Installation Instructions
Electronic pressure sensor
PA95xx
704903 / 00 08 / 2010
UK
2
1 Safety instructions
Please read the product description prior to installing the unit.
Ensure that the product is suitable for your application without any restrictions.
If the operating instructions or the technical data are not adhered to, personal
injury and/or damage to property may occur.
Please check for all applications that the product materials (see Technical data)
are compatible with the media to be measured.
Use in gases at pressures > 25 bar only after contacting the manufacturer ifm.
For units with cULus approval and the scope of validity cULus:
The device shall be supplied from an isolating transformer having a secondary
Listed fuse rated as noted in the following table.
Overcurrent protection
Control-circuit wire size Maximum protective device rating
Ampere
AWG (mm2)
26 (0.13) 1
24 (0.20) 2
22 (0.32) 3
20 (0.52) 5
18 (0.82) 7
16 (1.3) 10
The Sensor shall be connected only by using any R/C (CYJV2) cord, having
suitable ratings.
Contents
1 Safety instructions ................................................................................................2
2 Function and features ...........................................................................................2
2.1 Applications ....................................................................................................2
3 Installation ............................................................................................................3
4 Electrical connection.............................................................................................3
5 Scale drawing .......................................................................................................4
6 Technical data .......................................................................................................5
3
UK
2 Function and features
The pressure sensor detects the system pressure and converts it into an analog
output signal.
0...10 V
2.1 Applications
Type of pressure: relative pressure
Order no. Measuring range Permissible
overload pressure
Bursting
pressure
bar PSI bar PSI bar PSI
PA9521 0...250 0...3 625 400 5 800 850 12 300
PA9522 0...100 0...1 450 300 4 350 650 9 400
MPa = bar ÷ 10 / kPa = bar × 100
Static and dynamic overpressures exceeding the indicated overload
pressure are to be avoided by taking appropriate measures.
The indicated bursting pressure must not be exceeded. Even if the bur-
sting pressure is exceeded only for a short time, the unit can be destroyed.
NOTE: Risk of injury!
3 Installation
Before mounting and removing the sensor, make sure that no pressure is
applied to the system.
Insert the unit in a suitable process connection (see type label “Port Size”).
Tighten firmly.
4 Electrical connection
The unit must only be connected by an electrician.
The national and international regulations for the installation of electrical
equipment must be observed.
Voltage supply to EN50178, SELV, PELV.


Specyfikacje produktu

Marka: IFM
Kategoria: Niesklasyfikowane
Model: PA9522

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z IFM PA9522, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane IFM

IFM

IFM TW2001 Instrukcja

14 Stycznia 2025
IFM

IFM EVC231 Instrukcja

13 Stycznia 2025
IFM

IFM UGT582 Instrukcja

13 Stycznia 2025
IFM

IFM TY0058 Instrukcja

13 Stycznia 2025
IFM

IFM OT5012 Instrukcja

11 Stycznia 2025
IFM

IFM SUH201 Instrukcja

11 Stycznia 2025
IFM

IFM LW2760 Instrukcja

5 Stycznia 2025
IFM

IFM AL2305 Instrukcja

5 Stycznia 2025
IFM

IFM E30560 Instrukcja

5 Stycznia 2025
IFM

IFM E30559 Instrukcja

5 Stycznia 2025

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane