALLING YOUR UPS SYSTEM
LCD STATUS DEFINITION
BATTERY REPLAC
E
MENT
9. USB port.
This is a connectivity port allowing communication and control among
the UPS and the connected computer. You should install on your
computer the PowerPanel® Business Edition S/W appropriate to the
operating system you are using.
10. Protected Communication Ports RJ11/RJ45
Ports protect standard single line modem, fax, telephone line or network
cable.
11. Site Wire Fault Indicator
This LED will illuminate to warn the user that a wiring problem exists
within the AC receptacle, such as a bad ground or reversed wiring. If
illuminated, disconnect all equipment and contact an electrician to
ensure outlet is properly wired.
12. Coax/Cable/DSS Surge Protection
The Coax/Cable/DSS surge protection ports will protect any cable
Modem, CATV converter or DSS receiver.
13. Serial Port I
Serial port allows connection and communication between the UPS and
the computer.
14. Serial Port II
Serial Port II relays information to equipment that can utilize a contact
closure UPS.
15. SNMP/HTTP Network slot
Remove the cover panel to install optional SNMP that allows remote
monitoring and control of your UPS on a network.
16. EPO (Emergency Power Off) Port:
Allow for an emergency UPS Power-Off from a remote location.
BASIC OPERATION
When you first receive the
unit, plug in the unit to fully
charge the battery.
The primary computer with
PowerPanel® Business
Edition software connected
to the UPS with either a
serial cable or a USB cable.
The equipment can
read information
via dry contact.
Dry connect is controlled by the PowerPanel
®
Software, please
go to www.cyberpowersystems.com for free download.
* Both USB and Serial cannot be used simultaneously. NOTE:
Unplug the unit and turn Power
Off when first connecting your
computer and peripherals.
1. Remove the front panel on the
right side. 2. Remove the two retaining screws of
the cable protection cover then remove
the cover.
3. Remove the two retaining screws of
the cable connectors.
4. Disconnect the black and red
cable
.
5. Remove the three retaining screws. 6. Pull out the old battery pack and replace.
Reassemble the retaining screws, covers, black and
red cable, and front panel in the reverse sequence
of the above steps. Recharge the unit for 4-8 hours
to ensure maximum UPS battery runtime.
1 YEAR LIMITED WARRANTY
TECHNICAL SPECIFICATIONS
TROUBLE SHOOTIMG
LCD STATUS AND SETUP FUCTIONS
1. General Mode:
a. Press the “Display-Toggle” button to check the status of the UPS.
b. Press and hold the “Display-Toggle” button for 4 seconds,
If the machine is in the Battery Mode with active alarm, it will become silent.
If the machine is in the Line Mode, a self- diagnostic test will take place.
c. If the “Display-Toggle” button remains untouched for over 30 seconds, the
LCD backlight will turn off automatically.
2. Set-up Mode
Step 1: Hold the “Display-Toggle” button for 10 seconds to enter the UPS
Set-Up Mode.
Step 2: By pressing the Display toggle, users can switch between setup
functions. Some User Configurable functions are as follows:
a. Delay Time: The time delay between switching from Battery Mode to Line Mode. There are 9 different settings. The default
setting is 0 minutes.
b. Battery Pack Numbers: This function provides the estimated UPS runtime using various numbers of battery packs. The default
setting is 0.
c. Static Frequency Tolerance: There are 6 settings (1,2,4,6,8,10 %), and the default setting is +/-6%. Functional description: The
setting may be adjusted to the quality of the electricity in use.
d. Slew rate: Also known as Dynamic Frequency Tolerance. There are 5 different settings (0.25,0.5,1,2,4 Hz/Sec). The fault value
is 4Hz/sec. “Slew Rate” indicates the tolerance of a device in accepting frequency variance. Lower Functional Description:
“Slew Rate” results in less tolerance but better protection for the connected load and vice versa.
e. Low Battery Shutdown Voltage: This function will adjust the UPS shutdown point according to the battery’s remaining capacity.
The settable items are sorted by unit as in the following table :
Step 3: Press and hold the display-toggle for 4 seconds. When the icons blink, the
value of each item is changed by slightly pressing the toggle.
Step 4: To save the value and return to general mode, press and hold the toggle for
4 seconds.
Note! If the UPS is left idle for over 30 seconds during setup, it will turn off the
backlight and return to general mode automatically.
Note! If the user does not want to save the new settings and return to the
general mode, there are two methods:
1. Wait for the backlight to turn off, or,
2. By pressing and holding the “Display-toggle” key for 10 second.
Problem Possible Cause Solution
Outlet do not provide power
to equipment
Circuit breaker has tripped
due to an overload.
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by depressing the
button, and then turn the UPS on.
Batteries are discharged Recharge the unit for at least 4 hours
Unit has been damaged by a
surge or spike.
Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
Uncritical outlets have
turned off automatically
due to an overload
Push the toggle button to make the uncritical outlets turn on.
The UPS does not perform
expected runtime.
Battery not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is degraded Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
The UPS will not turn on.
The on/off switch is designed
to prevent damage by rapidly
turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the
UPS on.
The unit is not connected to
an AC outlet. The unit must be connected to a 110/120v outlet.
The battery is worn out. Contact CyberPower Systems about replacement batteries at
tech@cpsww.com
Mechanical problem. Contact CyberPower Systems at tech@cpsww.com
PowerPanel® Personal
Edition is inactive
The serial cable or USB cable
is not connected.
Connect the cable to the UPS unit. You must use the cable that
came with the unit.
The cable is connected to the
wrong port. Try another port of your computer
The unit is not providing
battery power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS back on. This should reset
the unit.
The serial cable is not the
cable that was provided
with the unit.
You must use the cable included with the unit for the
software
Additional troubleshooting information can be found at www.cyberpowersystems.com/support.htm
Model PR1000LCDRT2U PR1500LCDRT2U PR2200LCDRT2U PR1000LCDRTXL2U
Capacity(VA) 1000 1500 2170 1000
Capacity(Watts) 700 1000 1600 700
Input
Input Voltage Range 80Vac-150Vac
Input Frequency Range 50/60Hz+/-3Hz(auto sensing)
Output
On Battery Output Voltage Pure Sine Wave at 120Vac+/-5%
On Battery Output Frequency 50/60 Hz +/-0.1Hz
Transfer Time(Typical) 4 ms
Overload Protection On Utility: Circuit Breaker, On Battery: Intemal Current Limiting
Surge Protection and Filtering
Lightning/Surge Protection Yes
Internet Ready(DSL/Phone/
FAX/Modem Protection) RJ11/RJ45(One In/One Out)
Physical
Output Receptacles 8 6
Dimensions(in) 2U Rack, 17.1’’ x 15.3’’x 3.5’’
Weight (lb) 58 60 66 66
Battery
Sealed Maintenance Free Lead
Acid Battery 12V / 7.0AHx4 12V / 9.0AHx4 12V / 7.0AHx4
Extended runtime
Hot Swappable External Battery Yes
Warning Diagnostics
Indicators Power On, Wiring Fault, LCD Display (Using Battery, AVR, Load Level, Battery Level)
Audible Alarms On Battery, Low Battery, Overload
Environmental
Operating Temperature 32 to 104 ( 0 to40 ) ℉ ℉ ℃ ℃
Operating Relative Humidity 0 to 95% Non-Condensing
Communication
PowerPanel ®Business Edition
Windows 98/ME/NT/2000/XP, Vista
Management
Self-Test Manual Self-Test
Auto-Charger/ Auto-Restart Yes
COM Interface True RS232 x1+ Dry connector p2-x1
Built-in USB Interface Yes
SNMP/ HTTP Network Slot Yes
Safety Approvals UL1778,cUL107,FCC/Doc Class B
GreenPower UPS™
The CyberPower GreenPower UPS™ cuts UPS energy costs by up to 75% compared to the conventional UPS
circuits. Conventional UPS systems pass power through a transformer to provide normal output voltage to protected
devices. By contrast, the GreenPower UPS™ circuitry bypasses the transformer when utility power is normal,
significantly increasing the power efficiency of the UPS. As a result, a GreenPower UPS™ produces less heat and
uses less energy reducing energy costs.
When utility power is abnormal, the GreenPower UPS™ operates like a normal UPS. Since utility power operates
normally 88% of the time, the GreenPower UPS™ operates primarily in its cost-cutting bypass mode.
By purchasing a recertified CyberPower UPS in the United States or Canada, the original end-user consumer purchaser (referred to as the "Initial
Customer") receives a 1 Year limited warranty.
1 Year Limited Warranty. The Initial Customer receives a 1 Year limited warranty explained below (referred to as the "1 Year Limited Warranty")
for the UPS (referred to as the "UPS").
If you are the Initial Customer, you are asked to read the following terms and conditions carefully before using the UPS. By using the UPS you
consent to be bound by and become a party to the terms and conditions of the 1 Year Limited Warranty provided in this document. If you do not
agree to the terms and conditions of the 1 Year Limited Warranty, you should return the UPS for a full refund prior to using it.
CyberPower warrants to you, the Initial Customer, that the UPS will be free from defects in material and workmanship for 1 Year from the date of
original purchase, subject to the terms of this 1 Year Limited Warranty. This 1 Year Limited Warranty gives you specific rights and you may have
other rights, which vary from State to State or Province to Province.
Making a 1 Year Limited Warranty Claim.
To make a 1 Year Limited Warranty claim, you must do the following:
1. Provide proof of purchase (for example, a sales receipt) that establishes you as the Initial Customer (the original end-user consumer purchaser)
of the UPS and prove that the UPS was purchased within 1 Year of the failure of the UPS.
2. Call CyberPower at (877) 297-6937 (toll free), write to CyberPower at 4241 12th Ave E, Suite 400, Shakopee, MN 55379, or send us an e-mail
to tech@cyberpowersystems.com within TEN (10) days of the failure of the UPS.
3. When you contact CyberPower, identify the UPS by model number, serial number, provide the purchase date, and request Return Materials
Authorization (RMA) information from CyberPower.
4. Pack and ship the UPS to CyberPower as instructed in your RMA. Show the RMA code on the shipping label or include it with the UPS. You
MUST prepay all shipping costs and you are responsible for packaging and shipment.
What CyberPower Will Do After You Make a Claim.
CyberPower will inspect and examine the UPS. If the UPS is defective in material or workmanship, and you have complied with the terms of this
1 Year Limited Warranty, CyberPower will:
1. Repair or replace the UPS with a new or recertified UPS and return it to you at CyberPower's expense, or,
2. Refund to you the full purchase price you paid for the UPS (purchase receipt showing price paid is required) if CyberPower is unable to or
decides not to repair or replace the UPS (if defective) within a reasonable time with a new or recertified UPS.
Exclusion of Consequential and Other Damages
Your exclusive remedies and CyberPower’s sole obligations are those provided by this 1 Year Limited Warranty. This exclusion of other express
warranties applies to written and oral express warranties.
Any Implied Warranty of Merchantability or of Fitness for a Particular Purpose, if applicable to the UPS, is limited in duration to 1 Year from the
date of original purchase by the Initial Customer. This provision shall NOT create any Implied Warranty or Merchantability or of Fitness for a
Particular Purpose that would not otherwise apply to the UPS. NOTE: Some States and Provinces do not allow limitations on how long an
implied warranty lasts, so the above limitation may not apply to you.
This 1 Year Limited Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the UPS, a
UPS in transit, in shipment, or in storage, improper operation or maintenance, or use with items not designed or intended for use with the UPS
(such as laser printers, copiers, shredders, appliances, devices with motors or heating elements, etc.). You must contact CyberPower within ten
(10) days of the failure of the UPS in order to make a warranty claim.
CyberPower excludes any liability for personal injury under the 1 Year Day Limited Warranty. CyberPower excludes any liability for direct,
indirect, special, incidental, or consequential damages, whether for damage to or loss of property, damage to equipment connected to the UPS,
loss of profits, business interruption, or loss of information or data. This exclusion applies even though damage or loss is caused by negligence
or other fault. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the above
limitation may not apply to you.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT OR OTHER HIGH RISK ACTIVITIES.
CyberPower does not sell the UPS for use in high-risk activities. The UPS is not designed or intended for use in hazardous environments
requiring fail-safe performance, including the operation of nuclear facilities, aircraft navigation or communication systems, air traffic control,
weapons systems, life support or medical applications, or for use in any circumstance in which the failure of the UPS could lead directly to death,
personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively,
"High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities. CyberPower does not
authorize use of any UPS in any High Risk Activities. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF A CYBERPOWER UPS.
This 1 Year Limited Warranty is governed by the laws of the United States and the State of Minnesota, without reference to conflict of law
principles.
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
Contact Information: Cyber Power Systems (USA), Inc., 4241 12th Ave E, Suite 400, Shakopee, MN 55379, (877) 297-6937 (toll free).
