ECCM32 Installation manual
(cod. 5679612 Rev.1)
Page 1 of 12
ECCM32
Energy calculator
for heat metering
INSTALLATION MANUAL
This manual is intended for qualified, previously trained
personnel: therefore, it does not provide basic information
concerning the general application context.
The “Advanced programming and user’s guide ECCM ” and the “
Service” configuration software can be downloaded from
“www.fantinicosmi.it” web site.
Warning! This unit contains “lithium-thionyl chloride”
batteries that may be potentially dangerous.
Read through the safety precautions for use in chapter 14.
1. Introduction
The ECCM32 unit is an electronic device used for heat sub metering
in heating and cooling systems as well as the volumes of cold and
hot sanitary water meters.
The calculator features separate sections able to simultaneously
record the following:
•
thermal energy in a heating and cooling circuit;
•
sanitary cold water volume;
•
sanitary hot water volume.
The unit has been designed to facilitate the installation and reduce
the time needed for the commissioning operations.
The ECCM32 unit is equipped with a wired “M-Bus” interface and a
wired “Local-bus” interface that allow the user to read, by means
of compatible equipment, the consumption from inside one’s own
apartment.
2. Package contents
• Calculator;
• Installation kit including:
one supporting bracket- two screws 3x6mm – one screw
2,9x9,5mm – one O-ring – two security seals;
• Installation manual.
3. General information
• Read through and strictly comply with the instructions and
specifications contained in this manual.
• The unit shall be installed, maintained and repaired by qualified
personnel, in accordance with the general prescriptions
concerning the electric equipment installation.
• This type of product is ruled by the EN1434 Standard (parts 1÷6)
and the 2004/22/CE Directive (Annex MI-004). Moreover, the
national standards concerning the calibration, verification and
validity, as applicable in the country where the equipment is
operated, shall be complied with.
• The certified manufacturing process guarantees the correct
operation of the unit and the conformity to the safety standards.
The warranty will be null and void if the seals inside the unit are
damaged or have been removed, or if any arbitrary modification
is made to the unit itself.
• The unit shall be cleaned, if necessary, by using only a cloth
moistened with water.
• The flow meter and the electronic unit shall have the same
impulse rate.
• The cables shall be kept at least 20 cm far from electromagnetic
interference sources (e.g. switches, regulators, circulation pumps,
etc.) and, also, at least 5 cm far from other electric cables.
4. Installation
4.1. Installing the calculator
The calculator is factory-set to the “delivery” mode, as
evidenced by the OFF writing on the display.
The keys shall be pressed only to proceed with “commissioning”
(refer to chapter 11) upon completion of the installation and
connection operations.
Open the calculator by acting on the two side hooks to remove the
upper assembly with the electronic section.
Carefully put the electronic section aside in the package.
Remove the fastening bracket from the bottom section and fix it to
the wall; then, fit the bottom onto the bracket and fix it by making
use of the “anti-removal” kit (i.e. screw and O-ring) supplied
together with the unit.
The special seals shall be put onto the calculator following the
installation and commissioning operations.
MID examination certifica
CH-MI004-13017
![](https://manualstech.ams3.cdn.digitaloceanspaces.com/html/nl/fantini-cosmi/eccm32/html/bg2.png)
ECCM32 Installation manual
(cod. 5679612 Rev.1)
Page 2 of 12
4.2. Installing the temperature sensors
Refer to the installation instructions and prescriptions relative to
the temperature sensors.
4.3. Installing the flow meter
Refer to the installation instructions and prescriptions relative to
the flow meters.
5. Connecting the external components
It is recommended that you should draw in advance a
wiring diagram with the various connections to be made
depending on the planned system application.
The electrical connections with the external devices (e.g.
temperature sensors, flow meters) and the communication
infrastructures (e.g. M- Bus and Local-bus) shall be made on the
terminal block fitted to the unit’s bottom section.
One dedicated through-hole shall be used for each cable (by acting
on the predrilled rubber block).
5.1. Description of the terminal block
The fourteen pole numbering complies to the EN1434-2 numeric
identification, as shown below:
EN1434
Numbering
Acronym Description of the connection
24
M-Bus
M-Bus communication line
25
M-Bus
M-Bus communication line
60
Loc B
Local bus communication line
61
Loc B
Local bus communication line
10
Vol1
Flow sensor C1 input
11
Gnd
Flow sensor C1 reference
50
n.c.
Not used
51
Vol3
Flow sensor C3 input
52
Gnd
Flow sensor C3/C4 reference
53
Vol4
Flow sensor C4 input
5
Tf1
Circuit 1 forward temperature sensor
6
Tf1
Circuit 1 forward temperature sensor
7
Tr1
Circuit 1 return temperature sensor
8
Tr1
Circuit 1 return temperature sensor
Tighten the terminals down and verify that the connections
are made firmly.
5.2. Connecting the temperature sensors
Use only compliant to the EN1434-2 Pt500 temperature sensors
Standard and certified by MID (2004/22/CE).
The “Service” menu (refer to paragraphs 10.2 and 10.3) allows
you to set, for each pair of sensors, the cable length depending
on the special system application:
• lenght 2,5÷3 m (standard, factory set)
• lenght 5÷6 m (type 1)
• lenght 10÷12 m (type 2)
It is mandatory that the cables of the two sensors of each
circuit (i.e. forward and return ) are of the same length.
5.3. Connecting flow meter C1
Use only flow meters equipped with class OA (reed output) and
class OC (open-collector) pulse outputs, with pulse rate “k”
(liters/pulse) compatible with the ones managed by the calculator.
Refer to chapter 6 and chapter 10 (paragraphs 10.2 and 10.3) for
more details.
When flow meters with class OC (open-collector) outputs
are used, the connection polarity shall be complied with.
Forward Return
Circuit 1
+
-
Circuit C1
Flow met
![](https://manualstech.ams3.cdn.digitaloceanspaces.com/html/nl/fantini-cosmi/eccm32/html/bg3.png)
ECCM32 Installation manual
(cod. 5679612 Rev.1)
Page 3 of 12
5.4. Connecting flow meters C3 and e C4
Pulse inputs to record the C3 and C4 are used sanitary hot and
cold water volumes. Refer to chapter 8 for more details
. Refer to
chapter 8 for more details.
Use only flow meters equipped with class OA (reed output) and
class OC (open-collector) pulse outputs, with pulse rate “k”
(liters/pulse) compatible with the ones managed by the calculator.
Refer to chapter 6 and chapter 10 (paragraphs 10.2 and 10.3) for
more details.
When flow meters with class OC (open-collector) outputs
are used, the connection polarity shall be complied with.
The connection example refers to the use of both pulse inputs. If
one or both inputs are not used, their respective terminals shall
be left open (not connected).
5.5. M-Bus network and Local-bus line connections
To connect the calculator communication interfaces, follow the
instructions below. The cable access to terminals 60 and 61 is
protected by a plastic membrane (to be removed) used to
prevent making wrong connections.
Warning! The M-Bus network operates at a rated voltage
of 48 V
DC
; therefore, any wrong connection of the M-Bus
network cables to other terminals of the calculator may cause
irreparable damage to the unit.
Polarity needs not be complied with for both
connections; however, it may be recommended that you
should keep the same polarity for the entire wiring, due to
system-related reasons.
Both the length and the section of the M-Bus network cables shall
be adequate to the communication speed. Except for special
applications, a of the type,telephone cable J-Y(ST) Y2x2x0.8
mm
2
, can be used for connecting with the M-Bus network.
The of the line shall be . maximum length Local-Bus 50 meters
Use ordinary duplex cables (2x0.6mm
2
) for the connection.
Warning! Only data consultation units (master units)
compliant to the safety requirements provided for by the
EN 13757-6 Standard shall be connected to the Local-Bus line.
6. Measurement representation format
The representation format, i.e. the decimal digits, for the energy
and power volume and flow rate measurements and the
measurements will be determined in accordance with pulse rate
“k” (liters/pulse) as set on the unit. The pulse rate will also
determine the maximum power that will turn out to be, in
conformity to paragraph 6.3.7 of the EN1434-2, as follows:
when k <100 the maximum power will be 33333 kW
when k ≥100 the maximum power will be 333333 kW
Important! After a volume input has acquired pulses, the
respective pulse rate “k” will no longer be able to be
changed. Therefore, the parameter shall be programmed prior to
applying the unit to the base and starting the unit.
Tables below show the representation formats for the “k” value
(litres/pulse) and for the units of measurement adopted for
energy and power and for volume and flow rate.
Pulse rate
“k”
Energy and power Energy and power
[MWh
] *
o [GJ] [kW] [kWh] o [MJ]
1
0.000
0.00
0.00
0
2.5
0.000
0.00
0.00
0
10
*
0.000
0.00
0.00
0
25
0.000
0.00
0.00
0
100
0.00
0.00
0.00
0
250
0.00
0.00
0.00
0
1000
0.00
0.00
0.00
0
2500
0.00
0.00
0.00
0
Pulse rate
“k”
Volume and flow rate Volume and flow rate
[m
3
]
*
[m
3
/h] [litro] [l/h]
1 0.000 0.000 0 0
2.5 0.000 0.000 0 0
10
*
0.000 0.000 0 0
25 0.000 0.000 0 0
100 0.00 0.000 0 0
250 0.00 0.000 0 0
1000 0.00 0.000 0 0
2500 0.00 0.000 0 0
(*) Factory setup values.
