Operating instructions
Compact speed monitor M18
DI6005
11473498 / 0007 / 2022
GB
DI6005 Compact speed monitor M18
6
4 Function
The unit has two independently configurable switching channels.
About the measuring function:
The sensor measures the time between 2 successive transitions from “undamped” to “damped”. The
pulse/pause ratio undamped/damped is not relevant, but both the damped and undamped states
should be reliably detected.
If the frequency determined from this time [1/min] is below the last measured value, the output speed
decreases with 1/t. At less than 0.5 pulses/min, 0.0 pulses/min is measured. There is no underload.
An overload is present at over 32,000.0 pulses/min (533 Hz).
4.1 Single-point mode
SP1
H
SSC
0 PDV
OFF ON
Fig.1: Normally open = low active (factory setting)
SP1: Switch-off point
SP1+H: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP1
ON OFF
Fig.2: Normally closed = high active
SP1: Switch-on point
SP1+H: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1 + H
SP1
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active
DI6005 Compact speed monitor M18
8
4.3 Two-point mode
SP2 SP1
H
SSC
0 PDV
OFF ON
Fig.5: Normally open = low active
SP2: Switch-off point
SP1: Switch-on point
If a set rotational speed is not reached, the transistor output will signal this as non-conducting.
H
SSC
0 PDV
SP2 SP1
ON OFF
Fig.6: Normally closed = high active
SP2: Switch-on point
SP1: Switch-off point
If a set rotational speed is not reached, the transistor output will signal this as conducting.
Imp./min.
3000
2500
2000
1500
1000
500
0
1
0
1
0
OUT
2
3
4
1
OUT
SP1
SP2
t
1: Power-on delay time
2: Start-up delay
3: Normally open = low active
4: Normally closed = high active
It is also possible to configure SP1 as the lower switch point and SP2 as the upper switch point.
The lower switch point must be at least 10% lower than the higher switch point.
4.4 IO-Link mode
IO-Link allows the configuration of internal parameters such as switching threshold, start-up delay and
switching behaviour (normally closed/normally open) as well as reading the current measured values.
Furthermore IO-Link protects against signal faults and measured value losses as well as tampering
with the sensor. IO-Link facilitates the identification of connected devices in the system and provides
diagnostic functions.


Specyfikacje produktu

Marka: IFM
Kategoria: Niesklasyfikowane
Model: DI6005

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z IFM DI6005, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane IFM

IFM

IFM TW2001 Instrukcja

14 Stycznia 2025
IFM

IFM EVC231 Instrukcja

13 Stycznia 2025
IFM

IFM UGT582 Instrukcja

13 Stycznia 2025
IFM

IFM TY0058 Instrukcja

13 Stycznia 2025
IFM

IFM OT5012 Instrukcja

11 Stycznia 2025
IFM

IFM SUH201 Instrukcja

11 Stycznia 2025
IFM

IFM LW2760 Instrukcja

5 Stycznia 2025
IFM

IFM AL2305 Instrukcja

5 Stycznia 2025
IFM

IFM E30560 Instrukcja

5 Stycznia 2025
IFM

IFM E30559 Instrukcja

5 Stycznia 2025

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane