Pack Contents
• Zircon unvented water heater incorporating immersion heater(s) & thermal controls
• Factory tted temperature/pressure relief valve (set at 90°C / 1 Mpa (10bar))
• Cold water combination valve assembly
• Expansion vessel & mounting bracket
• Tundish
• 2 Port motorised valve (indirect models only)
• Compression nuts & olives
• Immersion heater spanner
• Installation & servicing instructions
• Guarantee card
IMPORTANT
Please read & understand all these instructions before commencing installation.
Please leave this manual with the customer for future reference.
Zircon Installation Manual
Unvented Direct & Indirect Water Heaters
Installation & Servicing Instructions
2
INTRODUCTION............................................................2
GENERAL REQUIREMENTS........................................3
INSTALLATION GENERAL............................................5
INSTALLATION DISCHARGE........................................7
INSTALLATION DIRECT...............................................11
INSTALLATION INDIRECT...........................................12
COMMISSIONING.......................................................14
MAINTENANCE...........................................................15
USER INSTRUCTIONS...............................................16
FAULT FINDING & SERVICING..................................17
SPARES.......................................................................18
HEAT LOSS.................................................................19
ENVIRONMENTAL INFORMATION.............................19
COMMISSIONING CHECK LIST.................................22
SERVICE RECORD.....................................................23
GUARANTEE...............................................................24
TECHNICAL SUPPORT...............................................24
CONTENTS
The cylinder is a purpose designed unvented water
heater. The unit has a stainless steel inner vessel,
which ensures an excellent standard of corrosion
resistance. The outer casing is a combination of
resilient thermoplastic mouldings and plastic coated
corrosion proofed steel sheet. All products are
insulated with CFC free polyurethane foam to give
good heat loss performance. (see Table 6, page 19)
The unit is supplied complete with all the necessary
safety and control devices needed to allow
connection to the cold water mains. All these
components are preset and not adjustable.
This appliance complies with the requirements of the
CE marking directive and is Kiwa approved to show
compliance with Building Regulations (Section G3).
The following instructions are offered as a guide
to installation which must be carried out by a
competent plumbing and electrical installer in
accordance with Building Regulation G3, The
Building Standards (Scotland) Regulations 1990, or
The Building Regulations (Northern Ireland).
NOTE: Prior to installation the unit should be stored
in an upright position in an area free from excessive
damp or humidity.
THE BENCHMARK SCHEME
Benchmark places responsibilities on both
manufacturers and installers. The purpose is to
ensure that customers are provided with the correct
equipment for their needs, that it is installed,
commissioned and serviced in accordance with the
manufacturer’s instructions by competent persons
and that it meets the requirements of the appropriate
Building Regulations. The Benchmark Checklist can
be used to demonstrate compliance with Building
Regulations and should be provided to the customer
for future reference.
Installers are required to carry out installation,
commissioning and servicing work in accordance
with the Benchmark Code of Practice which is
available from the Heating and Hotwater Industry
Council who manage and promote the Scheme. Visit
www.centralheating.co.uk for more information.
IMPORTANT NOTE TO USER: PLEASE REFER TO
THE USER INSTRUCTIONS SECTION ON PAGE 16
FOR IMPORTANT INFORMATION WITH RESPECT TO
THE BENCHMARK SCHEME
INTRODUCTION
3
IMPORTANT:
THIS APPLIANCE IS NOT INTENDED FOR THE
USE BY PERSONS (INCLUDING CHILDREN)
WITH REDUCED PHYSICAL, SENSORY
OR MENTAL CAPABILITIES, OR LACK OF
KNOWLEDGE AND EXPERIENCE, UNLESS
THEY HAVE BEEN GIVEN SUPERVISION OR
INSTRUCTION CONCERNING THE USE OF THE
APPLIANCE BY A PERSON RESPONSIBLE FOR
THEIR SAFETY.
CHILDREN MUST BE SUPERVISED TO ENSURE
THEY DO NOT PLAY WITH THE APPLIANCE.
SITING THE UNIT
The cylinder must be vertically oor mounted.
Although location is not critical, the following points
should be considered:
• The cylinder should be sited to ensure minimum
dead leg distances, particularly to the point of
most frequent use.
