5.36 General Catalogue • Modular Devices • Technical
Contactor selection
Heating
The choice of the contactor depends on the mechanical endurance
(number of operations) and on the electrical heating load
i.e. resistive elements, infra-red element, convectors.
Choice of Contactors
The choice of contactor is dependant upon many parameters
i.e. operating voltage, size of contacts, number of operations,
ambient temperature, type of load supplied etc.
Type of Load
Loads are categorised into various AC ratings, (AC1, AC2, AC3 etc.)
and the higher the AC rating the more inductive the load becomes.
All Hager contactor ratings are given at AC1, therefore they must be
de-rated if used on other types of AC load.
Heat Dissipation Inserts
The ambient temperature around a contactor can affect its life
expectancy, therefore, we strongly recommend that heat
dissipation inserts (LZ060) are tted between all contactors and
adjacent devices.
U R R
R
R
R
U
U
U
Single Phase Three Phase
Motors
Single Phase 230V (AC3 or AC7b) Three Phase 400V (AC3 or AC7b)
L1 U
V
M
L2
L1 U
W
M
L3
L2 V
Choice of Contactor According to control diagram
Single Phase with Capacitor 230V Three Phase (AC3 or AC7) 400V 2 Wires 3 Wires
Maximum
load in kW
0.88 2 pole 25A
2.6 2 pole 40A
2.6 3 pole 25A
7.8 3 pole 40A
10 3 pole 63A
Requirements of Use
Influence of Working Temperature
Derating factor between 40°C and 50°C : 0.9
Example: Heating with convector
The maximum load of ESC225 is 4.6kW for 50,000 operations and for
a temperature <40°C.
between 40°C and 50°C, the load is 4.6 x 0.9 i.e. 4.14kW
Close Fitting
It is necessary to put a heat dissipation insert (reference LZ060)
between each contactor.
Number of operations
100,000 150,000 200,000 500,000 1,000,000
Max. load in kW
230V
16A 3 2.5 1.9 0.85 0.7
25A 4.6 4 3 1.35 1
40A 7.3 6.3 4.7 2.2 1.6
63A 11.6 10 7.5 3.5 2.5
400V
16A 8.9 8 5.8 2.8 2
25A 13.8 12 8.6 4.3 3
40A 22 18.5 14.385 6.3 5
63A 35 30 22.6 10.2 7.6
5.37
Sales Service Centre • 01952 675612 Technical Support Helpline • 01952 675689
Contactors and Override Contactors
Description Modular contact Auxiliary
contact
Standard conformity EN 61095
Approvals NF - VDE- IMQ - KEMA - RMC / CCC
Relay Contactor Relay Contactor Contactor Contactor Contactor
Number of modules 1 2 3 ½
Thermal current lth (40ºC) 16A 25A 16A 25A 40A 63A 6A
Rated frequency 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz 50 - 60 Hz
Rated insulation voltage (Ui) 250V 250V 440V 440V 440V 440V 250V
Rated impulse withstand voltage (Uimp) 4kV 4kV 4kV 4kV 4kV 4kV 4kV
Protection Degree 2 2 2 2 2 2 2
Rated Operating currents and power ratings in AC
AC-1 / AC-7a Rated operational currents Ie 16A 16A 16A 25A 40A 63A -
Rated operational power 230V 3kW 4.6kW 3kW 4.6kW 7.3kW 11.6kW -
400V - - 8.9kW 13.8kW 22kW 35kW -
AC-3 / AC-7b Rated operational currents Ie 5.5A 8.5A 5.5A 8.5A 25A 32A -
Rated operational power 230V 570W 880W 570W 880W 2.6kW 3.3kW -
400V - - 1.7kW 2.6kW 7.8kW 10kW -
AC-12 Rated operational currents Ie @
230V ------6A
AC-15 Rated operational currents Ie @
230V ------2A
Mechanical and Electrical Endurances
Mechanical endurance Number of
operations 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000 1,000,000
Electrical endurance @ Ie AC7a (AC12
for aux contact)
Number of
operations 60,000 60,000 60,000 60,000 60,000 60,000 60,000
MCB Protected short-circuit withstand
Prospected short-circuit current rms 1kA 3kA 1kA 3kA 3kA 3kA 1kA
Associated protection MCB C16-6kA MCB C25-6kA MCB C16-6kA MCB C25-6kA MCB C40-
10kA
MCB C63-
10kA
6A 10x38 gG
Fuse
Power dissipation
Power dissipation per current path 1W 1.5W 1W 1.5W 3.2W 5W 0.4W
Magnetic system for Eco and standard contactor
Pick-up 2.2W 2.2W 2.8W 2.8W 5W 5W -
Coil consumption 2.2W 2.2W 2.8W 2.8W 5W 5W -
Closing delay 25ms 25ms 25ms 25ms 25ms 25ms -
Opering delay 15ms 15ms 15ms 15ms 20ms 20ms -
Connection
Main contact cable section Rigid 1...10mm
21...10mm21...10mm21...10mm24...25mm24...25mm21...6mm2
Flexible 1...6mm21...6mm21...6mm21...6mm24...16mm24...16mm21...6mm2
Main contact connection screw Type M3.4 M3.4 M3.4 M3.4 M5 M5 M3.4
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 PZ2
Max. tight.
torque 1.2Nm 1.2Nm 1.2Nm 1.2Nm 2Nm 2Nm 1.2Nm
Coil connection cable section Rigid 1...10mm
21...10mm21...10mm21...10mm21...10mm21...10mm2-
Flexible 1...6mm21...6mm21...6mm21...6mm21...6mm21...6mm2-
Coil connection screw Type M3.5 M3.5 M3.5 M3.5 M4 M4 -
Posidrive PZ2 PZ2 PZ2 PZ2 PZ2 PZ2 -
Max. tight.
torque 1.2Nm 1.2Nm 1.2Nm 1.2Nm 1.5Nm 1.5Nm -
Working temperature
-10ºC to +50ºC
Storage temperature
-40ºC to +80ºC
Modular
Devices
5.38 General Catalogue • Modular Devices • Technical
Contactors & Relays cont.
Lamp Power 16A 25A 16A + 25A + 40A 63A
Compact fluo lamps
Compact uo lamp with
external electronic ballast
5W 11 15 17 27 49 76
7W 11 15 17 27 49 76
9W 9 13 16 26 40 63
11W 9 13 16 26 40 63
15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
23W 7 11 14 22 36 57
26W 7 11 14 22 36 57
Compact uo lamp with
integrated electronic ballast
5W 17 27 34 54 86 135
7W 17 27 34 54 86 135
9W 17 27 34 54 86 135
11W 17 27 34 54 86 135
15W 17 27 34 54 86 135
18W 13 20 25 40 63 100
20W 13 20 25 40 63 100
23W 13 20 25 40 63 100
26W 13 20 25 40 63 100
Incandescent lamps
Tungsten & halogen lamps
230V
40W 32 50 36 57 76 120
60W 21 33 28 45 67 105
75W 17 27 24 38 63 100
100W 13 20 17 28 41 65
150W 8 13 11 18 29 45
200W 6 9 8 14 22 35
300W 4 7 6 10 15 23
500W 2 3 3 6 9 14
1000W 0 0 1 2 4 7
Tungsten & halogen lamps
12 ou 24V
20W 13 20 25 40 139 218
35W 8 13 16 26 82 129
50W 6 9 11 18 60 94
75W 4 6 7 12 52 82
100W 2 3 3 6 35 55
150W 1 2 2 4 20 31
LED
LED 230V with integrated
electronic ballast - non
dimmable
4W 17 27 34 54 86 135
4.5W 17 27 34 54 86 135
6W 17 27 34 54 86 135
7W 17 27 34 54 86 135
8W 17 27 34 54 86 135
12W 17 27 34 54 86 135
17W 13 20 25 40 63 101
18W 13 20 25 40 63 101
22W 13 20 25 40 63 101
30W 9 14 17 28 44 70
34W 9 14 17 28 44 70
40W 9 14 17 28 44 70
50W 7 11 14 22 35 55
LED 230V with integrated
electronic ballast - dimmable
4W 38 60 76 120 159 250
5.5W 38 60 76 120 159 250
6W 38 60 76 120 159 250
7W 38 60 76 120 159 250
8W 38 60 76 120 159 250
12W 38 60 76 120 159 250
17W 28 44 56 88 118 185
18W 28 44 56 88 118 185
22W 28 44 56 88 118 185
30W 20 31 39 62 82 130
34W 20 31 39 62 82 130
40W 20 31 39 62 82 130
50W 16 24 30 48 65 102
LED 230V headlight with
integrated electronic ballast
100W - - 3 5 6 9
150W - - 1 3 4 6
200W - - 1 2 4 6
LED 12V with separated
transformer - dimmable
1W 38 60 76 120 180 220
2.5W 38 60 76 120 180 220
4W 38 60 76 120 180 220
5W 38 60 76 120 180 220
7W 38 60 76 120 160 200
10W 38 60 76 120 160 200
15W 28 44 56 88 160 200
Fluorescent tubes
T5 single - uncompensated 15W 13 20 19 30 70 100
18W 13 20 19 30 70 100
20W 12 19 19 30 70 100
36W 12 15 17 28 60 90
40W 10 13 16 26 60 90
42W 9 12 15 24 55 83
58W 7 9 10 17 35 56
65W 6 8 10 17 35 56
80W 5 7 9 15 30 48
115W 4 5 6 10 20 32
140W 3 5 6 10 16 26
T5 single - paralell
compensation
15W 7 11 12 20 36 57
18W 7 11 12 20 36 57
20W 7 11 12 20 36 57
36W 7 11 12 20 34 53
40W 7 11 12 20 29 45
42W 7 11 12 20 29 45
58W 6 10 9 15 27 42
65W 6 10 9 15 27 42
80W 6 10 9 15 27 42
115W 6 10 9 15 25 39
Lamp Power 16A 25A 16A + 25A + 40A 63A
Fluorescent tubes
T5 double - uncompensated 2 x 18W 13 20 25 40 50 78
2 x 20W 12 19 24 38 50 78
2 x 36W 12 15 19 30 44 69
2 x 40W 10 13 16 26 40 63
2 x 42W 9 12 15 24 40 63
2 x 58W 7 9 11 18 27 42
2 x 65W 6 8 10 16 27 42
2 x 80W 5 7 8 14 22 35
2 x 115W 4 5 6 10 16 25
T5 double - serie
compensation
2 x 18W 7 11 14 22 34 53
2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25
T5 single - electronic ballast 15W 7 11 14 22 36 57
18W 7 11 14 22 36 57
20W 7 11 14 22 36 57
36W 7 11 14 22 34 53
40W 7 11 14 22 29 45
42W 7 11 14 22 29 45
58W 6 10 12 20 27 42
65W 6 10 12 20 27 42
80W 6 10 12 20 27 42
115W 6 10 12 20 25 39
T5 double - electronic ballast 2 x 18W 7 11 14 22 34 53
2 x 20W 7 11 14 22 29 45
2 x 36W 6 10 12 20 27 42
2 x 40W 6 10 12 20 27 42
2 x 42W 6 10 12 20 27 42
2 x 58W 6 10 12 20 25 39
2 x 65W 5 7 8 14 23 36
2 x 80W 5 7 8 14 20 31
2 x 115W 4 5 6 10 17 25
Discharge lamps
High-pressure mercury-
vapor lamps - without
compensation
50W 9 14 17 28 32 50
80W 6 9 11 18 24 37
125W 3 5 6 10 18 28
250W 2 3 3 6 10 15
400W 1 1 1 2 6 9
700W 0 0 0 0 4 5
High-pressure mercury-
vapor lamps - paralell
compensation
50W 7 11 14 22 26 40
80W 5 8 10 16 22 34
125W 3 5 6 10 15 23
250W 2 3 3 6 9 14
400W 1 1 1 2 5 8
700W 0 0 0 0 3 5
1000W 0 0 0 0 2 3
Low pressure sodium lamps
- without compensation
18W 8 10 8 12 17 23
35W 4 6 7 9 14 20
55W 3 6 7 9 14 20
90W 2 4 5 6 9 14
135W 1 3 3 4 6 8
180W 1 2 2 4 6 8
Low pressure sodium lamps
- paralell compensation
18W 5 7 5 8 12 24
35W 4 6 4 7 10 23
55W 3 5 3 5 10 19
90W 2 3 3 4 8 16
135W 1 2 1 2 5 7
180W 1 2 1 2 5 6
High pressure sodium lamps
- without compensation
35W 11 14 15 24 30 50
50W 9 12 10 15 22 34
70W 8 9 8 12 18 28
110W 6 8 6 10 14 22
150W 4 7 5 8 10 16
250W 2 4 3 5 6 10
400W 0 1 1 2 4 6
1000W 0 1 1 1 2 3
High pressure sodium-
vapour lamps - electronic
ballast or parallel
compensation
35W 6 9 11 18 31 50
50W 6 9 11 18 22 35
70W 4 6 7 12 16 25
110W 3 5 6 8 13 21
150W 3 5 4 6 8 13
250W 2 3 3 4 7 11
400W 1 1 1 2 5 8
1000W 0 0 0 1 2 3
Metal halide lamps - without
compensation
35W 12 24 19 30 42 55
70W 10 15 12 17 26 36
150W 6 7 8 12 14 20
250W 3 5 5 8 9 14
400W 1 2 2 4 6 9
1000W 0 0 0 0 3 5
Metal halide lamps -
electronic ballast or parallel
compensation
35W 6 10 12 18 22 39
70W 5 8 10 13 22 39
150W 3 5 6 8 12 22
250W 3 5 6 7 9 16
400W 1 1 1 2 5 7
1000W 0 0 0 1 2 3
Lighting systems with electronic ballasts cause inrush current peaks. Therefore we recommend you use the chart below to determinate the maximum amount of
lamps that can be connected to a Hager contactor: The chart gives the maximum amount of lamps per contact. In 2014 the performances of the contactors in
combination with lights increased. The products identi ed on the front face with the ‘+’ can accept a higher number of lamps. For these products, see the gures in  
the column with the ‘+’ in the header.


