Instrukcja obsługi ACV BMV


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla ACV BMV (48 stron) w kategorii Różne sterowanie klimatem. Ta instrukcja była pomocna dla 5 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/48
BMV3 / BMV4 / BMV5 : 662Y1000 • A
en
1
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5
BMV
INSTALLATION, OPERATION AND
MAINTENANCE INSTRUCTIONS
en
2
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5 : 662Y1000 • A
Dear customer,
We are pleased that you have decided to purchase an ACV
burner.
The BMV burner model is a modern generation ame burner.
The advantage of this burner construction is the extensive
energy saving operation with very low emissions (Sampling
test according to EN 267:1999-11 Class 3, German environ-
mental label “Blue Angel” according to RAL-UZ 9, Sampling
test according to the Swiss Emissions Regulation LRV).
Every burner is checked in the scope of a thorough nal in-
spection. In addition to the hydraulic and electrical parame-
ters, the appearance of the ame is also inspected.
The warranty period as of the date of purchase (receipt date)
is 2 years.
Please note that the installation, start up and inspection tasks
must be accomplished by a trained technician. The installa-
tion and operating instructions that are provided contain im-
portant information to this purpose.
We recommend a yearly inspection of the burner by a trained
technician to guarantee continuous energy saving and low
emission operation.
Table of contents
1. Technical data 3
1.1 Burner performance 3
1.2 Certification 3
1.3 Operating range 3
1.4 Fuel 3
1.5 Electrical data 3
1.6 Burner dimensions 3
1.7 Acoustic emissions 3
1.8 Burner components 3
2. Assembly 4
2.1 Assembly dimensions 4
2.2 Installing the burner 4
2.3 Service position 4
2.4 Change of nozzle 4
2.5 Nozzle table 4
2.6 Combustion chamber - minimum dimensions 4
2.7 Oil supply 5
2.8 Oil pipes dimensions 5
2.9 Flexible oil line connection of the burner 6
2.10 Electrical connection 6
2.11 General inspections 6
3. Initial operating and maintenance 6
3.1 Adjusting burner 7
3.2 Chimney draft 7
3.3 Combustion air 7
3.4 Flame monitoring 7
3.5 Oil pressure 8
3.6 Final and safety tests 8
3.7 Chimney 8
4. Basic adjustment table 9
5. Electric wiring diagram : LOA24 10
6. Burner quick service 11
7. Troubleshooting 12
Figure 3 — BMV3 / BMV4
Figure 2 — BMV3 / BMV4 / BMV5
Figure 1
en
3
EN
FR
NL
ES
IT
DE
PL
RU
BMV3 / BMV4 / BMV5 : 662Y1000 • A
Figure 6
Figure 5
Figure 4
1. TECHNICAL DATA
1.1. Burner performance
Type Oil throughput (kg/h) Burner output (kW)
BMV3 1.4 - 4.1 16 - 48
BMV4 1.4 - 4.1 16 - 48
BMV 5 3.2 - 4.7 38 - 56
* Specications for units with a low pressure furnace and an exhaust
gas loss of approx. 8%.
1.2. Certification
DIN EN 267:1999-11: register number: 5G966/11
Class 3 emission limits (only HL60 E/FLV.2-S)
German ecolabel “Blue Angel according to RAL-ZU 9: Con-
tract no. 14415 (only HL60 E/FLV.2-S)
1.3. Operating range
In the chart, you nd allowed combustion chamber pressure
as function of the oil ow (see g. 4).
The operating ranges have been determined on a test-
ing unit and refer to an altitude of approx. 100 m above
sea-level and a room temperature of approx. 20°C. The
oil ow that can be achieved in practice depends on the
starting resistance of the heater.
The starting resistance is inuenced by the combustion
chamber, the ue gas line and the starting load. Exact values
can therefore only be determined on each respective system.
1.4. Fuel
Fuel oil EL according to DIN 51603-1
Heating oil EL, low sulphur, according to DIN 51603-1
Fuel oil EL A Bio 10 (bio fuel oil according to DIN SPEC
51603-6, fuel oil EL, low sulphur, with up to 10% of FAME
according to the quality requirements of DIN 14214)
1.5. Electrical data
Nominal voltage ...................................................................230 V ~ 50 Hz
Starting power ................................................................................ca. 435 W
Operating power ..............................................................ca. 135 - 235 W
Contact rating of the thermostats and switches, ......min. 6A~
1.6. Burner dimensions
Specications of dimensions in mm (see g. 5 + 6)
Packing .............................................................l 370 / w 350 / h 485 mm
Transport weight ................................................................................14.5 kg
1.7. Acoustic emissions
The sound pressure level at maximum burner performance
is 57 dB(A).
The measurements were carried out with an accuracy class
2 measuring device according to IEC 60651 at a (horizontal)
distance of 2m.
1.8. Burner components
Item Make Ref
Motor Hanning O1A095-030
Oil pump Danfoss BFP 21 L3
Oil pre-heater Danfoss FPHE 5
Ignition unit Co TRK2-40SHK
Photocell Danfoss LDS 057H7097
Automatic oil ring unit Siemens LOA 24.171B27
Pression foyer en mbar
1,00
0
0,1
0,2
0,3
0,4
0,5
0,6
2,0
BMV3 / BMV4
BMV5
3,0 4,0 5,0 6,0 7,0
Débit de oul en kg/h
Oil mass flow in kg/h
Combustion chamber pressure in mbar


Specyfikacje produktu

Marka: ACV
Kategoria: Różne sterowanie klimatem
Model: BMV

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z ACV BMV, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Różne sterowanie klimatem ACV

ACV

ACV BMR 31 Instrukcja

1 Lipca 2024
ACV

ACV BMV Instrukcja

1 Lipca 2024

Instrukcje Różne sterowanie klimatem

Najnowsze instrukcje dla Różne sterowanie klimatem