Instrukcja obsługi Senseair aSENSE Duct
Senseair
Czujnik CO2
aSENSE Duct
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Senseair aSENSE Duct (4 stron) w kategorii Czujnik CO2. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek
Strona 1/4
Installation Manual
aSENSE Duct
CO2 / temperature transmitter
for mounting in ventilation ducts
1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box)
2 Sealing gasket 7 PCB (Factory supplied mounted in box)
3 Largest locking nob 8 Snap-in lid
4 2 washers BRB 5,3x10x1 9 PG9 cable entry bushing
(not included)
5 2 screws RXS 4,8x16 10 Temperature sensor (to be put into the sampling tube)
(not included)
1
2
12
3
456
7
9
8
10
Mounting of aSENSE Duct on to the duct.
10 Hole with 25 mm diameter
11 Temperature sensor with 110 mm cable mounted in the sampling probe
Mounting Instruction
Since there might be a substantial pressure difference in duct mounting applications, it is essential to
avoid ambient air from suction into the duct mounting box. For correct function it is indispensible that
the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance
are absolutely tight. The duct entrance may need extra sealing paste in order to prevent leakage. The
PCB must be handed carefully and protected from electrostatic discharge.
1) Electrical cable entry: The box has a factory mounted cable entry bushing in dimension PG9.
Never feed more than one cable through each cable entry bushing, or else gas might leak
through!
2) Mounting the tube: Drill a hole (10) with 25 mm diameter (or 1 inch) for the sampling probe and
two holes with 4 mm diameter for the screws (5) into the air duct and mount the tube (1) with the
gasket (2). The sampling probe should be mounted with the largest locking knob on top. The unit
can be mounted with the air coming from the left or right.
3) Attaching the sensor box is made to the sampling probe by a snap-in bayonet fitting. First,
carefully stick the temperature probe (11) into the sampling probe. (1). Orient the box onto the
sampling probe so that the box upside is on the same side as the largest locking knob (3). When
the probe is fitted into the notches of the box, then turn the box clockwise until stop (see Figure
1). Position 1 indicates open where the box can be removed from the sampling probe. In position
2 the box is locked to the probe.
If for some reason the PCB must be removed it must be handed carefully and protected from
electrostatic discharge! Normally, removing the PCB is not required.
11
10
Electrical connections
NOTE:
The power supply has to be connected to and . is considered as system ground. If the
analogue output is connected to a controller the same ground reference has to be used for the aSENSE
Duct unit and for the control system! Unless different transformers are used, special precautions need to
be taken.
The aSENSE signal and power supply grounds are common.
Connect the power after mounting. The analogue output should be connected before measuring.
Connection
Terminal
Function
Electrical Data
Remarks
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%), 3W
24 VAC/DC-
2W without output load
See note 1!
Out(1)
Out(2)
Not marked
Analogue Output 1 (+)
Analogue Output 2 (+)
Signal Ground (-)
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
Connected to via PTC
fuse
According to positions of
Out(1) and start point
jumpers.
See note 2!
According to positions of
Out(2) and start point
jumpers.
See note 2!
See note 1!
Note 1: The ground terminal is used as negative power supply DC input or AC phase ground
(halfwave rectifier). The signal ground M, protected by a PTC resistor, is the same as power ground
(permitting a ”3-wire” configuration). A single transformer may be used for the entire system.
Note 2: aSENSE can deliver a voltage or a current loop for Out(1) / Out(2). To change between
voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and
one for Out(2), so that one output can be a voltage output and the other a current output. Both, voltage
output and current outputs, can have start points 0 % (0-10 VDC or 0-20mA) or 20% (2-10 VDC or 4-
20mA). The same start point is used for both outputs. See the function manual.
~
+
~
+
Specyfikacje produktu
Marka: | Senseair |
Kategoria: | Czujnik CO2 |
Model: | aSENSE Duct |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Senseair aSENSE Duct, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Czujnik CO2 Senseair
26 Września 2024
24 Września 2024
22 Września 2024
18 Września 2024
1 Września 2024
29 Sierpnia 2024
Instrukcje Czujnik CO2
- Czujnik CO2 Edimax
- Czujnik CO2 Bresser
- Czujnik CO2 Aktivia
- Czujnik CO2 Econox
- Czujnik CO2 Orcon
- Czujnik CO2 Duco
- Czujnik CO2 EnviSense
- Czujnik CO2 Brink Climate
Najnowsze instrukcje dla Czujnik CO2
27 Września 2024
26 Września 2024
26 Września 2024
26 Września 2024
25 Września 2024
24 Września 2024
23 Września 2024
18 Września 2024
3 Lipca 2024
3 Lipca 2024