Doc # INT-100132-001
Part No. 191556 Rev. 4
DITEK Technical Support Available 24/7
1-888-472-6100 www.ditekcorp.com
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALLATION
This Surge Protective Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to communication loop circuits that have been isolated
from the public switched telephone network or where the SPD is directly connected to the
electronic device. Maximum protection will only be achieved if the SPD is properly installed.
Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable
requirements of the NEC and the following instructions. These devices are only to be employed on
communication loop circuits which have been isolated from the Public Switched Telephone Network.
APPLICATION
DTK-MB10 base can be installed inside a 4”x4” electrical boxes and other locations where there is a space
constraint. This base is available as a 1 up array (standard) or 2 through 5 up array for multiple pair
terminations at one point of use. Specify DTK-2MB, 3MB, 4MB or 5MB for 2 through 5 up arrays.
DTK-2MHLPxxFWB surge module is for hardwired series installations for voltages ranging from 5-75 Volts
on circuits that operate at less than 1 Amp.
DTK-2MHLPxxBWB surge module is for hardwired series installations for voltages ranging from 5-75 Volts
on circuits that operate at less than 5 Amps.
DTK-2MHTP surge module is for hardwired series installations for dialer circuits and POTS lines for
communication circuits.
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of the unit.
Improper installation voids the warranty.
MB BASE INSTALLATION
1. Turn off the power at the circuit to be protected before beginning installation.
2. Securely mount the snap track between the field wiring and your equipment to be protected. Use the two #8 screws
provided to fasten the snap track.
3. Connect ground to the ground terminal using a minimum of 14 AWG wire, make this conductor as short as possible.
Ground Resistance Rule: Max ground resistance is 25 Ohms, 5 Ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
4. Connect the supply/field wiring to the side of the MB base. Connect the 1st pair to UNPROTECTED
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
5. Connect the equipment wiring to the side of the MB base. Connect the 1st pair to PROTECTED
position 1+ and 1- , than the 2nd pair to position 2+ and 2-.
6. Make sure the supply/field wiring and equipment wiring conductors do not occupy UNPROTECTED PROTECTED
the same space or conduits.
7. Make sure the wire distance from the base to protected equipment is about 3’ of conductor length. This can be a
coiled service loop if necessary.
MODULE INSTALLATION
Insert the module into the base making sure the polarizing keys in the block are aligned with the notches cut into
the edge card printed circuit board.
8. After all connections have been made and no hazards exist, restore power.
Drawn By: RMitchell 3-3-11
Revised By: RMitchell 6-14-16
SUPPLY WIRING
or FIELD WIRING
GROUNDING
#14AWG MIN.
Pair 1
Pair 2
GND Pair 1
Pair 2
ALLOW FOR 3’ OF CONDUCTOR LENGTH
BETWEEN BASE AND PROTECTED EQUIPMENT
DTK-2MHLP BASE
EQUIPMENT WIRING
3’ SERVICE LOOP
INSTALL INSTRUCTIONS
DTK-2MHLPxxFWB Series, DTK-2MHLPxxBWB Series,
DTK-2MHTPWB, MB10, 2MB-5MB, and DTK-2MHLP Module
DITEK Technical Support Available 24/7
1-888-472-6100 www.ditekcorp.com
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALLATION
Illustrations Page
DTK-MB10
1+
1-
2
+
2-
UN
P
R
O
T
E
CT
E
D
GN
D
PR
O
TE
CT
ED
Snap Track
1.50
3.25
1.03
1.15
INSTALL INSTRUCTIONS
DTK-2MHLPxxFWB Series, DTK-2MHLPxxBWB Series,
DTK-2MHTPWB, MB10, 2MB-5MB, and DTK-2MHLP Module
Doc # INT-100132-001
Part No. 191556 Rev. 4
Drawn By: RMitchell 3-3-11
Revised By: RMitchell 6-14-16
DTK-2MHLPxxFWB
DTK-2MHLPxxBWB
DTK-2MHTPWB
DTK-2MB DTK-4MB
DTK-3MB DTK-5MB


Specyfikacje produktu

Marka: Ditek
Kategoria: nieskategoryzowany
Model: DTK-MB10

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Ditek DTK-MB10, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Ditek

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Meec Tools

Meec Tools 010-084 Instrukcja

6 Października 2024
Outwell

Outwell Scenic Road 250 Instrukcja

5 Października 2024
Impact

Impact QuikBalance Instrukcja

4 Października 2024
Impact

Impact CA-112 Instrukcja

4 Października 2024
Impact

Impact LS-BHA Instrukcja

4 Października 2024
Impact

Impact LKB-5C Instrukcja

4 Października 2024
Impact

Impact RST-001 Instrukcja

4 Października 2024