Owner’s Manual
EnviroSense2
Leak Detection Sensor
Model: E2SLD
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2017 Tripp Lite. All rights reserved.
PROTECT YOUR INVESTMENT!
Register your product for quicker service and ultimate peace of mind.
You could also win an ISOBAR6ULTRA surge protector—a $100 value!
www.tripplite.com/warranty
1 Introduction 2
1-1 Parts List 2
1-2 Tools Required 2
1-3 Specifications 2
2 Important Safety Instructions 2
3 E2SLD Installation 3
3-1 Mounting the Leak Detection Sensor 3
3-2 Wiring the Sensor 3
4 Connecting to WEBCARDLX and E2MTHDI 4
5 Warranty and Product Registration 4
Español 5
Français 9
Русский 13
2
1-1 Parts List
A Water Sensor
B Cover
C 22 AWG Cable, 15 ft. (4.6 m)
D Owner’s Manual
E Double-Sided Adhesive Tape
1-2 Tools Required
A Wire Cutters
B Wire Strippers
C Phillips Screwdriver
D Flathead Screwdriver
1-3 Specifications
Electrical
Voltage: 5~24V DC
Standby Current: 1 mA
Alarm Current: 200 mA
Contact Closure Type: Normally Open
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that must be followed during the installation and operation of the products
described in this manual. Read all instructions and warnings thoroughly before attempting installation. Failure to comply may
invalidate the warranty and cause property damage and/or personal injury.
1 – Introduction
2 – Important Safety Instructions
The E2SLD leak detection sensor is designed to detect water leakage or leakage of any electrically conductive fluid. The E2SLD supports a
Normally Open contact closure connection. It must be used with a compatible Tripp Lite UPS or PDU equipped with the WEBCARDLX or
LX Platform interface, along with a compatible E2 environmental sensor module (both are sold separately).
Install in a controlled indoor environment, away from moisture, temperature extremes, flammable liquids and gasses, conductive contami-
nants, dust and direct sunlight.
Provide suitable grounding in accordance with all applicable electrical wiring regulations.
Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life
support equipment or to significantly affect its safety or effectiveness is not recommended.
A
A B C D
B
C
DE
3
3 – E2SLD Installation
The E2SLD leak detection sensor should be mounted on a raised floor near cooling units and other applications where water and other
electrically conductive fluid leakage detection can occur.
Approximately 1” (25 mm)
Approximately 0.38” ( )10 mm
3-1 Mounting the Leak Detection Sensor
The E2SLD supports mounting by screws, double-sided tape, or adhesive.
1 Mark the intended location of the E2SLD with the probes facing
downward approximately 1/8” (3 mm) above the floor.
2 Mount the sensor to a wood, metal, or concrete* surface using the
provided #6 screws or double-sided tape.
*A user-supplied adhesive will be necessary for concrete surface mounting.
3-2 Wiring the Sensor
1 Before attaching the wire to the switch, use wire cutters to clip to
desired length (if necessary).
2 Use wire strippers to cut back the covering of the two wires and
remove a small amount of insulation from the end of each wire
(do not cut through the insulation into the wire itself).
3 Correct polarity is required. Twist the tinned or bare ends of
each wire and place the red wire on the “+” positive marked
terminal and the black wire on the “-” negative marked terminal.
Wrap them clockwise under the head of each screw on the
sensor. Tighten the screw by turning it clockwise.
4 Use cable ties and adhesive cable tie holders (user-provided) to
secure the entire length of the wire.
5 Route the wire away from the sensor and attach the other ends
to one of the input connections on the compatible E2MTHDI
module, noting the polarity markings that were wired at the
sensor.*
*Each E2MTHDI input contacts will have “+” positive polarity markings to
ensure proper wiring connection.
FLOOR
1/8” (3 mm)


Specyfikacje produktu

Marka: Tripp Lite
Kategoria: detektor
Model: E2SLD

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Tripp Lite E2SLD, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje detektor Tripp Lite

Tripp Lite

Tripp Lite E2SLD Instrukcja

23 Sierpnia 2024

Instrukcje detektor

Najnowsze instrukcje dla detektor