TECHNICAL REFERENCE MANUAL
31-00102-02
BACnet Protocol Implementation
Conformance Statement
BACNET FIXED FUNCTION THERMOSTAT
PRODUCT DESCRIPTION
Honeywell's BACnet® Fixed Function Thermostat, BACnet FF, is a configurable device with 19 pre-loaded applications.
The thermostat is a communicating, intelligent sensor-controller combination with built-in temperature and humidity
sensors used to control applications such as roof top units, fan-coil units and heat pumps. The thermostat communicates
over an MS/TP LAN so it operates as a fully-functioning BACnet controller and easily integrates with the building
automation system. The two available models are TB3026B and TB3026B-W, which includes a wireless sensor option.
Table 1. BACnet Standardized Device Profile (Annex L).
Table 2. List all BACnet Interoperability Building Blocks Supported (see Annex K).
Table 3. Segmentation Capability.
Table 4. Standard Object Types Supported.
Description
BACnet Advanced Workstation (B-AWS)
BACnet Operator Workstation (B-OWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
DS-RP-A,B SCHED-I-B DM-DDB-A,B
DS-RPM-B DM-DOB-B
DS-WP-A,B DM-DCC-B
DS-WPM-B DM-PT-A,B
DM-TS-B
DM-UTC-B
DM-RD-B
Description
Able to transmit segmented messages Window Size:
Able to receive segmented messages Window Size:
Device
Dynamically Creatable: No
Dynamically Deletable: No
BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
31-00102—02 2
Optional Properties Supported: Location
Description
Local_Time
Local_Date
Daylight_Saving_Status
UTC_Offset
Max_Master
MAX_Info_Frames
Writable Properties: Object_Name Limit: 30 Characters
Location Limit: 30 Characters
Description Limit: 30 Characters
UTC_Offset Range: -780...780
APDU_Timeout Range: 1000...60000
Number_Of_APDU_Retries Range: 0...16
MAX_Info_Frames Range: 1…60
Proprietary Properties: aler-devinfo (512) Datatype: Octet String
Purpose: Diagnostics.
Analog Input
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Description Limit: 30 Characters
Proprietary Properties: n/a
Analog Output
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Present_Value Range: 0...102.4
Description Limit: 30 Characters
Proprietary Properties: n/a
Analog Value
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Present_Value Range: REAL
Description Limit: 30 Characters
Proprietary Properties: n/a
Binary Input
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Description Limit: 30 Characters
Proprietary Properties: n/a
Binary Output
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Present_Value
Description Limit: 30 Characters
Proprietary Properties: n/a
BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT
3 31-00102—02
Binary Value
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Priority_Array (only on BV40)
Relinquish_Default (only on BV40)
Writable Properties: Present_Value
Description Limit: 30 Characters
Relinquish_Default
Proprietary Properties: n/a
Calendar
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: Date_List
Proprietary Properties: n/a
Multistate Value
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: State_Text
Writable Properties: Present_Value Limit: Preset Values
Proprietary Properties: n/a
File
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Writable Properties: n/a
Proprietary Properties: n/a
Program
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Reason_for_Halt
Description_of_Halt
Program_Location
Instance_of
Writable Properties: Program_Change
Proprietary Properties: n/a
Schedule
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description
Weekly_Schedule
Exception-Schedule
Writable Properties: Weekly_Schedule
Priority-for-Writing
Proprietary Properties: n/a

Specyfikacje produktu

Marka: Honeywell
Kategoria: termostat
Model: BACnet TB3026B

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Honeywell BACnet TB3026B, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje termostat Honeywell

Instrukcje termostat

Najnowsze instrukcje dla termostat

Siemens

Siemens RDG100T Instrukcja

15 Października 2024
Junkers

Junkers TA 21E Instrukcja

14 Października 2024
Oreg

Oreg AT90E Instrukcja

9 Października 2024
Oreg

Oreg AT60E Instrukcja

9 Października 2024
Heatit

Heatit PRO Instrukcja

9 Października 2024
Heatit

Heatit MULTIREG6 Instrukcja

9 Października 2024
Avidsen

Avidsen HomeFlow W Instrukcja

9 Października 2024
ORNO

ORNO OR-SH-17701 Instrukcja

8 Października 2024
ORNO

ORNO OR-SH-17702 Instrukcja

8 Października 2024
STI

STI -9102 Instrukcja

8 Października 2024