Instrukcja obsługi Eltako DSZ15D-3x80A

Eltako miary DSZ15D-3x80A

Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Eltako DSZ15D-3x80A (2 stron) w kategorii miary. Ta instrukcja była pomocna dla 3 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
Maximum current 3x80 A. Standby loss 0.5 watt per path only.
Modulair device for DIN-EN 60715 TH35 rail mounting in distribution
cabinets with IP51 protection class.
4 modules = 70mm wide and 58 mm deep.
Accuracy class B (1%). With S0 interface as standard.
It measures active energy by means of the current between input and output.
The internal power consumption of 0.5 watt active power per path is neither
metered nor indicated.
1, 2 or 3 phase conductors with max. currents up to 80 A can be connected.
The inrush current is 40mA.
The N terminal must always be connected.
The 7 segment LC display is also legible twice within a period of 2 weeks
without power supply.
Power consumption is shown by a bar flashing at a rate of 100 times per kWh.
Designed as standard for using as double-tariff meter: Switch over to a
second tariff by applying 230 V to terminals E1/E2.
On the right next to the display are the keys MODE and SELECT. Press them
to scroll through the menu. First the background lighting switches on. The
display then shows the total active energy per tariff, the active energy of the
resettable memory RS1 or RS2 as well as the instantaneous values of
consumption, voltage and current per phase.
Error message (false)
When the phase conductor is missing or the current direction is wrong 'false'
and the corresponding phase conductor are indicated on the display.
Three-phase energy meter DSZ15D-3x80A
with display and MID approval
Only skilled electricians may install this electrical equipment
otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -25°C up to +55°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
28 380 015 - 1
GB Menu guidance
Typical connection:
4-wire-connection 3x230/400V
S0 output
Technical data
Rated voltage, extended range 3x230/400 V, 50 Hz,
-20%/+15%
Reference current Iref (Limiting current Imax ) 3x0.5 - 10(80)A
Internal consumption active power 0.5 W per path
Display LC display 7 digits,
therefrom 1 or 2 digits after the decimal point
Accuracy class ±1% B
Inrush current according to accuracy class B 4OmA
Operating temperature -25/+55°C
Interface Pulse interface S0 according to DIN EN 62053-31,
potential free by opto-coupler,
max. 30 V DC/2O mA and min. 5 V DC,
impedance 100 ohms,
pulse length 30 ms, 1000 Imp./kWh
Terminal cover sealable Terminal cover claps
Protection degree lP50 for mounting in distribution cabines
with protection class IP51
Maximum conductor cross section1) L terminals 25mm2,
N terminals 16 mm
2,
S0 terminals and tariff terminals 6mm
2
Recommended torque2) L terminals 2,0 Nm (max. 2,5 Nm)
N terminals 1,5 Nm (max. 2,0Nm)
S0 terminals and tariff terminals 0,8Nm (max. 1,2Nm)
EC type examination certificate 0120 /SGS0204
The energy meter is used indoors.
Mechanical environmental conditions class M1
Electromagnetic environmental conditions class E2
1) The carrying capacity of cables and wires is defined in DIN VDE 0298-4.
2) The torques for screw terminals are mentioned in DIN EN 60999-1.
To avoid damages at the energy meter, the recommended torque values for each terminal
must not be exceeded!
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de
eltako.com
23/2020 Subject to change without notice.
Must be kept for later use!
We recommend the housing for operating instructions GBA12.


Specyfikacje produktu

Marka: Eltako
Kategoria: miary
Model: DSZ15D-3x80A

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Eltako DSZ15D-3x80A, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą