Push-button controller, built-in
Light Management
Push-button controller, built-in
Art.-No.: 240-10 EB
Operationsmanual
1 Safety instructions
Electrical equipment may only be installed and fitted by electrically skilled persons.
Failure to observe the instructions may cause damage to the device and result in fire and
other hazards.
Danger of electric shock. Device is not suitable for disconnection from supply voltage.
Danger of electric shock. Always disconnect before carrying out work on the devise or
load. At the same time, take into account all circuit breakers that supply dangerous
voltage to the device or load.
These instructions are an integral part of the product, and must remain with the end
customer.
2 Device components
picture 1: Device components
(1) Control unit
(2) adjuster Basic brightness
(3) adjuster Memory
(4) 1-10 V interface
3 Function
Intended use
- Brightness setting for lamp operating devices with 1-10 V interface
- Installation in false ceilings or surface mounting
Product characteristics
- The light bulb is switched on and off via the load cable and dimmed via the 1-10 V
interface.
- Operation via installation button, NO contact
- Can be switched to memory function with brightness memory
- The 1-10 V interface is short-circuit proof for the control current.
1/5
82515713
J:0082515713 13.08.2010
4 Operation
Switch light
o Press push-button briefly.
Memory function switched off: light is switched on with maximum brightness or light is
switched off.
Memory function switched on: light is switched on with the last brightness set or light is
switched off.
Switch light on at minimum brightness
Memory function switched off.
o Long press on push-button until the light switches on.
Adjust the brightness
Light is switched on.
o Long press on push-button.
Memory function switched off: the light becomes brighter up to maximum brightness,
remains there briefly and becomes dimmer down to minimum brightness, remains there
briefly and becomes brighter again. This process repeats for as long as the push-button
remains pressed.
i The dimming direction is retained when there is another long press on the push-button.
Memory function switched on: the light becomes brighter or dimmer as far as the first limit
value, remains there briefly, and then changes the dimming direction. This process repeats
for as long as the push-button remains pressed.
i The dimming direction is reversed when there is another long press on the push-button.
i A mains failure of longer than 2 seconds deletes the stored brightness value.
5 Information for electrically skilled persons
5.1 Fitting and electrical connection
DANGER!
Electrical shock when live parts are touched.
Electrical shocks can be fatal.
Before carrying out work on the device or load, disengage all the
corresponding circuit breakers. Cover up live parts in the working environment.
2/5
82515713
J:0082515713 13.08.2010
Light Management
Push-button controller, built-in
Connecting and mounting the control unit.
picture 2: Connection diagram, single-phase
picture 3: Connection diagram, three-phase
(1) Control unit
(5) Lamp operating device with 1-10 V interface, electronic ballast
(6) Installation button, NO contact
i The load output is not protected internally. For device protection, connect a 10 A miniature
circuit breaker upstream.
i Control cable: appropriate type, cross-section and routing for the VDE specifications for
250 V cables, control voltage has basic insulation. The control cable and load cable can be
run in a shared cable, e.g. NYM J 5 x 1.5. Connect lamp operating device and electronic
ballast with earth conductor in accordance with the manufacturer's instructions.
i The maximum number of lamp operating devices that can be controlled by the control unit
is the sum of the control currents I1 + I2 + I3 (picture 2) and I (picture 3)(see chapter 6.1.
Technical data). For the control current of the lamp operating devices, see the information
provided by the manufacturer.
3/5
82515713
J:0082515713 13.08.2010
Light Management
Push-button controller, built-in


Specyfikacje produktu

Marka: JUNG
Kategoria: multimetr
Model: 240-10

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z JUNG 240-10, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje multimetr JUNG

JUNG

JUNG 240-10 Instrukcja

17 Sierpnia 2024

Instrukcje multimetr

Najnowsze instrukcje dla multimetr