Read and understand the instruction manual before using the product.
For your safety, read and follow the below safety considerations before using. For your safety,
read and follow the considerations written in the instruction manual.
Keep this instruction manual in a place where you can find easily.
The specifications, dimensions, etc are subject to change without notice for product improvement.
Safety Considerations
Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.
symbol indicates caution due to special circumstances in which hazards may occur.
Warning Failure to follow instructions may result in serious injury or death
01. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss.(e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in personal injury, economic loss or fire.
02. Do not use the unit in the place where flammable/explosive/corrosive gas, high humidity,
direct sunlight, radiant heat, vibration, impact or salinity may be present.
Failure to follow this instruction may result in explosion or fire.
03. Install on a device panel to use.
Failure to follow this instruction may result in fire or electric shock.
04. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in fire or electric shock.
05. Check ‘Connections’ before wiring.
Failure to follow this instruction may result in fire.
06. Do not disassemble or modify the unit.
Failure to follow this instruction may result in fire or electric shock.
Caution Failure to follow instructions may result in injury or product damage
01. When connecting the power input and relay output, use AWG 20 (0.50 mm 2) cable or over, and
tighten the terminal screw with a tightening torque of 0.74 to 0.90 N m.
When connecting the sensor input and communication cable without dedicated cable, use
AWG 28 to 16 cable and tighten the terminal screw with a tightening torque of 0.74 to 0.90 N
m.
Failure to follow this instruction may result in fire or malfunction due to contact failure.
02. Use the unit within the rated specifications.
Failure to follow this instruction may result in fire or product damage
03. Use a dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in fire or electric shock.
04. Keep the product away from metal chip, dust, and wire residue which flow into the unit.
Failure to follow this instruction may result in fire or product damage.
Cautions during Use
Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
Check the polarity of the terminals before wiring the temperature sensor.
For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length. For
thermocouple (TC) temperature sensor, use the designated compensation wire for extending wire.
Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power
line and input signal line closely, use line filter or varistor at power line and shielded wire at input
signal line. Do not use near the equipment which generates strong magnetic force or high frequency
noise.
Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting
the power.
Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.
When changing the input sensor, turn off the power first before changing. After changing the input
sensor, modify the value of the corresponding parameter.
Make a required space around the unit for radiation of heat. For accurate temperature measurement,
warm up the unit over 20 min after turning on the power.
Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
Do not wire to terminals which are not used.
This unit may be used in the following environments.
- Indoors (in the environment condition rated in ‘Specifications’)
- Altitude Max. 2,000 m
- Pollution degree 2
- Installation category II
Product Components
Product (+ bracket) Instruction manual
Specifications
Series TCN4S-24R
Power supply 100 - 240 VAC~ 50/60 Hz
Permissible voltage
range 90 to 110 % of rated voltage
Power consumption ≤ 5 VA
Sampling period 100 ms
Input specification Refer to 'Input Type and Using Range.
Control
output Relay 250 VAC~ 3A, 30 VDC~ 3A, 1a
Alarm output 250 VAC~ 1 A 1a
Display type 7 Segment (red, green), LED type
Control
type
Heating,
Cooling ON/OFF, P, PI, PD, PID Control
Hysteresis 1 to 100 (0.1 to 50.0) °C/°F
Proportional band (P) 0.1 to 999.9 °C/°F
Integral time (I) 0 to 9,999 sec
Derivative time (D) 0 to 9,999 sec
Control cycle (T) 0.5 to 120.0 sec
Manual reset 0.0 to 100.0%
Relay
life
cycle
Mechanical 5,000,000 operations
Electrical OUT1/2: ≥ 200,000 operations (load resistance: 250 VAC~ 3 A)
AL1/2: ≥ 300,000 operations (load resistance: 250 VAC~ 1 A)
Dielectric strength Between the charging part and the case: 2,000 VAC~ 50/60 Hz for 1 min
Vibration 0.75 mm amplitude at frequency of 5 to 55 Hz in each X, Y, Z direction for 2 hours
Insulation resistance ≥ 100 MΩ (500 VDC megger)
Noise immunity ±2 kV square shaped noise (pulse width: 1 µs) by noise simulator R-phase,
S-phase
Memory retention ≈ 10 years (non-volatile semiconductor memory type)
Ambient temperature -10 to 50 °C, storage: -20 to 60 °C (no freezing or condensation)
Ambient humidity 35 to 85%RH, storage: 35 to 85%RH (no freezing or condensation)
Insulation type Mark: , double or reinforced insulation (dielectric strength between the measuring
input part and the power part: 2 kV)
Certification
Unit weight (packaged) TCN4S: ≈ 100 g (≈ 147 g)
Input Type and Using Range
The setting range of some parameters is limited when using the decimal point display.
Input type Decimal
point Display Using range (°C) Using range (°F)
Thermo
-couple
K (CA) 1 -50 to 1,200 -58 to 2,192
0.1 -50.0 to 999.9 -58.0 to 999.9
J (IC) 1 -30 to 800 -22 to 1,472
0.1 -30.0 to 800.0 -22.0 to 999.9
L (IC) 1 -40 to 800 -40 to 1,472
0.1 -40.0 to 800.0 -40.0 to 999.9
T (CC) 1 -50 to 400 -58 to 752
0.1 -50.0 to 400.0 -58.0 to 752.0
R (PR) 1 0 to 1,700 32 to 3,092
S (PR) 1 0 to 1,700 32 to 3,092
RTD
Cu50 1 -50 to 200 -58 to 392
0.1 -50.0 to 200.0 -58.0 to 392.0
DPt100 Ω 1 -100 to 400 -148 to 752
0.1 -100.0 to 400.0 -148.0 to 752.0
Display accuracy
Input type Using
temperature Display accuracy
Thermocouple RTD
At room
temperature
(23°C ±5 °C)
(PV ±0.5% or ±1 °C higher one) ±1-digit
Thermocouple R, S below 200 °C:
(PV ±0.5% or ±3 °C higher one) ±1-digit
Over 200 °C:
(PV ±0.5% or ±2 °C higher one) ±1digit
Thermocouple L, RTD Cu50 Ω:
(PV ±0.5% or ±2 °C higher one) ±1-digit
Out of room
temperature
range
(PV ±0.5% or ±2 °C higher one) ±1-digit
Thermocouple R, S below 200 °C:
(PV ±1.0% or ±6 °C higher one) ±1digit
Over 200 °C:
(PV ±0.5% or ±5 °C higher one) ±1digit
Thermocouple L, RTD Cu50 Ω:
(PV ±0.5% or ±3 °C higher one) ±1digit
If the input specification is set to 'decimal point 0.1' display, add ±1 by accuracy standard.°C
Unit Descriptions
1. PV Display part (red)
RUN mode: Displays PV (Present value)
Setting mode: Displays parameter name
2. SV Display part (green)
RUN mode: Displays SV (Setting value)
Setting mode: Displays parameter setting value
3. Indicator
Display Name Description
AL1/2 Alarm
output Turns ON when the alarm output is ON.
OUT Control
output
Turns ON when control output is ON
CYCLE/PHASE control of SSR
drive output: Turns ON when MV is
over 3.0% [AC power model]
AT Auto
tuning Flashes during auto tuning every 1 sec
°C, °F Unit Displays selected unit (parameter).
4. Input key
Display Name
[MODE] Mode key
[◄], [▼ ▲], [ ] Setting value
control key
Errors
Display Description Troubleshooting
Flashes when input sensor is disconnected or sensor is
not connected. Check input sensor status.
Flashes when PV is higher than input range.
01) When input is within the rated input
range, this display disappears.
Flashes when PV is lower than input range.
01)
01) Be careful that when / error occurs, the control output may occur by recognizing the maximum or minimum input
depending on the control type.
Dimensions
Unit: mm
Panel cut-out
Body Panel cut-out
A B C D E F G H I
TCN4S 48 48 6 64.5 44.8 ≥ 65 ≥ 65 45 +0.6
045 +0.6
0
Bracket
TCN4S
Installation Method
TCN4S
Flathead screwdriver
After mounting the product to panel with bracket, insert the unit into a panel, fasten the bracket by
pushing with a flathead screwdriver.
Dual Display PID Temperature Controllers
TCN4S-24R
Item no.: 3016146
INSTRUCTION MANUAL
TCD210225AB
Connections
TCN4S
Crimp Terminal Specifications
Unit: mm, use the crimp terminal of the following shape.
≥3.0
≤5.8
≥3.0
≤5.8
Wire ferrule Fork crimp terminal Round crimp terminal
Terminal
number a b c
1 to 8 61.7 ≤ 3.7
9 to 11 6 to 8 2.1 ≤ 4.2
12 to 14 6 to 8 ≤ 1.5 ≤ 3.5
Mode Setting
[MODE], [◄], [▲ ▼], [ ]
[MODE] 2 sec
Move digits: [◄]
Change value: [ ], [ ]▲ ▼
Save: [MODE]
[MODE] over 3 sec
[MODE] over 3 sec
Refer to ‘Parameter Reset’
Auto
[MODE] 4 sec
[◄] + [▲ ▼] + [ ] over 5 sec
[ ] + [ ] over 3 sec▲ ▼
SV setting
Parameter 1 group
Parameter 2 group
Parameter reset
Digital input key
RUN RUN
Parameter Reset
01. Press the [ ] + [ ] + [ ] keys for over 5 sec. in run mode, INIT turns ON.▲ ▼
02. Change the setting value as YES by pressing the [ ], [ ] keys.▲ ▼
03. Press the [MODE] key to reset all parameter values as default and to return to run mode.
Parameter Setting
Some parameters are activated/deactivated depending on the model or setting of other parameters.
Refer to the description of each item.
The setting range in parentheses is for using the decimal point display in the input specification.
If there is no key input for more than 30 seconds in each parameter, it returns to RUN mode.
When pressing the [MODE] key within 1 second after returning to the operation mode from the
parameter group, it will enter the parameter group before returning.
[MODE] key: Saves the current parameter setting value and moves to the next parameter.
[◄] key: Checks the fixed item / Moves the row when changing the set value
[ ], [ ] keys: Selects the parameter / Changes the set value▲ ▼
Recommended parameter setting sequence: Parameter 2 group → Parameter 1 group → SV setting
mode
Disposal
This symbol must appear on any electrical and electronic equipment placed on the EU
market. This symbol indicates that this device should not be disposed of as unsorted
municipal waste at the end of its service life.
Owners of WEEE (Waste from Electrical and Electronic Equipment) shall dispose of it
separately from unsorted municipal waste. Spent batteries and accumulators, which are not
enclosed by the WEEE, as well as lamps that can be removed from the WEEE in a non-
destructive manner, must be removed by end users from the WEEE in a non-destructive
manner before it is handed over to a collection point.
Distributors of electrical and electronic equipment are legally obliged to provide free take-back of waste.
Conrad provides the following return options free of charge (more details on our website):
in our Conrad offices
at the Conrad collection points
at the collection points of public waste management authorities or the collection points set up by
manufacturers or distributors within the meaning of the ElektroG
End users are responsible for deleting personal data from the WEEE to be disposed of.
It should be noted that different obligations about the return or recycling of WEEE may apply in countries
outside of Germany.
