Instrukcja obsługi Lowell ACR-SEQ6-2009

Lowell Niesklasyfikowane ACR-SEQ6-2009

Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Lowell ACR-SEQ6-2009 (3 stron) w kategorii Niesklasyfikowane. Ta instrukcja była pomocna dla 9 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/3
Lowell strives to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without prior notication.
©2021 Lowell Manufacturing Co., 100 Integram Dr., Pacic MO 63069 / tel. 800.325.9660 / www.lowellmfg.com
Spec 1607
Model ACR-SEQ6-2009 Rev. 05-11-21 | pg. 1/3
INTERNAL USE ONLY: PN 24209
DESCRIPTION: Model ACR-SEQ6-2009 power distribution
panel with sequencer features nine NEMA outlets—six switched
(controlled by power switch for sequential activation/deactivation)
and three unswitched (always on). Outlets are clearly marked
to assist the integrator with connections. The panel can also be
activated and deactivated by a remote switch or alarm system
that's connected to the plug-in barrier strip INPUT terminal blocks
in the rear. In addition, there's an OUTPUT terminal block where
remote power controls (RPCs) can be connected and controlled by
this panel. RPC devices would occupy steps ve and six in the
sequence order.
The compact steel chassis with black powder epoxy nish is
designed to occupy minimal rack space with overall dimensions
of 19"W x 9"D x 1.75"H (1U). Termination is via an attached nine
foot power cord with NEMA 5-20P plug.
FEATURES:
Outlets: Unit features a total of nine 15A NEMA outlets, which are
either switched (controlled by switch) or unswitched (always on).
Front Outlet:
NEMA 5-15R (1 unswitched single)
Rear Outlets:
NEMA 5-15R (2 unswitched single, 2 switched single,
2 switched duplex)
Activation & Sequencing: Front rocker switch with momentary
contacts (normally open SPST) plus rear barrier strip termination
blocks for momentary (normally open) remote switches. Switch
initializes the delayed start up sequence, activating the switched
outlets in four steps, plus any remote power controls (RPCs)
connected to the rear terminal block as steps ve and six. A green
LED ashes while the unit is powering up and holds steady when
the cycle is complete. The switch also initializes the delayed shut
down sequence, deactivating RPCs and outlets in reverse order. A
red LED ashes while the unit is powering down and holds steady
when the cycle is complete. Delay between steps can be adjusted
with a screwdriver (0.5–10 seconds).
Connections for External Controls: Plug-in barrier strip terminal
block inputs in the rear of the panel allow external controls to
activate and deactivate the switched outlets. The terminal block
output allows this panel to control remote RPC units.
Left Terminal Block—input from Alarm System: Lock On,
Lock Off, and Switch Lock for alarm system or master control
panel.
Center Terminal Block–output to Remote Power Control
(RPC): External RPC Series devices can be controlled when
connected to the center terminal block. The connected RPCs
would activate/deactivate as Steps 5 and 6.
Right Terminal Block—input from Remote Switch: Connect
a remote switch with momentary closure.
120VAC, 60Hz, 20A (outlets are 15A)Power Rating:
EMI/RFI Filter: 19dB@500kHz, 42dB@30MHz
Circuit Breaker Protection: 20A breaker with reset switch
Attached 9-ft. cord with NEMA 5-20P plugPower Cord:
19"W x 9"D x 1.75"H (1U), 11 lbs.Chassis:
Certication: ETL Listed in US/Canada (UL60065)
Country of Origin: Made in the U.S.A. with global components
A&E SPECIFICATIONS: The rackmount power distribution panel
with sequencer and remote power control circuitry shall be Lowell
Model ACR-SEQ6-2009. It shall feature a total of nine NEMA 5-15R
outlets (six switched in rear, two unswitched in rear, one unswitched
in front) and a 20A circuit breaker. A rocker style switch in the front
shall sequentially activate switched outlets in four steps, plus any
remote power control devices connected to the rear terminal block
as steps five and six (RPC Series, ordered separately). When pressed
again, the switch shall deactivate devices and outlets in reverse
order. Color coded LEDs on the front panel shall indicate sequencing
status and the delay between steps shall be screwdriver adjustable
(0.5 to 10 seconds). The panel shall have a power rating of 120VAC,
60Hz, 20A with EMI/RFI ltering. The 19"W x 9"D x 1.75"H (1U)
steel chassis shall have a black powder epoxy nish. Termination
shall be via an attached 9 ft. cord with NEMA 5-20P plug.
AC Power Distribution Panel w/Sequencer: ACR-SEQ6-2009
Rear view
Front view
System
circuit
breaker
NEMA
5-15R single
(unswitched)
Power
status
Power
switch
Sequence &
remote trigger status
Delay
adjust
Made in USA
Power cord
(attached) NEMA
5-15R single
(unswitched)
NEMA
5-15R single
(switched)
Step 2
NEMA
5-15R duplex
(switched)
Step 4
NEMA
5-15R single
(unswitched)
NEMA
5-15R single
(switched)
Step 1
NEMA
5-15R duplex
(switched)
Step 3
INPUT
from
alarm
system
INPUT
from
remote
switch
OUTPUT
to RPC
Steps
5 & 6
Lowell strives to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without prior notication.
©2021 Lowell Manufacturing Co., 100 Integram Dr., Pacic MO 63069 / tel. 800.325.9660 / www.lowellmfg.com
Spec 1607
Model ACR-SEQ6-2009 Rev. 05-11-21 | pg. 2/3
INTERNAL USE ONLY: PN 24209
WIRING: Since switch functions are handled by low-voltage, low-current DC signals, almost any type of wire will work (CAT5, mic line,
intercom wire, speaker wire, or phone wire). Shielding is not required but can be used.
Maximum wire distance: 24 ga.=20,000 ft., 22 ga.=31,200 ft., 18 ga.=76,800 ft.
CONNECTIONS for EXTERNAL CONTROLS: Plug-in barrier strip terminal block inputs allow external controls to activate and
deactivate switched outlets. The terminal block output allows this panel to control remote RPC units.
LEFT TERMINAL BLOCK – Input from Alarm System (or Master Control Panel):
If required by local building code, facility usage, or the Fire Marshal, system switches can be overridden
and the system controlled by contact closures provided by the re alarm panel or another similarly installed
device. A maintained contact between the ‘Com’ terminal and any of the terminals shown will provide the
following functions. CAUTION: Do not allow alarm system to make more than one of the contacts described
below at the same time—it could cause controller board damage
Lock OFF: A maintained contact between the ‘Com’ terminal and the ‘Lock Off’ terminal will turn the
system off and keep it off regardless of other switch activations. If the system is already off, it will be
kept off.
Lock ON: A maintained contact between the ‘Com’ terminal and the ‘Lock On’ terminal will turn the
system on and keep it on regardless of other switch activations. If the system is already on, it will be
kept on.
Switch Lock: A maintained contact between the ‘Com’ terminal and the ‘Switch Lock’ terminal will lock
the system in its current state, either on or off, regardless of any other switch activations.
CENTER TERMINAL BLOCK – Output to Remote Power Controls (RPC):
Connect Remote Power Controls to Output 5 and Output 6 in the center terminal block. The maximum num-
ber of RPC units that can be connected is 60 for each output, depending on limits of the electrical panel.
Note: Use RPC Series with classic connections. DO NOT use RPC-P Series with pass-through connections.
RIGHT TERMINAL BLOCK – Input from Remote Switch:
Connect remotely located momentary closure switch(es). Up to ve switches can be utilized.
Surge Protection Active When Lit (-S models only)
Power
Switch
Activated
Common
+24VDC Out
Switch
Common
+24VDC Out
Surge Protection Active When Lit (-S models only)
Power
Activated
5 6
Wiring to remote power controls
(RPC Series with classic connection)
Alarm System
Interface
Switch
Lock
Lock
ON
Lock
OFF
Com
RPC
Trigger
5 6
Remote
Switch(es)
Switch
OFF
Ind.
ON
Ind.
V+
Wiring to momentary switch w/1 LED
requires 3 conductors
Wiring to momentary switch w/2 LEDs
requires 4 conductors
Lowell strives to provide accurate information while reserving the right to change specications and/or improve manufacturing methods without prior notication.
©2021 Lowell Manufacturing Co., 100 Integram Dr., Pacic MO 63069 / tel. 800.325.9660 / www.lowellmfg.com
Spec 1607
Model ACR-SEQ6-2009 Rev. 05-11-21 | pg. 3/3
INTERNAL USE ONLY: PN 24209
OPTIONS: (order separately)
Lowell momentary closure switches:
Model Description Model Description
RPSW-MP 1 LED rocker switch, white wall plate RPSW2-MP 2 LED rocker switch, white wall plate
RPSB-MP 1 LED rocker switch, black wall plate RPSB2-MP 2 LED rocker switch, black wall plate
RPSB-MR 1 LED rocker switch, 19" panel RPSB2-MR 2 LED rocker switch, 19" panel
RPSW-MKP 1 LED key switch, white wall plate RPSW2-MKP 2 LED key switch, white wall plate
RPSB-MKP 1 LED key switch, black wall plate RPSB2-MKP 2 LED key switch, black wall plate
RPSB-MKR 1 LED key switch, 19" panel RPSB2-MKR 2 LED key switch, 19" panel
Compatible RPC Series remote power controls (classic connections only):
Model Number Description
RPC-15 RPC with (2) 15A NEMA outlets
RPC-15-S RPC with (2) 15A NEMA outlets, surge suppression
RPC-20-CD RPC with (2) 20A NEMA outlets
RPC-20-SCD RPC with (2) 20A NEMA outlets, surge suppression
RPC-3N1 RPC with (8) 15A NEMA outlets
RPC-20-HW RPC with (2) 20A NEMA outlets, hardwired
RPC-20-SHW RPC with (2) 20A NEMA outlets, surge suppression, hardwired
ACR Series Power Distribution Panels
Outlets Input from Input from Input from Output to
Power Front Rear Surge Power Switch Controlled Network Charging Time Remote External Alarm Remote Country
Model No. Rating Outlets Outlets Supp. Input Type by Switch Interface Ports Delay Switch Trigger System Control Lights of Origin
ACR-1505-SSI-RC 15A 1 (15A) 4 (15A) yes 6' cord --- --- yes rear --- --- --- --- --- --- USA
ACR-1506-LTS 15A --- 6 (15A) yes 9' cord rocker all --- --- --- --- --- --- --- hd USA
ACR-1507-GNLT 15A 1 (15A) 6 (15A) --- 9' det.cord rocker 2 --- --- --- --- --- --- --- goose USA
ACR-1507-HDLT 15A 1 (15A) 6 (15A) --- 9' det.cord rocker 2 --- --- --- --- --- --- --- hd-nt USA
ACR-1507-SSI-FC 15A 1 (15A) 6 (15A) yes 6' cord --- --- yes front --- --- --- --- --- --- USA
ACR-1508-SHW 15A --- 8 (15A) yes 6'
conduit
--- --- --- --- --- --- --- --- --- --- USA
ACR-1509-S 15A 1 (15A) 8 (15A) yes 9' cord rocker 3 --- --- --- --- --- --- --- --- China
ACR-159-S 15A 1 (15A) 8 (15A) yes 9' cord rocker all --- --- --- --- --- --- --- --- China
ACR-2009 20A 1 (15A) 8 (15/20A) --- 9' cord rocker 5 --- --- --- --- --- --- --- --- USA
ACR-209-S 20A 1 (20A) 8 (20A) yes 9' cord rocker all --- --- --- --- --- --- --- --- China
ACR-RPC-1508-SD 15A --- 8 (15A) yes 9' cord ext 6 --- --- --- yes yes yes --- --- USA
ACR-SEQ4-1509 15A 1 (15A) 8 (15A) --- 9' cord rocker & ext 6 --- --- SEQ yes --- yes --- --- USA
ACR-SEQ6-2009 20A 1 (15A) 8 (15A) --- 9' cord rocker & ext 6 --- --- SEQ yes --- yes yes --- USA
Surge Suppression = Panel includes basic surge suppression. (For rackmount panels with advanced surge suppression see ACSPR Series.)
Power Input = cord (attached cord), det.cord (detachable cord), conduit (non-metallic flexible conduit)
Switch Type (activation) = rocker (rocker switch on front), ext (external switch, not included)
Outlets Controlled by Switch = Number of outlets activated/deactivated by switch. Other outlets are unswitched (always on).
Network Interface = Panel includes network pass-through ports.
Charging Ports = Panel includes high speed charging connectors for devices (USB-A, Type-C)
Time Delay (SEQ) = Panel includes sequencing to activate/deactivate switched outlets with a time delay between steps (adjustable).
Input from Remote Switch = Panel can be controlled by an external switch, typically placed in a remote location (order RPS Series switch separately).
Input from External Trigger = Panel can be controlled by external trigger voltage (separate control system by others, not included).
Input from Alarm System = Panel can accept control override from an alarm system (alarm by others, not included).
Output to Remote Control = Panel can activate/deactivate remote equipment (order RPC Series remote power controls separately).
Lights = hd (hooded white light), goose (gooseneck lights), hd-nt (hooded night-vision lights)
See individual product spec sheets for more information.
This
spec


Specyfikacje produktu

Marka: Lowell
Kategoria: Niesklasyfikowane
Model: ACR-SEQ6-2009

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Lowell ACR-SEQ6-2009, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Lowell

Lowell

Lowell ACS-2010-RPC-HW Instrukcja

7 Października 2024
Lowell

Lowell ACS-2020-6C-HW Instrukcja

7 Października 2024
Lowell

Lowell RPC-15-S Instrukcja

7 Października 2024
Lowell

Lowell RPC-3N1 Instrukcja

7 Października 2024
Lowell

Lowell SEQ-8 Instrukcja

7 Października 2024
Lowell

Lowell ACSP-1502-VTE Instrukcja

7 Października 2024
Lowell

Lowell RPC-20-SCD Instrukcja

7 Października 2024
Lowell

Lowell ACS-1512 Instrukcja

7 Października 2024
Lowell

Lowell ACS-1506 Instrukcja

7 Października 2024

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Stihl

Stihl HT 70 Instrukcja

15 Października 2024
Ernesto

Ernesto H14270 Instrukcja

15 Października 2024
Uniden

Uniden BT MIC KIT Instrukcja

15 Października 2024
Vaude

Vaude Omnis Bike 26 Instrukcja

15 Października 2024
ART

ART ProChannel II Instrukcja

15 Października 2024
Aukey

Aukey DR02J Instrukcja

15 Października 2024
Master Lock

Master Lock 653EURD Instrukcja

15 Października 2024
Roland

Roland FR-18 Diatonic Instrukcja

15 Października 2024