• Avoid siting where extreme cold temperatures
will be experienced. All exposed pipe work
should be insulated.
• The discharge pipework from the safety valves
must have minimum fall of 1:200 from the unit
and terminate in a safe and visible position.
• Access to associated controls and immersion
heaters must be available to provide for the
servicing and maintenance of the system.
Where these controls are installed against a wall a
minimum distance of 250mm must be left (see
Fig. 1).
• Ensure that the oor area for the cylinder is level
and capable of permanently supporting the
weight when full of water. (see Table 1)
WATER SUPPLY
Bear in mind that the mains water supply to the
property will be supplying both the hot and cold
water requirements simultaneously.
It is recommended that the maximum water
demand is assessed and the water supply
checked to ensure this demand can be
satisfactorily met.
Note: A high mains water pressure will not
always guarantee high ow rates.
Wherever possible the mains supply pipe should
be 22mm. We suggest the minimum supply
requirements should be 0.15MPa (1.5 bar) pressure
and 20 litres per minute owrate. However, at
these values outlet ow rates may be poor if
several outlets are used simultaneously. The higher
the available pressure and ow rate the better the
system performance.
The cylinder has an operating pressure of 0.35MPa
(3.5 bar) which is controlled by the cold water
combination valve assembly. The cold water
combination valve assembly can be connected to a
maximum mains pressure of 1.6MPa (16 bar).
OUTLET/TERMINAL FITTINGS (TAPS, ETC.)
The cylinder can be used with most types of terminal
ttings. It is advantageous in many mixer showers
to have balanced hot and cold water supplies. In
these instances a balanced pressure cold water
connection should be placed between the 2 pieces
of the cold water combination valve assembly (see
Fig. 2). Outlets situated higher than the cylinder will
give outlet pressures lower than that at the heater, a
10m height difference will result in a 0.1MPa (1 bar)
pressure reduction at the outlet. All ttings, pipework
and connections must have a rated pressure of at
least 0.6MPa (6 bar) at 80°C.
GENERAL REQUIREMENTS
Table 1: Unit weights
Fig. 1: Siting the Unit
WALL
Min 250mm Min 250mm
Type Model
Reference
Nominal
Capacity
(litres)
Weight of
unit full
(Kg)
Weight
of unit
(Kg)
Indirect 120zi 120 147 27
150zi 150 182 32
170zi 170 204 34
210zi 210 250 40
250zi 250 294 44
300zi 300 352 52
Direct 120zd 120 144 24
150zd 150 178 28
170zd 170 201 31
210zd 210 247 37
250zd 250 289 39
300zd 300 349 49
Specyfikacje produktu
Marka: | Elson |
Kategoria: | Bojler |
Model: | Zircon |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Elson Zircon, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje Bojler Elson
4 Września 2024
Instrukcje Bojler
- Bojler AEG
- Bojler Morco
- Bojler Bosch
- Bojler Siemens
- Bojler Remeha
- Bojler Truma
- Bojler Buderus
- Bojler Thermex
- Bojler Viessmann
- Bojler Vaillant
- Bojler Atag
- Bojler Inventum
- Bojler Junkers
- Bojler ACV
- Bojler De Dietrich
- Bojler Wijas
- Bojler Nefit
- Bojler A.O. Smith
- Bojler Agpo Ferroli
- Bojler Ariston
- Bojler Eldom
- Bojler Stiebel Eltron
- Bojler Elco
- Bojler Itho-Daalderop
- Bojler Saunier Duval
- Bojler TTulpe
- Bojler Atlantic
- Bojler Bulex
- Bojler AWB
- Bojler Quooker
- Bojler Daalderop
- Bojler Eccotemp
- Bojler Thermor
- Bojler LEMET
- Bojler Oertli
- Bojler Benekov
- Bojler Worcester-Bosch
- Bojler Lochinvar
- Bojler Eco Heating Systems
- Bojler MTS
- Bojler Strom
- Bojler Moa
- Bojler Schafer Heiztechnik
- Bojler Thermona
Najnowsze instrukcje dla Bojler
14 Października 2024
28 Września 2024
28 Września 2024
28 Września 2024
28 Września 2024
28 Września 2024
28 Września 2024
28 Września 2024
27 Września 2024
27 Września 2024