7. Communication interfaces
The calculator is equipped with two wired serial communication
interfaces: one M-Bus port and one “Local-Bus” port.
7.1. M-Bus interface
The wired M-Bus communication port features galvanic insulation
and makes it possible to remotely read the data by means of data
collection devices conforming to the communication standards as
per EN1434-3 and EN13757 (parts 2 and 3). The factory-set
communication speed (baud rate) is 2,400 baud; moreover, two
additional speeds can be selected (i.e. 300 and 9600 baud).
The communication with the unit can be established by means of
the primary address (which can be set through the “Service” menu)
or the secondary address (i.e. the unit’s serial number) available in
page 22 of the “consultation” menu.
7.2. Local-Bus interface
The “Local-Bus” communication port features an interface
conforming to the EN 13757-6 Standard as well as a proprietary
protocol. It allows the users to read, by means of a compatible
display (i.e. a chronothermostat or domotic system), the
consumption data (i.e. the current ones and the ones found in the
twelve monthly logs as well as logs ‘A’ and ‘B’). Contact the
technical support office for more details.
In accordance with the 2004/22/CE Directive, this data
collection method does not replace the consumption data
consultation/collection by means of the unit’s display or the M-
Bus data line.
+
-
-
+
Circuit C3 Circuit C4
Flow mete
Flow met
Local Bus
Specyfikacje produktu
Marka: | Fantini Cosmi |
Kategoria: | Sprzęt pomiarowy |
Model: | ECCM32 |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Fantini Cosmi ECCM32, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Sprzęt pomiarowy Fantini Cosmi
![Fantini Cosmi](/images/pdf_free.png)
8 Września 2024
![Fantini Cosmi](/images/pdf_free.png)
2 Września 2024
![Fantini Cosmi](/images/pdf_free.png)
26 Sierpnia 2024
![Fantini Cosmi](/images/pdf_free.png)
22 Sierpnia 2024
![Fantini Cosmi](/images/pdf_free.png)
22 Sierpnia 2024
Instrukcje Sprzęt pomiarowy
- Sprzęt pomiarowy PeakTech
- Sprzęt pomiarowy Beurer
- Sprzęt pomiarowy Joy-It
- Sprzęt pomiarowy Pioneer
- Sprzęt pomiarowy Voltcraft
- Sprzęt pomiarowy Milwaukee
- Sprzęt pomiarowy SilverCrest
- Sprzęt pomiarowy Technics
- Sprzęt pomiarowy Bosch
- Sprzęt pomiarowy Yato
- Sprzęt pomiarowy GW Instek
- Sprzęt pomiarowy Nedis
- Sprzęt pomiarowy Be Cool
- Sprzęt pomiarowy Rossmax
- Sprzęt pomiarowy Black & Decker
- Sprzęt pomiarowy Hazet
- Sprzęt pomiarowy DeWalt
- Sprzęt pomiarowy Einhell
- Sprzęt pomiarowy Homedics
- Sprzęt pomiarowy Eberle
- Sprzęt pomiarowy Silverline
- Sprzęt pomiarowy Honeywell
- Sprzęt pomiarowy Shimano
- Sprzęt pomiarowy Testo
- Sprzęt pomiarowy ORNO
- Sprzęt pomiarowy TFA
- Sprzęt pomiarowy Chauvin Arnoux
- Sprzęt pomiarowy Uni-T
- Sprzęt pomiarowy Flex
- Sprzęt pomiarowy LogiLink
- Sprzęt pomiarowy Grohe
- Sprzęt pomiarowy IFM
- Sprzęt pomiarowy Clean Air Optima
- Sprzęt pomiarowy Owon
