Operating instructions
AS-i PCB module
AC2750
AC2751
AC2752
AC2753
80285129/00 04/2019
UK
2
1 Preliminary note
An instruction is indicated by "►".
Example: ► Mount the unit as shown.
Important note
Non-compliance can result in malfunction or interference.
2 Safety instructions
Please read the operating instructions prior to set-up of the device.
Ensure that the product is suitable for your application without any restrictions.
The unit conforms to the relevant regulations and EC directives.
Improper or non-intended use may lead to malfunctions of the unit or to
unwanted effects in your application.
Installation, electrical connection, set-up, operation and maintenance of the
unit must only be carried out by qualified personnel authorised by the machine
operator.
3 Functions and features
The AS-i module functions as digital I/O slave in the AS-i system and is exclusively
supplied via AS-i. It connects 4 sensors (2-wire sensors or 3-wire sensors) and
max. 4 actuators (pnp) with the AS-i master.
Maximum number of modules per master: 62 (A/B slave)
Watchdog function: If the connection to the master is interrupted for more than
40 ms, all outputs are disconnected.
AS-Interface version 3.0, downward compatible
4 Installation
Disconnect the system from power before installation.
Install the module in a protected location, e.g. in a housing with at least IP 54.
Use the supplied adhesive pad or the DIN rail adapter E70432 (accessory) for
fixing.
When using the adhesive pad, the surfaces must be kept free from dust, oil,
release agents and other kinds of contamination.
3
UK
Position the adhesive pad in the centre of the back of the PCB module.
Carry out a set-up test after installation of the module.
5 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment
must be adhered to.
Disconnect the installation from power and connect the unit.
5.1 External protective circuitry for inductive loads
The switch-on and switch-off capacity for triggering solenoids is rated up to 2.5 W
(IEC 60947-5-1, utilisation category DC-13).
Recommendation: For inductive loads use a free wheel diode on the load.
5.2 Wiring
AC2750 (4 DI / 4 DO) / AC2751 (4 DI / 3 DO)
Connection cables
I1 WH (white)
I2 WH (white)
I3 WH (white)
I4 WH (white)
O1 YE (yellow)
O2 YE (yellow)
O3 YE (yellow)
O4 YE (only AC2750)
0- BK (black)
I+ RD (red)
AS-i - (FLT) BU (blue)
AS-i + (PWR) BN (brown)
Switching input sensor 1
Switching input sensor 2
Switching input sensor 3
Switching input sensor 4
Switching output actuator 1
Switching output actuator 2
Switching output actuator 3
Switching output actuator 4
Sensor and actuator supply 0 V
Sensor and actuator supply 24 V
AS-i -
AS-i +


Specyfikacje produktu

Marka: IFM
Kategoria: Niesklasyfikowane
Model: AC2750

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z IFM AC2750, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane IFM

IFM

IFM TW2001 Instrukcja

14 Stycznia 2025
IFM

IFM EVC231 Instrukcja

13 Stycznia 2025
IFM

IFM UGT582 Instrukcja

13 Stycznia 2025
IFM

IFM TY0058 Instrukcja

13 Stycznia 2025
IFM

IFM OT5012 Instrukcja

11 Stycznia 2025
IFM

IFM SUH201 Instrukcja

11 Stycznia 2025
IFM

IFM LW2760 Instrukcja

5 Stycznia 2025
IFM

IFM AL2305 Instrukcja

5 Stycznia 2025
IFM

IFM E30560 Instrukcja

5 Stycznia 2025
IFM

IFM E30559 Instrukcja

5 Stycznia 2025

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane