Installation, Operating, Maintenance
and After Sales Manual.
Product Serial Number:
Please leave this manual with the end user.
Part Number: 1370057
Issue 5
LO-LINE RC & LO-LINE RC Heater/Cooler
Models: 6-4, 9-6, 14-10, 19-15
01.06.2011 ISSUE 5
23678 Lo-Line RC manual UK 27/06/2011 09:28 Page 2
1.0 General Information 03
2.0 Heating System Design 03
3.0 Unit Selection/Sizing 03
4.0 Location 03
5.0 Preparation 04
6.0 Fixing 04
7.0 Water Connections 05
8.0 Electrical Connection 06
9.0 Commissioning Procedure 06
10.0 Technical Data 08
11.0 Operating Instructions 09
12.0 Troubleshooting 10
13.0 Maintenance 11
Contents
23678 Lo-Line RC manual UK 27/06/2011 09:28 Page 3
03
LO-LINE RC & LO-LINE RC Heater/Cooler
1.0 General Information
2.0 Heating System Design
lThis MYSON LO-LINE fan convector is designed for wall
mounted installation with a minimum installation height of
150mm to the underside of the unit.
lThe LO-LINE should only be used on closed circulation, two
pipe, pump assisted central heating systems (LO-LINE) or
heating and cooling systems (LO-LINE Heater/Cooler).
lThe LO-LINE Heater and Heater/Cooler can be used on heat
pump systems.
lThe minimum side clearance is 100mm.
lThe maximum ceiling height is 3m.
lBefore proceeding with the installation, the heating system
design must be considered and the unit correctly sized to
meet the heat loss requirements of the room at normal fan
speed.
lThis unit is supplied with an infra red remote control system
and has 3 operating modes -
Automatic – the desired room temperature is programmed in
to the unit and the fan speed is automatically adjusted until
the desired room temperature is achieved.
Fan only – allows user selection of any of the 3 available fan
speeds irrespective of room temperature or water temperature
in the coil.
Fan only with water temperature control – allows the user to
select any of the available fan speeds, which will operate only
if the water temperature in the coil is above 32C. This enables
control of the unit via an externally mounted room thermostat
if desired.
lThis appliance is not intended for use by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure they do not play with
the appliance.
This fan convector must be fitted on a two pipe, pumped
circulation heating system.
For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the
heat exchanger. This means that:
1. The minimum pipe size from boiler to fan convector must be
15mm.
2. This unit is not suitable for use on microbore pipe-work.
3. Where the unit is fitted on to a system with other emitters a
separate circuit for the fan convector should be considered
to provide adequate water flow.
4. The system water must be above 32°C for heating mode.
5. For heat pump applications - see Commissioning Procedure
6. This unit is NOT suitable for one-pipe systems.
7. Optimum performance will require effective balancing of
the whole system.
8. This unit must not be used to replace a radiator in an
existing system unless an adequate flow of water through
the unit can be guaranteed.
3.0 Unit Selection/Sizing
Heat output performance is given in the Technical Data section
of this manual. Outputs are shown for the three fan speeds,
however, it is important to size the unit to match the calculated
heat loss requirements of the room with the unit operating on
the low fan speed. The higher fan speeds are used in automatic
mode when the room temperature is significantly lower than the
preset temperature.
When establishing the temperature difference, ie mean water to
room temperature, allowance should be made for temperature
drop in the system. It is the water temperature of the unit which
dictates the output.
4.0 Location
lThis LO-LINE unit may be fitted to any convenient wall at a
height from floor level that suits the application, providing an
unimpeded flow of warm air into the area to be heated.
lThe minimum distance from the underside of the unit to floor
level is 150mm.
lThe unit should be mounted on a flat wall, and stud or
partition walls should be avoided to minimise the possibility
of noise transmission.
lFor cooling applications, the need for disposal of condensate
may influence the position of the unit.
1.02.03.04.0
This unit MUST NOT be installed in a bathroom or other similar high humidity area.
23678 Lo-Line RC manual UK 27/06/2011 09:28 Page 4


Specyfikacje produktu

Marka: Myson
Kategoria: Ogrzewanie
Model: LO-LINE RC 14-10

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Myson LO-LINE RC 14-10, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Ogrzewanie Myson

Instrukcje Ogrzewanie

Najnowsze instrukcje dla Ogrzewanie