Parameter 1 group
Parameter Display Default Setting range Condition
1-1 AL1 alarm
temperature Deviation alarm: -F.S. to F.S. °C/°F
Absolute value alarm: Within input range
2-12/14
alarm
operation:
AM1 to AM6
1-2 AL2 alarm
temperature
1-3 Auto tuning OFF: Stop, ON: Execution
2-8 Control
type: PID
1-4 Proportional
band 0.1 to 999.9 °C/°F
1-5 Integral time 0 (OFF) to 9999 sec
1-6 Derivative time 0 (OFF) to 9999 sec
1-7 Manual reset 0.0 to 100.0%
2-8 Control
type: PID &
1-5 Integral
time: 0
1-8 Hysteresis 1 to 100 (0.1 to 50.0) °C/°F 2-8 Control
type: ONOF
Parameter 2 group
Parameter Display Default Setting range Condition
2-1 Input
specification01) Refer to 'Input Type and Using Range'. -
2-2 Temperature
unit01) °C, °F -
2-3 Input correction -999 to 999 (-199.9 to 999.9) °C/°F -
2-4 Input digital
filter 0.1 to 120.0 sec -
2-5 SV low limit02) Within 2-1 Input specification Input range,
L-SV ≤ H-SV - 1-digit °C/°F
H-SV ≥ L-SV + 1-digit °C/°F
-
2-6 SV high limit02) -
2-7 Control output
mode03) HEAT: Heating, COOL: Cooling -
2-8 Control type04) PID, ONOF: ON/OFF -
2-9 Control output RLY: relay -
2-11 Control cycle 0.5 to 120.0 sec 2-9 Control
output: RLY
2-12 AL1 alarm
operation
□□□
AM0: Off
AM1: Deviation high limit alarm
AM2: Deviation low limit alarm
AM3: Deviation high, low limit alarm
AM4: Deviation high, low reverse alarm
AM5: Absolute value high limit alarm
AM6: Absolute value low limit alarm
SBA: Sensor break alarm
LBA: Loop break alarm (LBA)
-
2-13 AL1 alarm
option
A: Standard
alarm
C: Standby
sequence 1
E: Standby
sequence 2
B: Alarm latch
D: Alarm latch and
standby sequence 1
F: Alarm latch and
standby sequence 2
-
Enter to option setting: Press [] key
in 2-12 AL-1 alarm operation.
2-14 AL2 alarm
operation Same as 2-12/13 AL1 alarm operation/
option -
2-15 AL2 alarm
option
2-16 Alarm output
hysteresis 1 to 100 (0.1 to 50.0) °C/°F
2-12/14
AL1/2 alarm
operation: AM1
to 6
2-17 LBA time 0 (OFF) to 9999 sec or auto (auto
tunning)
2-12/14
AL1/2 alarm
operation: LBA
2-18 LBA band 0 (OFF) to 999 (0.0 to 999.9) °C/°F or
auto (auto tunning)
2-12/14
AL1/2 alarm
operation: LBA
& 2-18 LBA
time: > 0
2-19 Digital input
key
STOP: Stop control output, AL.RE: Alarm
reset, AT*: Auto tuning execution, OFF
*2-8 Control
type: PID
2-20 Sensor error
MV
0.0: OFF, 100.0: ON 2-8 Control
type: ONOF
0.0 to 100.0% 2-8 Control
type: PID
2-21 Lock
OFF
LOC1: Parameter 2 group lock
LOC2: Parameter 1/2 group lock
LOC3: Parameter 1/2 group, SV setting
lock
-
01) Below parameters are initialized when the setting value is changed.
- Parameter 1 group: AL1/2 alarm temperature
- Parameter 2 group: Input correction, SV high/low limit, Alarm output hysteresis, LBA time, LBA band
- SV setting mode: SV
02) If SV is lower than low limit or higher than high limit when the value is changed, SV is changed to the low/high limit value.
If 2-1 Input specification is changed, the value is changed to Min./Max. value of Input specification.
03) When the setting value is changed, setting value of 2-20 Sensor error MV is initialized to 0.0 (OFF).
04) When changing the value from PID to ONOF, each value of following parameter is changed.
2-19 Digital input key: OFF, 2-20 Sensor error MV: 0.0 (when setting value is lower than 100.0)
This is a publication by Conrad Electronic SE, Klaus-Conrad-Str. 1, D-92240 Hirschau (www.conrad.com).
All rights including translation reserved. Reproduction by any method, e.g. photocopy, microlming, or the
capture in electronic data processing systems require the prior written approval by the editor. Reprinting, also
in part, is prohibited. This publication represents the technical status at the time of printing.
Copyright 2024 by Conrad Electronic SE.
*BN3016146 TCN_EN_TCD210225AB_20240417_INST_W


Specyfikacje produktu

Marka: Tru Components
Kategoria: termostat
Model: TCN4S-24R

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Tru Components TCN4S-24R, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje termostat Tru Components

Instrukcje termostat

Najnowsze instrukcje dla termostat