Specyfikacje produktu

Marka: Hager
Kategoria: przełącznik
Model: ESC340

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager ESC340, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje przełącznik Hager

Hager

Hager ESC225 Instrukcja

1 Stycznia 2025
Hager

Hager SPB413 Instrukcja

30 Grudnia 2025
Hager

Hager LVSR3TP Instrukcja

9 Grudnia 2024
Hager

Hager EE110 Instrukcja

9 Grudnia 2024
Hager

Hager HIB416M Instrukcja

9 Grudnia 2024
Hager

Hager LVSG2CPX Instrukcja

9 Grudnia 2024
Hager

Hager FZ51B Instrukcja

9 Grudnia 2024
Hager

Hager FZ45B Instrukcja

9 Grudnia 2024
Hager

Hager FZ44B Instrukcja

9 Grudnia 2024
Hager

Hager FZ737S Instrukcja

9 Grudnia 2024

Instrukcje przełącznik

Najnowsze instrukcje dla przełącznik

INOGENI

INOGENI CAM230 Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-5248P Instrukcja

14 Stycznia 2025
Luxul

Luxul AMS-2624P Instrukcja

14 Stycznia 2025
Luxul

Luxul XGS-1005 Instrukcja

14 Stycznia 2025
Luxul

Luxul AGS-1008M Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-1208P Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-7048P Instrukcja

14 Stycznia 2025
Luxul

Luxul AMS-2600 Instrukcja

14 Stycznia 2025