- Sprzęt pomiarowy Eastron
- Sprzęt pomiarowy Digitus
- Sprzęt pomiarowy Vimar
- Sprzęt pomiarowy Dahua Technology
- Sprzęt pomiarowy Eurolite
- Sprzęt pomiarowy Techno Line
- Sprzęt pomiarowy TrueLife
- Sprzęt pomiarowy Sekonic
- Sprzęt pomiarowy Sonel
- Sprzęt pomiarowy BaseTech
- Sprzęt pomiarowy Perel
- Sprzęt pomiarowy Janitza
- Sprzęt pomiarowy Trotec
- Sprzęt pomiarowy Ansmann
- Sprzęt pomiarowy Velleman
- Sprzęt pomiarowy Meec Tools
- Sprzęt pomiarowy Danfoss
- Sprzęt pomiarowy Güde
- Sprzęt pomiarowy Victron Energy
- Sprzęt pomiarowy Pyle
- Sprzęt pomiarowy VDO
- Sprzęt pomiarowy Midland
- Sprzęt pomiarowy Werma
- Sprzęt pomiarowy Microlife
- Sprzęt pomiarowy Gossen Metrawatt
- Sprzęt pomiarowy Fluke
- Sprzęt pomiarowy Megger
- Sprzęt pomiarowy Greisinger
- Sprzęt pomiarowy Mitsubishi
- Sprzęt pomiarowy GoClever
- Sprzęt pomiarowy BENNING
- Sprzęt pomiarowy Camille Bauer
- Sprzęt pomiarowy Continental Edison
- Sprzęt pomiarowy DURO PRO
- Sprzęt pomiarowy Metrix
- Sprzęt pomiarowy Westfalia
- Sprzęt pomiarowy Oregon Scientific
- Sprzęt pomiarowy Milesight
- Sprzęt pomiarowy TDE Instruments
- Sprzęt pomiarowy Bresser
- Sprzęt pomiarowy Omnitronic
- Sprzęt pomiarowy Hama
- Sprzęt pomiarowy Eltako
- Sprzęt pomiarowy Maximum
- Sprzęt pomiarowy Goobay
- Sprzęt pomiarowy Reely
- Sprzęt pomiarowy Kemo
- Sprzęt pomiarowy Hager
- Sprzęt pomiarowy Extech
- Sprzęt pomiarowy Testboy
- Sprzęt pomiarowy Albrecht
- Sprzęt pomiarowy Stabila
- Sprzęt pomiarowy Kyoritsu
- Sprzęt pomiarowy Vemer
- Sprzęt pomiarowy Klein Tools
- Sprzęt pomiarowy ENTES
- Sprzęt pomiarowy Ridgid
- Sprzęt pomiarowy Lanaform
- Sprzęt pomiarowy Topcom
- Sprzęt pomiarowy Emko
- Sprzęt pomiarowy Powerfix
- Sprzęt pomiarowy Tempo
- Sprzęt pomiarowy Seaward
- Sprzęt pomiarowy Alecto
- Sprzęt pomiarowy Steinberg
- Sprzęt pomiarowy Carrier
- Sprzęt pomiarowy Eizo
- Sprzęt pomiarowy Monacor
- Sprzęt pomiarowy ADE
- Sprzęt pomiarowy Livington
- Sprzęt pomiarowy H-Tronic
- Sprzęt pomiarowy HT Instruments
- Sprzęt pomiarowy Elgato
- Sprzęt pomiarowy ProfiCare
- Sprzęt pomiarowy KS Tools
- Sprzęt pomiarowy Pico
- Sprzęt pomiarowy AkYtec
- Sprzęt pomiarowy Kern
- Sprzęt pomiarowy Adwa
- Sprzęt pomiarowy Laserliner
- Sprzęt pomiarowy Megasat
- Sprzęt pomiarowy Hikmicro
- Sprzęt pomiarowy Murideo
- Sprzęt pomiarowy ABB
- Sprzęt pomiarowy SRS
- Sprzęt pomiarowy Soler & Palau
- Sprzęt pomiarowy Fysic
- Sprzęt pomiarowy Amprobe
- Sprzęt pomiarowy Toolland
- Sprzęt pomiarowy VirtuFit
- Sprzęt pomiarowy Flir
- Sprzęt pomiarowy Soehnle
- Sprzęt pomiarowy Technoline
- Sprzęt pomiarowy LaCie
- Sprzęt pomiarowy Laica
- Sprzęt pomiarowy AS - Schwabe
- Sprzęt pomiarowy Festo
- Sprzęt pomiarowy IHealth
- Sprzęt pomiarowy Finder
- Sprzęt pomiarowy Wentronic
- Sprzęt pomiarowy Wago
- Sprzęt pomiarowy Comark
- Sprzęt pomiarowy REV
- Sprzęt pomiarowy Sauter
- Sprzęt pomiarowy Bruder Mannesmann
- Sprzęt pomiarowy CSL
- Sprzęt pomiarowy Multimetrix
