Installation Instructions
Inductive sensor
with optical setting aid
701228 / 03 11 / 2007
UK
UK
UK
UK
UK
2
Function and features
This inductive sensor detects metals without contact and indicates their presence by
providing a switched signal.
The nominal sensing range (Sn) can be seen in the type designation on the type
label on the unit; operating distance (Sa) 0 ... 0,81 x Sn; (values based on standard
measurement with mild steel; a shorter sensing range for other metals).
Electrical connection
Disconnect power before connecting the sensor. Connection strictly to the indications
on the type label. The unit can be used as normally open ( ) or as normally
closed ( ).
Installation
Mounting by means of a mounting device.
Adjust the unit. Adjustment is correct
when the red LED light. Secure does not
by means of the nuts provided so that it
cannot work loose.
Non-flush installation.
21
c
LED yellow / red
d
Target
Open space around the sensing face when mounted in metal:
3 x Sn
D
D
D
2 x Sn
3
UK
Minimum distance when several sensors of the same type are mounted:
2 x DD D
8 x Sn
Operation
Check the safe functioning of the sensor. Display by LEDs:
The yellow LED is lit when the output is switched.
The red LED is lit in case of faulty adjustment.
output function
LED yellow
No object in the detection range.
LED red
LED yellow
Safe detection of the object.
LED red
LED yellow Unsafe detection of the object
(readjust the unit).
LED red
LED yellow Uncertain function: predamping of the
unit by metal deposits or insufficient
open space around the active face;
(clean the active face or readjust the unit).
LED red
The operation of the sensor is maintenance-free.
For perfect functioning make sure that:
the sensing face and the open space are kept free of metal deposits and foreign
bodies, particularly for installation with the sensing face facing upwards;
EMC: The unit conforms to the requirements of EN 60947-5-2.


Specyfikacje produktu

Marka: IFM
Kategoria: Niesklasyfikowane
Model: IG5907

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z IFM IG5907, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane IFM

IFM

IFM TW2001 Instrukcja

14 Stycznia 2025
IFM

IFM EVC231 Instrukcja

13 Stycznia 2025
IFM

IFM UGT582 Instrukcja

13 Stycznia 2025
IFM

IFM TY0058 Instrukcja

13 Stycznia 2025
IFM

IFM OT5012 Instrukcja

11 Stycznia 2025
IFM

IFM SUH201 Instrukcja

11 Stycznia 2025
IFM

IFM LW2760 Instrukcja

5 Stycznia 2025
IFM

IFM AL2305 Instrukcja

5 Stycznia 2025
IFM

IFM E30560 Instrukcja

5 Stycznia 2025
IFM

IFM E30559 Instrukcja

5 Stycznia 2025

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane