Installation Instructions
Temperature transmitters
TA3xxx
TA4xxx
TA5xxx
TU3xxx
TU4xxx
TU5xxx
80270009 / 00 10 / 2017
UK
2
1 Safety instructions
Please read this document prior to set-up of the unit. Ensure that the product is
suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property can occur.
Improper or non-intended use may lead to malfunctions of the unit or to unwan-
ted effects in your application. That is why installation, electrical connection,
set-up, operation and maintenance of the unit must only be carried out by
qualified personnel authorised by the machine operator.
In order to guarantee the correct condition of the device for the operating time
the device must only be used in media to which the wetted parts are sufficiently
resistant (→ Technical data).
The responsibility whether the measurement devices are suitable for the
respective application lies with the operator. The manufacturer assumes no
liability for consequences of misuse by the operator. Improper installation and
use of the devices result in a loss of the warranty claims.
2 Functions and features
The unit detects the medium temperature and converts it into an analogue output
signal.
3
UK
3 Function
Fig. 1: Current output TAxxxx:
In the measuring range the output
signal is between 4 and 20 mA.
If the temperature is above or below
the measuring range, the analogue
output behaves as follows:
Temperature above the measuring
range: 20...20.6 mA.
Temperature below the measuring
range: 4...3.7 mA.
MAW MEW
20
20.6
4
3.7
T [°C/°F]
I [mA]
Fig. 2: Voltage output TUxxxx:
In the measuring range the output
signal is between 0.5 und 4.5 V.
If the temperature is above or below
the measuring range, the analogue
output behaves as follows:
Temperature above the measuring
range: 4.5...5V.
Temperature below the measuring
range: 0.5..0 V.
MAW MEW
4.5
5
0.5
T [°C/°F]
U [V]
T = Temperature
MAW = initial value of the measuring range
MEW = final value of the measuring range


Specyfikacje produktu

Marka: IFM
Kategoria: Niesklasyfikowane
Model: TY0058

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z IFM TY0058, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane IFM

IFM

IFM TW2001 Instrukcja

14 Stycznia 2025
IFM

IFM EVC231 Instrukcja

13 Stycznia 2025
IFM

IFM UGT582 Instrukcja

13 Stycznia 2025
IFM

IFM TY0058 Instrukcja

13 Stycznia 2025
IFM

IFM OT5012 Instrukcja

11 Stycznia 2025
IFM

IFM SUH201 Instrukcja

11 Stycznia 2025
IFM

IFM LW2760 Instrukcja

5 Stycznia 2025
IFM

IFM AL2305 Instrukcja

5 Stycznia 2025
IFM

IFM E30560 Instrukcja

5 Stycznia 2025
IFM

IFM E30559 Instrukcja

5 Stycznia 2025

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane