Instrukcja obsługi Elco R3500


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Elco R3500 (192 stron) w kategorii kocioł centralnego ogrzewania. Ta instrukcja była pomocna dla 17 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/192
R3400/R3500/R3600
Operation and Installation manual
for authorized technicians only
Betriebsanleitung
für die autorisierte Fachkraft
Bedienings- en Installatiehandleiding
alleen voor bevoegde vakmensen
Notice d’installation et d’emploi
réservée à l’usage des techniciens agréés
Istruzioni per l'uso
solo per il tecnico autorizzato
05/2014 420010582400
Operation and Installation manual
for authorized technicians only
R3400/R3500/R3600
05/2014 420010582400
Contents
2
Contents .................................................................. ...................................................... 2
Safety General regulation ............................................................................................ 3
Application ........................................................................................................ 3
Norms and regulations .............................. ...................................................... 3
Construction Layout of boiler ................................................................................................. 4
Operating principle ........................................................................................... 4
Technical data ......................................................................................................................... 5
Extent of delivery Standard boiler ............................................................................................... 15
Accessories .................................................................................................... 15
Installation Transport ........................................................................................................ 16
Removing the casing ...................................................................................... 18
Boiler installation ............................................................................................ 19
Connecting the boiler ..................................................................................... 20
Commissioning Water and hydraulic system ........................................................................... 22
Gas supply ..................................................................................................... 23
Condensate connection .................................................................................. 23
Flue and air intake connections ...................................................................... 23
Prepare boiler for first startup ......................................................................... 24
Combustion analysis ...................................................................................... 25
Air pressure switch ......................................................................................... 26
Check water flow ........................................................................................... 27
Check functionality of safety devices ............................................................. 28
Gas tightness check ....................................................................................... 28
Boiler shut down ............................................................................................. 28
Commissioning protocol ................................................................................. 29
Operating instructions Main menu (operating mode) ........................................................................ 30
Parameter menu(information/programming mode) ........................................ 30
Changing parameter values ........................................................................... 30
Maintenance Checklist ......................................................................................................... 31
Replacing the electrodes ................................................................................ 31
Cleaning the condensate receptacle .............................................................. 32
Cleaning and refilling the syphon ................................................................... 32
Water pressure and quality ............................................................................ 32
Water flow rate ............................................................................................... 32
Combustion analysis ...................................................................................... 32
Gas pressure .................................................................................................. 32
Gas tightness check ....................................................................................... 32
Safety devices ................................................................................................ 32
Maintenance protocol ..................................................................................... 33
Lockouts ....................................................................................................................... 34
Sensor values ....................................................................................................................... 36
Declaration of Conformity ....................................................................................................................... 37
Safety
General regulations
Application
Norms and regulations
3
General regulations
This documentation contains important
information, which is a base for safe
and reliable installation, commissioning
and operation of the R3400/R3500/
R3600 boiler. All activities described in
this document may only be excecuted
by authorized companies.
Changes to this document may be ef-
fected without prior notice. We accept
no obligation to adapt previously deliv-
ered products to incorporate such
changes.
Only original spare parts may be used
when replacing components on the
boiler, otherwise warranty will be void.
Application
The R3400/R3500/R3600 boiler may
be used for heating and hot water pro-
duction purposes only. The boiler
should be connected to closed systems
with a maximum temperature of 100ºC
(high limit temperature), maximum set-
point temperature is 90ºC.
Norms and regulations
When installing and operating the
R3400/R3500/R3600 boiler, all applica-
ble norms (european and local) should
be fulfilled:
Local building regulations for in-
stalling combustion air and flue gas
systems;
Regulation for connecting the boiler to
the electrical appliance;
Regulations for connecting the boiler
to the local gas network;
Norms and regulations according to
safety equipment for heating systems;
Any additional local laws/regulations
with regard to installing and operating
heating systems.
The R3400/R3500/R3600 boiler is CE
approved and applies to the follow-
ing European standards:
92 / 42 / EEC
Boiler efficiency directive
90 / 396 / EEC
Gas appliance directive
73 / 23 / EEC
Low voltage directive
89 / 336 / EEC
EMC directive
EN 656
Gas-fired central heating boilers –
Type B boilers of nominal heat input
exceeding 70 kW but not exceeding
300 kW
EN 15417
Gas-fired central heating boilers -
Specific requirements for condensing
boilers with a nominal heat input
greater than 70 kW but not exceeding
1000 kW
EN 13836
Gas fired central heating boilers -
Type B boilers of nominal heat input
exceeding 300 kW, but not exceeding
1000 kW
EN 15502-1
Gas-fired central heating boilers -
Part 1: General requirements and
tests
EN 55014-1
Electromagnetic compatibility - Re-
quirements for household appliances,
electric tools and similar apparatus -
Part 1: Emission
EN 55014-2
Electromagnetic compatibility - Re-
quirements for household appliances,
electric tools and similar apparatus -
Part 2: Immunity - Product family
standard
EN 61000-3-2
Electromagnetic compatibility (EMC) -
Part 3-2: Limits - Limits for harmonic
current emissions (equipment input
current 16 A per phase)
EN 61000-3-3
Electromagnetic compatibility (EMC) -
Part 3-3: Limitation of voltage chang-
es, voltage fluctuations and flicker in
public low-voltage supply
systems, for equipment with rated
current 16 A per phase and not sub-
ject to conditional connection
EN 60335-1
Household and similar electrical appli-
ances - Safety - Part 1: General re-
quirements
EN 50165
Household and similar electrical appli-
ances - Safety - Part 2-102: Particular
requirements for gas, oil and solid-
fuel burning appliances having electri-
cal connections
Additional national standards
Germany:
RAL - UZ 61 / DIN 4702-8
Switzerland:
SVGW
EKAS-Form. 1942: Flüssiggas-
Richtlinie Teil 2
Vorschriften der kantonalen Instanzen
(z.B. Feuerpoilizeivorschriften)
Netherlands:
(only applicable to
R3401-R3406 and R3600-R3605)
GASKEUR BASIS
GASKEUR SV
GASKEUR HR107
Belgium:
HR TOP
Construction
Layout of boiler
Operating principle
4
Layout of boiler
The R3400/R3500/R3600 boiler con-
sists of the following main components:
1 Return water connection
2 Flue gas connection
3 Water flow switch
4 Safety valve
5 Flow water connection
6 Filling/draining valve
7 Top plate
8 Plenum
9 Burner
10 1st Heat exchanger
11 Gas filter
12 2nd Heat exchanger
13 Gastrain
14 Frame
15 180° Bend
16 Compensator
17 Flue gas connection
18 Condensate receptacle
19 Flue gas receptacle
20 Combustion chamber
21 Entry electrical connections
22 Syphon
23 Main gas valve
24 Fan
25 Electrical box
26 Control panel
27 Casing
28 Air inlet damper
29 Butterfly valve
30 Main mixing channel
31 Pilot gas valve
32 Pilot mixing channel
33 Boiler pump
34 3rd Heat exchanger (only R3600)
A Air
B Gas
C Flue gasses
D Condensate
Operating principle
The R3400/R3500/R3600 is a fully
modulating boiler. The control unit of
the boiler adapts the modulation ratio
automatically to the heat demand re-
quested by the system. This is done by
controlling the speed of the fan. As a
result, the Whirlwind mixing system will
adapt the gas ratio to the chosen fan
speed, in order to maintain the best
possible combustion figures and there-
with the best efficiency. The flue gases
created by the combustion are trans-
ported downwards through
The KM628 control unit can control the
boiler operation based on:
fixed temperature (stand alone
operation);
weather compensated operation (with
optional controller);
with 0-10V external influence
(temperature or capacity) from a buil-
ding management system.
the boiler and leave at the back side
into the chimney connection.
The return water from the system en-
ters the boiler in the lower section,
where is the lowest flue gas tempera-
ture in the boiler. In this section con-
densation takes place. The water is
being transported upwards through the
boiler, in order to leave the boiler at the
top (burner) section. The cross flow
working principle (water up, flue gas
down) ensures the most efficient com-
bustion results.
