In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any modification(s) to the
following specifications for which MEPPI has not approved or authorized such modifications. Further, MEPPI shall not be liable for any
special, incidental, indirect, punitive or consequential damages arising out of or in connection with the use of such specifications.
Copyright © 2019, Mitsubishi Electric Power Products, Inc. U-ENS00085 Rev 1
UNINTERRUPTIBLE POWER SUPPLY
MODEL
9900D 400V/415V
SPECIFICATIONS
UNINTERRUPTED Peace of Mind®
In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any mod ification(s) to the following specifications for which MEPPI has not
approved or authorized such modifications. Further, MEPPI shall not be liable for any special, incidental, indirect, punitive or consequential damages arising out of or in connection with the use
of such specifications.
1
Copyright © 2019, Mitsubishi Electric Power Products Inc. U-ENS00 5 Rev 1 , 08
TABLE OF CONTENTS
PART 1 GENERAL .........................................................................................................................2
1.1 SUMMARY ............................................................................................................................2
1.2 STANDARD ...........................................................................................................................2
1.3 SYSTEM DESCRIPTION ......................................................................................................2
1.3.1 Components ......................................................................................................................2
1.3.2 Mode of Operation .............................................................................................................2
1.4 SUBMITTALS ........................................................................................................................3
1.4.1 Proposal Submittals ..........................................................................................................3
1.4.2 Delivery Submittals ............................................................................................................3
1.5 ENVIRONMENTAL CONDITIONS ........................................................................................4
1.6 WARRANTY ..........................................................................................................................5
1.7 QUALITY ASSURANCE ........................................................................................................6
1.7.1 Maintainability ....................................................................................................................6
1.7.2 Factory Test .......................................................................................................................6
PART 2 PRODUCT .........................................................................................................................6
2.1 ELECTRIC CHARACTERISTICS ..........................................................................................6
2.1.1 UPS Output Capacity ........................................................................................................6
2.1.2 Battery Capacity ................................................................................................................6
2.1.3 AC Input .............................................................................................................................6
2.1.4 Bypass Input ......................................................................................................................7
2.1.5 AC Output ..........................................................................................................................7
2.1.6 DC Input and Battery .........................................................................................................8
2.1.7 Efficiency ...........................................................................................................................8
2.2 COMPONENTS .....................................................................................................................8
2.2.1 Converter Section: .............................................................................................................8
2.2.2 Inverter ..............................................................................................................................11
2.2.3 UPS Module Control and Monitoring ................................................................................12
2.2.4 Bypass and Static Switch ..................................................................................................13
2.2.5 Operation/Display Panel ...................................................................................................14
2.2.6 Microprocessor Interface/Diagnostics ...............................................................................16
2.2.7 UPS Status and Function Interfacing ................................................................................16
2.2.8 (Option) Remote Status Alarm Panel ................................................................................18
2.2.9 (Option) DiamondSync ......................................................................................................18
2.3 MECHANICAL DESIGN ........................................................................................................18
2.3.1 Cabinet Structure (Enclosure) ...........................................................................................18
2.3.2 Serviceability .....................................................................................................................18
2.3.3 Ventilation ..........................................................................................................................19
2.3.4 (Option) Eyebolts ...............................................................................................................19
PART 3 EXECUTION ......................................................................................................................19
3.1 SITE PREPARATION ............................................................................................................19
3.2 INSTALLATION .....................................................................................................................19
3.3 FIELD QUALITY CONTROL ..................................................................................................19
In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any mod ification(s) to the following specifications for which MEPPI has not
approved or authorized such modifications. Further, MEPPI shall not be liable for any special, incidental, indirect, punitive or consequential damages arising out of or in connection with the use
of such specifications.
2
Copyright © 2019, Mitsubishi Electric Power Products Inc. U-ENS00 5 Rev 1 , 08
SECTION 2633 53
STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
PART 1 GENERAL
1.1 SUMMARY
This specification describes a three phase continuous duty, an on-line, solid-state, uninterruptible
power system, hereinafter referred to as the UPS. The UPS shall operate utilizing the existing
power distribution system to provide a high quality, reserve source of power to electronic
equipment loads. The system shall consist of a converter, system battery, solid-state inverter,
automatic static bypass transfer circuit.
1.2 STANDARD
The UPS has been designed in accordance with and complies with the following standards:
1. UL 1778 (Underwriter Laboratories) Standard for UPS Equipment.
2. CSA 22.2 (Canadian Standards Association cUL Equipment).
3. CE (European Conformity)
4. IEC (International Electro-technical Commission) Semiconductor Converter Standards.
5. EMI compatibility:IEC 62040-2 (category C3)
6. IEEE 587, ANSI C62.41 19 Standard for Surge Withstand Ability. 91
7. ISO 9001 Quality Assurance program.
1.3 SYSTEM DESCRIPTION
1.3.1 Components
The UPS system shall consist of the following major equipment:
A. UPS Module.
1. Insulated Gate Bipolar Transistor (IGBT) Converter.
2. Insulated Gate Bipolar Transistor (IGBT) Inverter.
3. Digital Signal Processor (DSP) using Pulse Width Modulation (PWM) for Direct
Digital Control (DDC) of all UPS control and monitoring functions.
4. Static bypass switch sized to provide fault clearing.
B. Battery system.
C. Battery protective and disconnect device.
D. Maintenance bypass switch (option).
E. Remote status alarm panel (option).
1.3.2 Mode of Operation
The UPS shall be designed to operate continuously at rated capacity as an on-line,
automatic reverse transfer system in the following modes:
A. Normal - The inverter continuously supplies AC power to the critical load. The
converter converts a utility AC power source to regulated DC power which then serves
as the inverter input and, simultaneously, as a float charge input to the storage battery.


Specyfikacje produktu

Marka: Mitsubishi
Kategoria: Niesklasyfikowane
Model: 9900D

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Mitsubishi 9900D, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Mitsubishi

Mitsubishi

Mitsubishi HMS100-W Instrukcja

8 Października 2024
Mitsubishi

Mitsubishi HMA60-W Instrukcja

8 Października 2024
Mitsubishi

Mitsubishi HMA100-W Instrukcja

8 Października 2024
Mitsubishi

Mitsubishi RLD-WR/1 Instrukcja

7 Października 2024
Mitsubishi

Mitsubishi 9900D Instrukcja

3 Października 2024
Mitsubishi

Mitsubishi RLD-KIT-E Instrukcja

3 Października 2024
Mitsubishi

Mitsubishi ESA30EH2 Instrukcja

29 Września 2024

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Stihl

Stihl HT 70 Instrukcja

15 Października 2024
Ernesto

Ernesto H14270 Instrukcja

15 Października 2024
Uniden

Uniden BT MIC KIT Instrukcja

15 Października 2024
Vaude

Vaude Omnis Bike 26 Instrukcja

15 Października 2024
ART

ART ProChannel II Instrukcja

15 Października 2024
Aukey

Aukey DR02J Instrukcja

15 Października 2024
Master Lock

Master Lock 653EURD Instrukcja

15 Października 2024
Roland

Roland FR-18 Diatonic Instrukcja

15 Października 2024