Instrukcja obsługi HP RT3000
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla HP RT3000 (18 stron) w kategorii UPS. Ta instrukcja była pomocna dla 3 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek
Strona 1/18
HP Tower UPS
User Guide
Abstract
This document is for the person who installs and maintains HP UPS products. HP assumes you are qualified
in the installation of electrical equipment and trained in recognizing hazards in products with hazardous
energy levels.
Part Number: 792523-001
November 17, 2014
Edition: 1
Page 2 792523-001 Edition 1
ENGLISH
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The Tower UPS models that are covered in this manual are intended for installation in an environment
within 0 to 40°C/32 to 100°F, free of conductive contaminant.
For all models:
• FCC/EN55022 Class B IEC62040-2 C1
Certication Standards
• UPS directives: UL 1778 4th edition (UL listed).
• Performance: IEC 62040-3: 2001.
• Radiated emission: FCC CFR 47 part 15 subpart B, Class B, VCCI.
• Surges withstand ability: IEEE ANSI C62.41 Category A2 (UL Listed).
Regulatory Notices
See HP EG regulatory notices at http://www.hp.com/support/Safety-Compliance-EnterpriseProducts.
792523-001 Edition 1
Page 3
ENGLISH
Personal Safety
• The system has an internal battery as a backup power source. Consequently, the power outlets may be energized,
even if the system is disconnected from the AC power source.
• Dangerous voltage levels are present within the system. It should be opened exclusively by qualied
service personnel.
• The system must be properly grounded.
• There are no user serviceable parts inside except for the replaceable battery.
• The battery supplied with the system contains small amounts of toxic materials.
• To avoid accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the
required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a re. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
Precautions must be taken for all handling:
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground.
Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock
can be reduced if such grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
Product Safety
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• A protection circuit breaker must be installed upstream and be easily accessible.
The system can be disconnected from the AC power source by opening this circuit breaker.
• Check that the indications on the rating plate correspond to your AC powered system and to
the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the outlet shall be installed near the equipment and shall
be easily accessible.
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The storage temperature range is -15 to +40ºC/5 to 104°F.
• The system is not for use in a computer room AS DEFINED IN the standard for the Protection
of Information Technology Equipment, ANSI/NFPA 75 (US installations only).
Special Precautions
• All handling operations will require at least two people (unpacking, installation in rack system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature
less than 25°C/77°F). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the battery module, it is imperative to use the same type and number of
element as the original battery module provided with the UPS to maintain an identical level of
performance and safety. For questions, contact your HP representative.
Important: Replace the battery module with the same type battery module, available from HP.
Specyfikacje produktu
Marka: | HP |
Kategoria: | UPS |
Model: | RT3000 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z HP RT3000, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS HP
28 Czerwca 2024
28 Czerwca 2024
Instrukcje UPS
- UPS Ikea
- UPS AEG
- UPS Lenovo
- UPS Voltcraft
- UPS LC-Power
- UPS Conceptronic
- UPS Siemens
- UPS APC
- UPS Tripp Lite
- UPS Block
- UPS Gembird
- UPS V7
- UPS Dell
- UPS Digitus
- UPS Schneider
- UPS FSP
- UPS GYS
- UPS Online USV
- UPS LevelOne
- UPS Equip
- UPS Emerson
- UPS CyberPower
- UPS JUNG
- UPS Eaton
- UPS Adj
- UPS PowerWalker
- UPS Salicru
- UPS Energenie
- UPS Steren
- UPS East
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Furman
- UPS Minuteman
- UPS Riello
- UPS Maruson
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Approx
- UPS Altronix
- UPS Bxterra
- UPS Middle Atlantic
- UPS Atlantis Land
- UPS FSP/Fortron
Najnowsze instrukcje dla UPS
15 Stycznia 2025
15 Stycznia 2025
14 Stycznia 2025
14 Stycznia 2025
14 Stycznia 2025
14 Stycznia 2025
14 Stycznia 2025
9 Stycznia 2025
9 Stycznia 2025
9 Stycznia 2025