2400W Single Output Power Supply
RSP 2400 - series
Model: 2400 24RSP- - Test Report 1 / 6
MODEL
RSP- - 2400 24
OUTPUT FUNCTION TEST
NO
TEST ITEM
SPECIFICATION
TEST CONDITION
VERDICT
1 RIPPLE & NOISE
V1
150
mVp-p (Max )
I/P
230VAC
O/PFULL LOAD
Ta25
V1
95 p-mV p (Max )
P
2 OUTPUT VOLTAGE
ADJUST RANGE
CH1
22 V~ 28 V
I/P
230 VAC
O/PMIN LOAD
Ta25
21.31
21.30
V~
V~
28.92
28.92
V/ 230 VAC
V/ 180 VAC
P
3 OUTPUT VOLTAGE
TOLERANCE
V1
1 %~ - 1 % (Max)
I/P
180VAC / 264 VAC
O/PFULL/ MIN LOAD
Ta25
V1
0.05 %~
- % 0.05
P
4 LINE REGULATION V1 - 0.5 %~ 0.5 % (Max)
I/P180VAC ~ 264 VAC
O/PFULL LOAD
Ta25
V1
0.03 %~
- % 0.03
P
5 LOAD REGULATION
V1
-0.5 %~ 0.5 % (Max)
I/P
230 VAC
O/PFULL ~MIN LOAD
Ta25
V1
0.03 %~ - % 0.03
P
6 SET UP TIME
230VAC
1000
ms (Max)
I/P
230 VAC
O/PFULL LOAD
Ta25
230VAC/
533
ms
P
7 RISE TIME
230VAC
80
ms (Max)
I/P
230 VAC
O/PFULL LOAD
Ta25
230VAC/
57
ms
P
8 HOLD UP TIME
230VAC
12
ms (TYP)
I/P
230 VAC
O/PFULL LOAD
Ta25
230VAC/
25.7
ms
P
9 OVER/UNDERSHOOT
TEST
< + 5% I/P 230 VAC
O/PFULL LOAD
Ta
25
TEST < 5 %
P
10 DYNAMIC LOAD
V1
2400 -p mVp
I/P
230 VAC
O/PFULL /Min LOAD 90%DUTY/
1KHZ
Ta25
229 -p mVp
P
2400W Single Output Power Supply
RSP 2400 - series
Model: 2400 24RSP- - Test Report 2 / 6
INPUT FUNCTION TEST
NO
TEST ITEM
SPECIFICATION
TEST CONDITION
RESULT
VERDICT
1 INPUT VOLTAGE RANGE 180VAC~264 VAC I/PTESTING
O/PFULL LOAD
Ta25
171 V~264V
P
I/P
- - V LOW LINE 3V= 177
- HIGH LINE+15%=300 V
O/PFULL/MIN LOAD
ON30 Sec . OFF30 Sec 10MIN
( AC POWER ON/OFF NO DAMAGE )
TEST OK
2 INPUT FREQUENCY RANGE 47HZ ~63 HZ
NO DAMAGE OSC
I/P
180 VAC ~ 264 VAC
O/PFULL~MIN LOAD
Ta
25
TEST
OK
P
3 POWER FACTOR 0.95 / 230 VAC(TYP) I/P 230 VAC
O/PFULL LOAD
Ta25
PF= 0.965 / 230 VAC
P
4 EFFICIENCY 90 % (TYP) I/P 230 VAC
O/PFULL LOAD
Ta
25
90.8 %
P
5 INPUT CURRENT
230V/
12
A (TYP)
I/P
230 VAC
I/P 180 VAC
O/PFULL LOAD
Ta25
I =
11.94
A/ 230 VAC
P
180 80V/ 15.5 A (TYP) I = 15.41 A/ 1 VAC
6 INRUSH CURRENT 230V/ 60 A (TYP) I/P 230 VAC
O/PFULL LOAD
Ta25
I = 55 A/ 230 VAC
P
COLD START
7 LEAKAGE CURRENT < 2 mA / 240 VAC
I/P
264 VAC
O/PMin LOAD
Ta25
L-FG
1.3
mA
P
N-FG
1.35 mA
PROTECTION FUNCTION TEST
NO
TEST ITEM
SPECIFICATION
TEST CONDITION
RESULT
VERDICT
1 OVER LOAD PROTECTION 2 % 100%~11 I/P 230 VAC
O/PTESTING
Ta25
106.6%/ 230 VAC
Constant Current Limiting
P
2 OVER VOLTAGE PROTECTION
CH1
28.8V~ 33.6V
I/P
230 VAC
O/PMIN LOAD
Ta25
31.4V/ 230 VAC
Shut down Re- power ON
P
3 OVER TEMPERATURE PROTECTION SPEC
TSW1 + 5 100 O.T.P
detect on heatsink of power
transistor
TSW2 85 + 5 O.T.P
detect on heatsink of O/P diode
NO DAMAGE
I/P 230 VAC
O/PFULL LOAD
O.T.P. Active
Shut down o/p voltagerecovers
automatically after temperature
goes down
P
4 SHORT PROTECTION SHORT EVERY OUTPUT
1 HOUR NO DAMAGE
I/P 264 VAC
O/PFULL LOAD
Ta25
NO DAMAGE
CN3 PIN9- 10 SHORT:
Shut down Re power ON-
CN3 PIN9-10 OPEN:
Current Limit
P
2400W Single Output Power Supply
RSP 2400 - series
Model: 2400 24RSP- - Test Report 3 / 6
CONTROL FUNCTION TEST
NO
TEST ITEM
SPECICATION
TEST CONDITION
RESULT
VERDICT
1
AUXILIARY POWER
(AUX)
12V @ 0.1A
(Only for Remote ON/OFF control )
I/P 230 VAC
O/PFULL LOAD
Ta
25
11.907V
P
2 REMOTE CONTROL Table1.1 Fig1.2(a)(b)(c)
Specification of Remote ON/OFF
I/P
230 VAC
O/PFULL LOAD
Ta25
Connection
Method
Fig1.2(a)
Fig1.2(b)
Fig1.2(c)
SW
Logic
Output
on
SW
Open
SW
Open
SW
Close
Output
off
SW
Close
SW
Close
SW
Open
P
3 ALARM SIGNAL
OUTPUT
Table2.1 Explanation of alarm
Function
Description
P OK
The signal is "Low" when the power
supply is
80% of the rated output
voltage-Power OK
The signal turns to be "High" when
the power supply
is under 80% of the rated output
voltage-Power Fail
I/P
230 VAC
O/PFULL LOAD
Ta25
Output of alarm
(P OK, relay contact)
Output of alarm
(P OK2, TTL Signal)
Low
(0.5V max at 500mA)
Low
(0.5V max at 10mA)
High or open
(External applied
voltage 500mA max.)
High or open
(External applied
voltage 10mA max.)
P
4
OUTPUT VOLTAGE
PROGRAMMABLE(PV)
(1) Adjustment of output voltage is possible
between 20~110%(Typ.) of the rated
output which is shown in Fig. 3.1
(2) Connecting a resistor externally
between PV and S on CN1 or CN2 that is -
shown in Fig. 3.2
I/P 230 VAC
O/PNOL LOAD
Ta25
PV=1V , Vout= 4.908 V
PV=3V , Vout= 14.808 V
PV=5V , Vout= 24.29 V
PV=5.5,Vout= 26.54 V
P
5 CURRENT SHARING PSU1-PSU2 < 10%
I/P
230 VAC
O/P 90%/50%
LOAD
Ta25
O/P
90% LOAD
PSU189.3 A
PSU289.8 A
PSU3
91.5 A
P
O/P50%
PSU148.8 A
PSU249.4 A
PSU3
52.0 A
6 REMOTE SENSE >0.25V
I/P
230 VAC
O/PFULL LOAD
Ta
25
> 0.25 V
P
7 FAN SPEED
CONTROL
------- I/P 230 VAC
O/P FULL
/NOLOAD
Ta
25
NO LOAD Fan Voltage= 7.32 V
100% LOAD Fan Voltage= V 12.549 P


Specyfikacje produktu

Marka: Mean Well
Kategoria: Niesklasyfikowane
Model: RSP-2400-24

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Mean Well RSP-2400-24, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Mean Well

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Stihl

Stihl HT 70 Instrukcja

15 Października 2024
Ernesto

Ernesto H14270 Instrukcja

15 Października 2024
Uniden

Uniden BT MIC KIT Instrukcja

15 Października 2024
Vaude

Vaude Omnis Bike 26 Instrukcja

15 Października 2024
ART

ART ProChannel II Instrukcja

15 Października 2024
Aukey

Aukey DR02J Instrukcja

15 Października 2024
Master Lock

Master Lock 653EURD Instrukcja

15 Października 2024
Roland

Roland FR-18 Diatonic Instrukcja

15 Października 2024