Instrukcja obsługi Ditek D50-CM


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Ditek D50-CM (2 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 20 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
INSTALL INSTRUCTIONS
D50-CM
DITEK Technical Support Available 24/7
1-888-472-6100
www.ditekcorp.com
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALLATION
This Surge Protective Device (SPD) is a high performance device, designed to provide protection
for sensitive electronic loads connected to service panels, fire panels, or where the SPD is
directly connected to the electronic device. Maximum protection will only be achieved if the SPD
is properly installed. Please read and follow the installation instructions carefully.
NOTICE: This SPD should be installed and grounded, by a licensed contractor, per the applicable
requirements of the NEC.
APPLICATION:
Type 1 SPD for hardwired parallel installations on 120/240 VAC Split phase
circuits, connected on the line side of the main breaker or disconnect.
Type 2 SPD for hardwired parallel installations on 120/240 VAC Split phase circuits, connected on
the load side of the main breaker or disconnect.
Expected system voltages: L1-G = 120VAC, L2-G = 120VAC, L1-L2 = 240VAC
INSTRUCTIONS:
Caution: Measure all voltages to insure applied voltage does not exceed the voltage rating of
the unit. Improper installation voids the warranty. This unit must be connected in parallel
with the equipment to be protected.
NOTE: Suitable for use on a circuit capable of delivering not more than 100,000 rms
symmetrical amperes. This SPD contains no serviceable parts.
Pre Install Actions:
1. Turn off main power before beginning the installation.
2. Remove the front cover from panel.
3. Remove the 3/4" knockout on the side of the panel box closest to the point of install.
4. Unscrew nut from unit, leaving the washer in place.
5. Feed all wires through the knockout hole then through nut. Tighten the nut to secure the unit
to the panel. Make sure the washer is sandwiched between the unit and the panel.
6. Connect the green (Ground) wire to the ground bus.
7. Always have one common ground per system to eliminate the possibility of a differential in
ground potentials.
8. This device features an internal protection that will disconnect the surge protective component
but will maintain power to the load - now unprotected. If this situation is undesirable for the
application, follow the manufacturer’s instructions for replacing the device.
Ground Resistance Rule: Max ground resistance is 25 ohms, 5 ohms or less is optimum.
This cannot be an assumed value and must be measured to assure proper grounding.
Type 1 Installation:
Intended for installation between the secondary of the service transformer and the line side of the
service equipment overcurrent device, as well as the load side, including watt-hour meter socket
enclosures and intended to be installed without an external overcurrent protective device.
Connect the phase (Black) wires to the line side of the main, making sure the leads are as
short as possible (Ground being the shortest). Refer to the Illustrations Page for wiring diagrams.
Type 2 Installation:
Intended for installation on the load side of the service equipment overcurrent device.
Connect the phase (Black) wires to the load side of the main, making sure the leads are as short as
possible (Ground being the shortest). For best performance connect the phase wires to a 2-pole,
20A circuit breaker rated 240V minimum. Refer to the Illustrations Page for wiring diagrams.
Post Install Actions:
After all connections have been made and no hazards exist, replace cover and restore power.
Maintenance:
Perform periodic inspections to verify the indicator LED is on. If the LED is off than surge protection is
compromised and the unit must be replaced.
Doc # INT-100160-001
Part No. 191587 Rev. 2
Drawn By: R. Mitchell 2-6-15
Approved By: H. Tu 3-17-15
Revised By: K. Nguyen 3-17-15
INSTALL INSTRUCTIONS
D50-CM
DITEK Technical Support Available 24/7
1-888-472-6100 www.ditekcorp.com
DITEK Corporation
ONE DITEK CENTER
1720 Starkey Road
Largo, FL 33771
INSTALLATION
Illustrations Page
Doc # INT-100160-001
Part No. 191587 Rev. 2
Drawn By: R. Mitchell 2-6-15
Approved By: H. Tu 3-17-15
Revised By: K. Nguyen 3-17-15
GROUND BUSS
GREEN WIRE
BLACK WIRES
DITEK UNIT
120 VAC
120 VAC
240 VAC
Line
Line
Ground
Black
Green
Black
Wiring Diagram
HVACR Disconnect Installation
Panel Installation
Ground Buss
Green Wire
Neutral Buss
2-Pole, 20A
Circuit Breaker
Main Breaker
Black Wires


Specyfikacje produktu

Marka: Ditek
Kategoria: nieskategoryzowany
Model: D50-CM

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Ditek D50-CM, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Ditek

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Meec Tools

Meec Tools 010-084 Instrukcja

6 Października 2024
Outwell

Outwell Scenic Road 250 Instrukcja

5 Października 2024
Impact

Impact QuikBalance Instrukcja

4 Października 2024
Impact

Impact CA-112 Instrukcja

4 Października 2024
Impact

Impact LS-BHA Instrukcja

4 Października 2024
Impact

Impact LKB-5C Instrukcja

4 Października 2024
Impact

Impact RST-001 Instrukcja

4 Października 2024