Owner’s Manual
Switched/Metered Rack PDU
with Automatic Transfer Switch
Models: PDUMH15AT, PDUMH15ATNET, PDUMH15HVAT,
PDUMH15HVATNET, PDUMH20AT, PDUMH20ATNET,
PDUMH20HVAT, PDUMH20HVATNET
Series Number: AGAC7625
1. Important Safety Instructions 2
2. Installation 3
2.1 Mounting the PDU 3
2.2 Connecting the PDU 3
2.3 Networking the PDU 6
2.4 Test and Configure 9
3. Features 11
4. Configuration and Operation 14
4.1 Automatic Transfer Switch 14
4.2 Remote Monitoring and Control 15
5. Technical Support 16
6. Warranty and Product Registration 16
Español 17
Français 33
16-05-185-9335E0.indb 1 7/28/2016 3:04:37 PM
2
SAVE THESE INSTRUCTIONS
• This manual contains instructions and warnings that should be followed
during the installation, operation, and storage of this product. Failure to
heed these instructions and warnings may affect the product warranty.
• Warning: This equipment is compliant with Class A of CISPR 32. In a
residential environment, this equipment may cause radio interference.
• The PDU provides the convenience of multiple outlets, but DOES NOT provide surge or line noise
protection for connected equipment.
• The PDU is designed for indoor use only, in a controlled environment, away from excess
moisture, temperature extremes, conductive contaminants, dust or direct sunlight.
• Keep indoor ambient temperature between 32°F and 122°F (0°C and 50°C).
• The PDU must be installed by a qualified technician only.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Install in accordance with National Electrical Code standards. Be sure to use the proper
overcurrent protection for the installation, in accordance with the plug/equipment rating.
• Connect the PDU to an outlet that is in accordance with your local building codes and that is
adequately protected against excess currents, short circuits and earth faults.
• The electrical outlets supplying power to the equipment should be installed near the equipment
and easily accessible.
• Do not connect the PDU to an ungrounded outlet or to extension cords or adapters that
eliminate the connection to ground.
• Be sure to provide a local disconnect device on any models that are permanently installed
without a plug that is easily accessible.
• Never attempt to install electrical equipment during a thunderstorm.
• Individual equipment connected to the PDU should not draw more current than the individual
PDU’s outlet’s rating.
• The total load connected to the PDU must not exceed the maximum load rating for the PDU.
• Do not attempt to modify the PDU, input plugs or power cables.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable
parts inside.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Use of this equipment in life support applications where failure of this equipment can reasonably
be expected to cause the failure of the life support equipment or to significantly affect its safety
or effectiveness is not recommended. Do not use this equipment in the presence of a
flammable anesthetic mixture with air, oxygen or nitrous oxide.
1. Important Safety Instructions
16-05-185-9335E0.indb 2 7/28/2016 3:04:37 PM
PDUMH15AT, PDUMH15ATNET,
PDUMH20AT, PDUMH20ATNET
PDUMH15HVAT, PDUMH15HVATNET
PDUMH20HVAT, PDUMH20HVATNET
PDUMH15HVATNET
3
Primary InputSecondary Input
Primary Input
Secondary Input
2.2.1
2.2.1
PDUMH20AT
PDUMH20ATNET
PDUMH15AT
PDUMH15ATNET
PDUMH20HVAT
PDUMH20HVATNET
Primary Input (120V Models) Primary Input (208-240V Models)
2.1 Mounting the PDU
The PDU supports 1U Rack configurations.
Note: The user must determine the fitness of
hardware and procedures before mounting. The PDU
and included hardware are designed for common
rack and rack enclosure types and may not be
appropriate for all applications. Exact mounting
configurations may vary.
1U Rack Mounting: Attach the PDU to the
rack by inserting four user-supplied screws A
through the PDU mounting brackets B and
into the mounting holes of the rack rail as
shown.
2. Installation
B
B
B
A
A
A
2.2 Connecting the PDU
All PDU models include a primary and secondary AC power input (see diagram). The reference
table below lists each model’s primary and secondary inputs:
Model Primary Input Secondary Input*
PDUMH15AT NEMA 5-15P (permanent cord) IEC C14 inlet
PDUMH15ATNET NEMA 5-15P (permanent cord) IEC C14 inlet
PDUMH15HVAT IEC C14 inlet (detachable cord) IEC C14 inlet
PDUMH15HVATNET IEC C14 inlet (detachable cord) IEC C14 inlet
PDUMH20AT NEMA 5-15P (permanent cord) IEC C20 inlet
PDUMH20ATNET NEMA 5-15P (permanent cord) IEC C20 inlet
PDUMH20HVAT IEC C20 inlet (detachable cord) IEC C20 inlet
PDUMH20HVATNET IEC C20 inlet (detachable cord) IEC C20 inlet
Note: The PDUMH15HVATNET model uses plug lock inserts over C13 plugs to securely connect to the C14
primary and secondary inputs.
16-05-185-9335E0.indb 3 7/28/2016 3:04:39 PM
Specyfikacje produktu
Marka: | Tripp Lite |
Kategoria: | Listwa zasilająca |
Model: | PDUMH15HVAT |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Tripp Lite PDUMH15HVAT, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Listwa zasilająca Tripp Lite
21 Września 2024
14 Września 2024
13 Września 2024
11 Września 2024
10 Września 2024
9 Września 2024
9 Września 2024
9 Września 2024
8 Września 2024
7 Września 2024
Instrukcje Listwa zasilająca
- Listwa zasilająca Sven
- Listwa zasilająca Yato
- Listwa zasilająca StarTech.com
- Listwa zasilająca Nedis
- Listwa zasilająca ATen
- Listwa zasilająca APC
- Listwa zasilająca Icy Box
- Listwa zasilająca Gembird
- Listwa zasilająca V7
- Listwa zasilająca Digitus
- Listwa zasilająca EVOline
- Listwa zasilająca Oehlbach
- Listwa zasilająca DataVideo
- Listwa zasilająca Panduit
- Listwa zasilająca Intellinet
- Listwa zasilająca Kindermann
- Listwa zasilająca Ewent
- Listwa zasilająca GoGen
- Listwa zasilająca Oregon Scientific
- Listwa zasilająca Hama
- Listwa zasilająca Ubiquiti Networks
- Listwa zasilająca CyberPower
- Listwa zasilająca Vivanco
- Listwa zasilająca Eaton
- Listwa zasilająca Geist
- Listwa zasilająca Brennenstuhl
- Listwa zasilająca Eglo
- Listwa zasilająca Caliber
- Listwa zasilająca Eminent
- Listwa zasilająca Energenie
- Listwa zasilająca Steren
- Listwa zasilająca Ufesa
- Listwa zasilająca Konig
- Listwa zasilająca HQ
- Listwa zasilająca REV
- Listwa zasilająca Panamax
- Listwa zasilająca Furman
- Listwa zasilająca Legrand
- Listwa zasilająca Bachmann
- Listwa zasilająca Kondator
- Listwa zasilająca Bauhn
- Listwa zasilająca Altronix
- Listwa zasilająca Middle Atlantic
- Listwa zasilająca Huslog
Najnowsze instrukcje dla Listwa zasilająca
14 Stycznia 2025
12 Stycznia 2025
31 Grudnia 2025
29 Grudnia 2024
24 Grudnia 2024
7 Grudnia 2024
7 Grudnia 2024
7 Grudnia 2024
7 Grudnia 2024
7 Grudnia 2024