Instrukcja obsługi Pyle PMA90

Pyle Windmeter PMA90

Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Pyle PMA90 (6 stron) w kategorii Windmeter. Ta instrukcja była pomocna dla 5 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/6
User's Manual
CFM/CMM Thermo-Anemometer
Model -PMA90
1.
LCD Display2.
Meter
3.
MAX/MIN
4.
5.
AREA
6.
7. NEXT
8. HOLD
9.
UNIT
AVG
Keypad
tAUTO POWER OFF Press to turn the meter ON or OFF
tMAX/MIN Used to record and store the highest, lowest and average
airflow or velocity readings.
(LEFT) also serves as change decimal point button in AR EA mode
tUNITS Press to select the mode of operation. In FLOW mode,
the meter displays air volume. In VELOCITY mode, the meter
displays air speed.
(UP) also serves as increase number button in AR E A mode.
tAVG Used to Average multiple readings in FLOW or VELOCITY
mode. Up to 20 readings can be averaged.
tHOLD Press to freeze the displayed reading. Press again to unlock
display. This button also functions as the R IGHT scroll button in
AR E A mode and RE C ALL mode.
tAREA Press and hold to manually enter the area of a duct in CFM
or CMM mode
t
t
t
NEXT In AREA mode, used to select memory locations 1-8.
°C °F
Battery compartment located on the back of the instrument.
The rubber protective jacket must be removed from the meter
to access the compartment.
Power On/Off
Introduction
Congratulations on your purchase of the Thermo-Anemometer. This
instrument measures Air Velocity, Air Flow (volume) and Temperature.
The large, easy-to-read backlit LCD includes primary and secondary
displays plus numerous status indicators. The meter is shipped fully
tested and calibrated and with proper use will provide years of reliable
service.
Meter Description
1 2
1)
2)
3)
4)
5)
6)
8)
9)
7)
The button is behind of battery cover, it needs to open
/
the battery cover that can set.
AUTO BACKLIGHT The model will be full auto backlight when
operation, it is more convenient.
Display Layout
MAX (top of LCD): Max Hold function
engaged for the Air Temperature function
HOLD (top of LCD): Data Hold function
engaged for the Air Temperature function
VEL: indicates that meter is in air velocity mode
FLOW: indicates that meter is in air flow mode
MAX (bottom of LCD): Max Hold for the IR Temperature and
RH function
HOLD (bottom of LCD): Data Hold for the IR Temperature
function and RH function
oC / oF: Temperature units of measure
CFM/CMM: airflow units of measure
Ft2, m2: units for area dimensions
m/s, ft/min, km/h, MPH, knots: air velocity units of measure
X10, X100: multipliers for air flow readings
AVG: air averaging mode
RECORD: indicates that min/max function is running (top for temp
, bottom for air)
Large LCD digits at center of display for Relative Humidity an
d IR Temperature
Smaller LCD digits at top, right of display for Probe Temperature
: Low battery indicator
Operation
Connecting the Vane
1. The vane plug is inserted in the meter’s sensor jack at the top of the
meter. The plug and jack are keyed so that the plug can only fit in
the jack one way.
2. Turn the plug carefully until it lines up with the jack and then firmly
push the plug in place. Do not apply undue force or try to twist the
plug side-to-side.
3. If the vane is not connected to the meter or if the sensor is defective,
the LCD display will indicate OL in place of a Temperature reading.
Air Velocity Measurements (Single Point)
1. Turn on the meter using the ON/OFF button.
2. Press UNITS button to select the desired unit of
measure. NOTE: At power up the meter will
display the last unit of measure previously
entered.
3. Place the sensor in the air stream. Ensure that
the air enters the vane as indicated by the arrow
sticker placed inside the vane.
4. View the readings on the LCD Display. The
large main LCD display shows the Air Velocity
reading. The upper right LCD sub-display shows
the temperature reading.
Air Velocity Averaging Mode
1. To enter 20 Point Averaging Mode, press and hold the AVG
button until it beeps twice. The AVG icon will be displayed.
2. Take a measurement and press the button. A singleAVG
beep will sound and the HOLD icon will appear in the display.
3. The average reading will be displayed and number of readings
measured will appear in the upper right hand corner of the display.
After 5 seconds, the display will return to the current reading.
airflow
Arrow
Side view of Vane
3 4

Specyfikacje produktu

Marka: Pyle
Kategoria: Windmeter
Model: PMA90

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Pyle PMA90, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Windmeter Pyle

Pyle

Pyle PMA90 Instrukcja

21 Sierpnia 2024

Instrukcje Windmeter

Najnowsze instrukcje dla Windmeter

BaseTech

BaseTech BS-10 Instrukcja

27 Sierpnia 2024
Extech

Extech 45158 Instrukcja

21 Sierpnia 2024