Instrukcja obsługi Hager EG 171


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Hager EG 171 (2 stron) w kategorii przełącznik. Ta instrukcja była pomocna dla 4 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
7
6
on
of f
5
4
3
2
1
ON
OFF
enter
reset
prog
aut o
manu
EG 171
Working principle :
The EG 171 is a time switch especially
designed to control any timed delayed
application (school bells, fans, etc...).
It is fully programmable with a maximum
of 20 program steps. Each program step
can be applied to one or several days,
maximising the use of each memory
location.
The front cover is sealable preventing
unauthorised access after completion of
programming.
Warning : at the beginning of use, please
reset the device in order to clear the
memory before programming.
This is achieved by using a pen to push
the reset button.
Presentation :
Display :
time
circuit status (ON or OFF)
day of the week
(1 = Monday, 2 = Tuesday ....)
Buttons :
Mode selector : to select one of the
following modes :
time setting
prog programming
auto running mode
manu manual override
1to “7: selection of the days
on/off: chooses whether the circuit
is on or off
+and -: changes settings
enter : to confirm
reset
Time and day setting :
1. Move mode selector to
2. Select with key “ ”1 to “ ”7 , the actual day
(1 = Monday, 2 = Tuesday.)
3. Input time with buttons “ ”+ and “ ”-.
Important :
The clock starts when exiting the time setting mode.
Programming :
1. Move mode selector to “ ”prog .
2. Input the impulse duration with keys “ ”+ and “ ”-
from 1 to 59 seconds (in 1 sec. increment),
then from 1 to 99 minutes (in 1 min. increment).
- seconds are shown as e.g. 10
- minutes are shown as e.g. 2
3. Select with keys 1” “ to 7 the day(s) assigned
to this program step. An arrow appears
above each day concerned.
4. Input switching time with buttons “ ”+ and “ ”-.
5. Enter this program step with button enter.
Program additional time settings by repeating
steps 3 to 5.
To modify the impulse duration while programming,
press on/off key.
To switch back to programmation, press on/off.
Important :
To activate the program, move mode selector to
auto.
Running Auto mode
This mode is the current displaying mode.
It does not allow any modification.
Move mode selector to “ ”auto .
Display of the time, the day and the state of the
channel.
To check your program :
1. Move mode selector to “ ”prog .
2. Press the enter key repeatedly to display
the different program steps (switching
time and days assigned).
To override the output :
Permanent override :
1. Move mode selector to “ ”manu .
2. Select the state of the output with key
on/off.
To switch back to automatic mode, move
mode selector to auto.
1 2 3 4 5 6 7
4
5
1
6 7 8 9
3
2
enter
reset
on
off
prog
auto
manu
OFF
1 2 3 4 5 6 7
enter
reset
on
off
prog
auto
manu
To modify or delete a program step :
1. Move mode selector to “ ”prog .
2. If necessary modify the impulse duration
and confirm with “ ”enter .
3. Press enter repeatedly and select the
program step to modify or to delete.
4. Modify :
- switching time with keys “ ”+ or “ ”-
- days assigned with keys “ ”1 to “ ”7
(an arrow flashes above all days assigned,
press once to add a day, press twice to
cancel).
- impulse duration by pressing key on/off
and then with “ ”+ and “ ”-
To delete a program step, press keys to “ ”1
“ ”7 in order to cancel all days assigned.
5. Confirm with the “ ”enter key.
1 impulse channel time
switch - weekly cycle
1 2 3 4 5 6 7
enter
reset
on
off
prog
auto
manu
ON
1 2 3 4 5 6 7
ON
enter
reset
on
off
prog
auto
manu
ON
1 2 3 4 5 6 7
enter
reset
on
off
prog
auto
manu
ON
User instruction GB
6E 6131.b
EG 171
3 4 5 621
L
N
Technical specifications :
Electrical characteristics :
- supply voltage : 230V +10/-15% 50Hz
- output : 1 changeover contact
µ 16A - 250V AC1.
µ 3A - 250V cos = 0.6
1000 W incandescent lighting
- power consumption : 1 VA
- protection degree : IP20
- insulation class : II
Functional characteristics :
- accuracy : ± 1sec. / day at 20 °C
- operating reserve : lithium battery,
total of three years.
Environment :
Operating temperature : -10 to +50 °C
Storage temperature : -10 to +50 °C
Connection tunnel terminals :
flexible : 0,5 to 2.5 mm2
rigid : 0,5 to 4 mm2
Dimensions : 3 modules (3x17,5mm)
Electrical connections :
1. Move mode selector to manu.
2. Select the state of the output with key
on/off.
3. Input with key + and - the override duration :
from 1 to 23 hours by steps of 1 hour,
then from 1 to 27 days by steps of 1 day.
4. Move mode selector to auto.
The state indication is flashing. This means a
timed override. Return to the initial program
after the duration.
To reset the time switch :
Press “ “reset to clear the program.
1. Move mode selector to manu.
2. Press key - + or until display -h.
3. Move mode selector to “ ”auto to switch
back to automatic mode.
Timed override :
To cancel the timed override :
1 2 3 4 5 6 7
enter
reset
on
off
prog
auto
manu
ON
1 2 3 4 5 6 7
enter
reset
on
off
prog
auto
manu
ON
A warranty period of 24 months is offered on hager products,
from date of manufacture, relating to any material of manu-
facturing defect. If any product is found to be defective it must
be returned via the installer and supplier (wholesaler). The
warranty is withdrawn if :
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary to
IEE wiring regulations and accepted practice within the industry
at the time of installation.
- the procedure for the return of goods has not been followed.
Explanation of defect must be included when returning
goods.
Warranty GB


Specyfikacje produktu

Marka: Hager
Kategoria: przełącznik
Model: EG 171

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager EG 171, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje przełącznik Hager

Hager

Hager ESC225 Instrukcja

1 Stycznia 2025
Hager

Hager SPB413 Instrukcja

30 Grudnia 2025
Hager

Hager LVSR3TP Instrukcja

9 Grudnia 2024
Hager

Hager EE110 Instrukcja

9 Grudnia 2024
Hager

Hager HIB416M Instrukcja

9 Grudnia 2024
Hager

Hager LVSG2CPX Instrukcja

9 Grudnia 2024
Hager

Hager FZ51B Instrukcja

9 Grudnia 2024
Hager

Hager FZ45B Instrukcja

9 Grudnia 2024
Hager

Hager FZ44B Instrukcja

9 Grudnia 2024
Hager

Hager FZ737S Instrukcja

9 Grudnia 2024

Instrukcje przełącznik

Najnowsze instrukcje dla przełącznik

INOGENI

INOGENI CAM230 Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-5248P Instrukcja

14 Stycznia 2025
Luxul

Luxul AMS-2624P Instrukcja

14 Stycznia 2025
Luxul

Luxul XGS-1005 Instrukcja

14 Stycznia 2025
Luxul

Luxul AGS-1008M Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-1208P Instrukcja

14 Stycznia 2025
Luxul

Luxul XMS-7048P Instrukcja

14 Stycznia 2025
Luxul

Luxul AMS-2600 Instrukcja

14 Stycznia 2025