- Sprzęt pomiarowy PCE
- Sprzęt pomiarowy Holzmann
- Sprzęt pomiarowy SIIG
- Sprzęt pomiarowy Enda
- Sprzęt pomiarowy Etymotic
- Sprzęt pomiarowy TFA Dostmann
- Sprzęt pomiarowy Testec
- Sprzęt pomiarowy YSI
- Sprzęt pomiarowy Kogan
- Sprzęt pomiarowy Kreg
- Sprzęt pomiarowy Pancontrol
- Sprzęt pomiarowy Peak
- Sprzęt pomiarowy X-Rite
- Sprzęt pomiarowy Ebro
- Sprzęt pomiarowy Tempest
- Sprzęt pomiarowy Arya
- Sprzęt pomiarowy RK Technology
- Sprzęt pomiarowy Tru Components
- Sprzęt pomiarowy Aktobis
- Sprzęt pomiarowy Trumeter
- Sprzęt pomiarowy Aeros
- Sprzęt pomiarowy Delta Ohm
- Sprzęt pomiarowy Aqua Master Tools
- Sprzęt pomiarowy Hanna
- Sprzęt pomiarowy Atmel
- Sprzęt pomiarowy Qualita
- Sprzęt pomiarowy MGL Avionics
- Sprzęt pomiarowy AREXX
- Sprzęt pomiarowy PCE Instruments
- Sprzęt pomiarowy UHoo
- Sprzęt pomiarowy CEM
- Sprzęt pomiarowy Hameg
- Sprzęt pomiarowy CESYS
- Sprzęt pomiarowy Angler
- Sprzęt pomiarowy Circutor
- Sprzęt pomiarowy Jonard Tools
- Sprzęt pomiarowy Aerospace Logic
- Sprzęt pomiarowy Zircon
- Sprzęt pomiarowy BJZ
- Sprzęt pomiarowy Johnson Level
- Sprzęt pomiarowy GMW
- Sprzęt pomiarowy SOEKS
- Sprzęt pomiarowy Rotronic
- Sprzęt pomiarowy Apollo Ultrasonic
- Sprzęt pomiarowy Softing
- Sprzęt pomiarowy Weltron
- Sprzęt pomiarowy Oscium
- Sprzęt pomiarowy Sanwa
- Sprzęt pomiarowy Condtrol
- Sprzęt pomiarowy J.P. Instruments
- Sprzęt pomiarowy MSW
- Sprzęt pomiarowy Qubino
- Sprzęt pomiarowy Lascar Electronics
- Sprzęt pomiarowy P3 International
- Sprzęt pomiarowy Beckmann & Egle
- Sprzęt pomiarowy Seek Thermal
- Sprzęt pomiarowy INFICON
- Sprzęt pomiarowy Motrona
- Sprzęt pomiarowy Blebox
- Sprzęt pomiarowy HOZO Design
- Sprzęt pomiarowy Corentium
- Sprzęt pomiarowy GQ
- Sprzęt pomiarowy Dostmann Electronic
- Sprzęt pomiarowy SecuTech
- Sprzęt pomiarowy NetPeppers
- Sprzęt pomiarowy SensoProtect
- Sprzęt pomiarowy Water-i.d.
- Sprzęt pomiarowy ZKETECH
- Sprzęt pomiarowy LabNation
- Sprzęt pomiarowy Electronics International
- Sprzęt pomiarowy Cliff
- Sprzęt pomiarowy ClimeMET
- Sprzęt pomiarowy Fixpoint
- Sprzęt pomiarowy Kübler
- Sprzęt pomiarowy MASIMO
- Sprzęt pomiarowy Noyafa
- Sprzęt pomiarowy Stamos
- Sprzęt pomiarowy Brookhuis
- Sprzęt pomiarowy Crowcon
- Sprzęt pomiarowy DriveTest
- Sprzęt pomiarowy PQ Plus
- Sprzęt pomiarowy Intact
- Sprzęt pomiarowy Aeroqual
- Sprzęt pomiarowy Helvi
Najnowsze instrukcje dla Sprzęt pomiarowy
![PCE Instruments](/images/pdf_free.png)
14 Stycznia 2025
![PCE Instruments](/images/pdf_free.png)
14 Stycznia 2025
![PCE Instruments](/images/pdf_free.png)
14 Stycznia 2025
![PCE Instruments](/images/pdf_free.png)
14 Stycznia 2025
![Klein Tools](/images/pdf_free.png)
14 Stycznia 2025
![Klein Tools](/images/pdf_free.png)
14 Stycznia 2025
![Ebro](/images/pdf_free.png)
13 Stycznia 2025
![Kern](/images/pdf_free.png)
10 Stycznia 2025
![PeakTech](/images/logos/peaktech.png)
10 Stycznia 2025
![PCE Instruments](/images/pdf_free.png)
10 Stycznia 2025