CyberPower is the warrantor under this 1 Year Limited Warranty. You may also visit CyberPower on the Internet at
www.cyberpowersystems.com.
FCC Notice
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1)This device
may not cause harmful interference, and (2) this device must accept any interference received, including interference that
may cause undesired operation.
WARNING!! This equipment has been tested and found to comply with the limits for a Class B Digital Device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment
generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the following measures: (1) Reorient or relocate the receiving antenna.
(2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to
which the receiver is connected. (4) Consult the dealer or an experienced radio/TV technician for help. Any special accessories needed for
compliance must be specified in the instruction.
Item Unit
1 Input Voltage V
2 Output Voltage V
3 Output Frequency Hz
4 Load Kw
5 Estimate Run Time Min
6 Load Capacity %
7 Battery Capacity %
8 Centigrade ℃
9 Fahrenheit ℉
Items Unit
Delay Time Min
Battery Pack Numbers A
Static Frequency Tolerance %
Slew Rate Hz
Battery Shutdown Voltage V
CYBERPOWER GREENPOWER
UPS
™
TECHNOLOGY
The Class B digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulation.
Cet appareil numerique de la class B respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada
Specyfikacje produktu
Marka: | CyberPower |
Kategoria: | zasilacz UPS |
Model: | Smart App Sinewave PR2200LCDRT2U |
Kolor produktu: | Czarny |
Typ wyświetlacza: | LCD |
Wysokość produktu: | 44 mm |
Szerokość produktu: | 438 mm |
Głębokość produktu: | 400 mm |
Waga produktu: | 28600 g |
Długość kabla: | 3.05 m |
Certyfikat środowiskowy (zrównoważonego rozwoju): | RoHS |
Czas ładowania: | 8 h |
Certyfikaty: | UL1778, cUL 107.1, FCC DOC B |
Napięcie operacyjne wejścia (maksymalne): | 150 V |
Technologia baterii: | Ołowiany (VRLA) |
Ilość portów Ethernet LAN (RJ-45): | 2 |
Zakres temperatur (eksploatacja): | 0 - 35 °C |
Zakres wilgotności względnej: | 0 - 95 % |
Układ: | Rackmount/Tower |
Liczba portów USB 2.0: | 1 |
Rodzaj baterii: | 12V/9AH |
Częstotliwość danych wejściowych: | 50/60 Hz |
Diody LED: | Power, Power fail |
Dołączone oprogramowanie: | PowerPanel Business Edition |
Dopuszczalna wysokość podczas eksploatacji (n.p.m.): | 0 - 3000 m |
Moc rzeczywista: | 1600 W |
Pojemność stelaża: | 2U |
Szeregowe porty komunikacyjne: | 2 |
Maksymalna możliwa do konfiguracji moc: | 2.17 kVA |
Napięcie operacyjne wejścia (minimalne): | 80 V |
Napięcie operacyjne wyjścia (maksymalne): | 120 V |
Napięcie operacyjne wyjścia (minimalne): | 120 V |
Wartość znamionowa udaru energii: | 1780 J |
Ilość gniazd sieciowych: | 8 x gniazdo sieciowe |
Typy wyjść AC: | NEMA 5–20P |
Porty modemu rj-11: | 2 |
Typowy czas podtrzymania przy połowie obciążenia: | 16 min |
Typowy czas podtrzymania przy pełnym obciążeniu: | 6 min |
Dopuszczalna wysokość (n.p.m.): | 0 - 15000 m |
Ilość komór baterii: | 4 |
Tryby alarmu dźwiękowego: | Wymiana baterii |
Ilość faz: | 1 |
Kasetka na zapasowe baterie: | BB Battery - HR9-12 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z CyberPower Smart App Sinewave PR2200LCDRT2U, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje zasilacz UPS CyberPower
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
Instrukcje zasilacz UPS
- zasilacz UPS APC
- zasilacz UPS Tripp Lite
- zasilacz UPS FSP
- zasilacz UPS Emerson
- zasilacz UPS Adj
- zasilacz UPS PowerWalker
- zasilacz UPS Ditek
- zasilacz UPS Murr Elektronik
Najnowsze instrukcje dla zasilacz UPS
19 Września 2024
9 Lipca 2024
9 Lipca 2024
17 Czerwca 2024
17 Czerwca 2024
2 Czerwca 2024
2 Czerwca 2024
2 Czerwca 2024
2 Czerwca 2024
30 Maja 2024