SmartOnline®
Rack/Tower Mount On-Line UPS
Systems
Not suitable for mobile applications.
Models:
SU750RTXL2U (Series Number: AGPS5542)
SU1000RTXL2UA (Series Number: AGPS5180)
SU1500RTXL2UA (Series Number: AGPS5194)
SU2200RTXL2UA (Series Number: AGPS5183)
SU3000RTXL2U, SU3000RTXR3U (Series Number: AGPS5204)
SU3000RTXR3UHW (Series Number: AGPS7039)
Important Safety Instructions 2
Installation 4
Basic Operation 9
Troubleshooting 13
Battery Replacement 14
Storage and Service 15
Product Registration 16
Regulatory Compliance 16
Español 17
Français 33
Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
17-05-032-932471.indb 1 5/23/2017 1:41:30 PM
2
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed during the
installation, operation and storage of all Tripp Lite UPS Systems. Failure to heed these
warnings may affect your warranty.
UPS Location Warnings
• Install your UPS indoors, away from excess moisture or heat, conductive contaminants, dust
or direct sunlight.
• For best performance, keep the indoor temperature between 32º F and 104º F
(0º C and 40º C).
• Leave adequate space around all sides of the UPS for proper ventilation.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in
this manner will seriously inhibit the unit’s internal cooling, eventually causing product
damage not covered under warranty.
UPS Connection Warnings
• Connect your UPS directly to a properly grounded AC power outlet. Do not plug the UPS into
itself; this will damage the UPS.
• Do not modify the UPS plug, and do not use an adapter that would eliminate the UPS ground
connection.
• Do not use extension cords to connect the UPS to an AC outlet.
• If the UPS receives power from a motor-powered AC generator, the generator must
provide clean, filtered, computer-grade output.
CAUTION: Install in accordance with National Electrical Code standards ANSI/NFPA 70 and
Canadian Electrical Code, Part I, C22.1. Be sure to use the proper overcurrent branch
protection for the installation, in accordance with the plug/equipment rating.
CAUTION: Short Circuit backup protection and overcurrent protection is provided by the
building installation for permanently connected models.
CAUTION: To reduce the risk of fire, connect only to a circuit-provided branch circuit
overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA 70 and
the Canadian Electrical Code, Part I, C22.1. Use 30A maximum overcurrent protection for
models SU3000RTXL2U and SU3000RTXR3U (series AGPS5204), and SU3000RTXR3UHW
(series AGPS7039).
• Your UPS may be equipped with a terminal block for permanent connection to AC Mains.
Installation is by qualified service personnel only. When connecting to permanently connected
units use only copper conductors 10AWG with a minimum temperature rating 165°F (75°C).
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
17-05-032-932471.indb 2 5/23/2017 1:41:30 PM
3
Important Safety Instructions
Equipment Connection Warnings
• Use of this equipment in life support applications where failure of this equipment can
reasonably be expected to cause the failure of the life support equipment or to significantly
affect its safety or effectiveness is not recommended.
• Do not connect surge protectors or extension cords to the UPS output. This may damage the
UPS and affect the surge protector and UPS warranties.
Battery Warnings
• Batteries can present a risk of electrical shock and burn from high short-circuit current.
Observe proper precautions. Do not dispose of the batteries in a fire. Do not open the UPS or
batteries. Do not short or bridge the battery terminals with any object. Unplug and turn off the
UPS before performing battery replacement. Use tools with insulated handles. There are no
user-serviceable parts inside the UPS. Battery replacement should be performed only by
authorized service personnel using the same number and type of batteries (Sealed Lead-
Acid). The batteries are recyclable. Refer to your local codes for disposal requirements or visit
http://www.tripplite.com/support/recycling-program for recycling information. Tripp Lite offers a
complete line of UPS System Replacement Battery Cartridges (R.B.C.).Visit Tripp Lite on the
Web at http://www.tripplite.com/products/battery-finder/ to locate the specific replacement
battery for your UPS.
17-05-032-932471.indb 3 5/23/2017 1:41:30 PM
Specyfikacje produktu
Marka: | Tripp Lite |
Kategoria: | zasilacz UPS |
Model: | SmartOnline SU1500RTXL2UA |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Tripp Lite SmartOnline SU1500RTXL2UA, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje zasilacz UPS Tripp Lite
7 Maja 2024
6 Maja 2024
6 Maja 2024
Instrukcje zasilacz UPS
- zasilacz UPS APC
- zasilacz UPS FSP
- zasilacz UPS Emerson
- zasilacz UPS CyberPower
- zasilacz UPS Adj
- zasilacz UPS PowerWalker
- zasilacz UPS Ditek
- zasilacz UPS Murr Elektronik
Najnowsze instrukcje dla zasilacz UPS
19 Września 2024
9 Lipca 2024
9 Lipca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024