34
Technical data
Technical data R3401 - R3405
5
R3401 R3402 R3403 R3404 R3405
Nominal heat output at 80-60ºC max/min kW 656/164 733/183 857/213 971/242 1084/270
Nominal heat output at 75-60ºC max/min kW 657/164 734/183 858/213 972/242 1085/270
Nominal heat output at 40/30ºC max/min kW 663/181 741/202 867/236 981/268 1095/298
Nominal heat input Hi max/min* kW 702/176 784/196 917/229 1038/260 1159/290
Efficiency at 80/60ºC % 93.5
Efficiency at 40/30ºC % 94.5
Annual efficiency (NNG 75/60ºC) % 100.0
Annual efficiency (NNG 40/30ºC) % -
Standstill losses (Twater = 70ºC) % 0.2
Max. condensate flow l/h -
Gas consumption H-gas max/min (10,9 kWh/m3) m3/h 64.5/16.2 71.9/18.0 84.1/21.0 95.2/23.8 106.3/26.6
Gas consumption L-gas max/min (8,34 kWh/m3) m3/h 84.3/21.1 94.0/23.5 109.9/27.4 124.4/31.2 139.0/34.8
Gas consumption LPG. max/min (12,8 kWh/kg) kg/h 54.9/13.8 61.2/15.3 71.6/17.9 81.1/20.3 90.5/22.6
Gas pressure H-gas mbar 20 35
Gas pressure L/LL-gas mbar 25 35
Gas pressure LPG mbar 30/50
Maximum gas pressure mbar 100
Flue gas temperature at 80/60ºC max/min ºC 165/70
Flue gas temperature at 40/30ºC max/min ºC 135/60
Flue gas quantity max/min* m3/h 1423/356 1580/395 1848/462 2091/523 2334/584
CO2 level main burner natural gas H/E/L/LL max/min % 10.0/9.3
CO2 level main burner liguid gas P max/min % 11.0/11.0
CO2 level pilot burner natural gas H/E/L/LL max/min % 10.0/10.2
CO2 level pilot burner liguid gas P max/min % 11.0/11.2
NOx level max/min mg/kWh 61.4/22.0
CO level max/min mg/kWh 9.8/3.3
Max. permissible flue resistance max/min Pa 150
Water volume l 50 53 70 75 80
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 28.5 31.6 37.0 41.8 46.8
Hydraulic resistance at nominal water flow kPa 46 53 36 43 50
Electrical connection V 400
Frequency Hz 50
Mains connection fuse A 16 20
IP class - IP20
Power consumption boiler (excl. pump) W 900 900 1270 1270 1270
Power consumption 3-step pump (optional) W
Weight (empty) kg 675 740 840 950 1070
Noise level at 1 meter distance dB(A) 64
Ionisation current minimum µA 6
PH value condensate - 3.2
CE certification code - CE-0063AR3514
Water connections - DN65 PN16 DN80 PN16
Gas connection - R 2” DN65 PN16
Flue gas connection mm 300 350 400
Air intake connection (for room sealed use) mm 250 300 355
Condensate connection mm 40
980 1010 1020 1450 1500
Technical data
Technical R3406 - R3410
6
R3406 R3407 R3408 R3409 R3410
Nominal heat output at 80-60ºC max/min kW 1196/298 1309/326 1496/373 1683/419 1870/466
Nominal heat output at 75-60ºC max/min kW 1197/298 1310/326 1498/373 1685/419 1872/466
Nominal heat output at 40/30ºC max/min kW 1209/329 1323/360 1512/412 1701/463 1890/515
Nominal heat input Hi max/min* kW 1279/320 1400/350 1600/400 1800/450 2000/500
Efficiency at 80/60ºC % 93.5
Efficiency at 40/30ºC % 94.5
Annual efficiency (NNG 75/60ºC) % 100.0
Annual efficiency (NNG 40/30ºC) % -
Standstill losses (Twater = 70ºC) % 0,2
Max. condensate flow l/h -
Gas consumption H-gas max/min (10,9 kWh/m3) m3/h 117.3/29.3 128.4/32.1 146.7/36.7 165.1/41.3 183.4/45.9
Gas consumption L-gas max/min (8,34 kWh/m3) m3/h 153.4/38.4 167.9/42.0 191.8/48.0 215.8/54.0 239.8/60.0
Gas consumption LPG. max/min (12,8 kWh/kg) kg/h 99.9/25.0 108.7/27.2 124.3/31.1 139.8/35.0 155.3/38.8
Gas pressure H-gas mbar 35 50
Gas pressure L/LL-gas mbar 35 50
Gas pressure LPG mbar 30/50 50
Maximum gas pressure mbar 100
Flue gas temperature at 80/60ºC max/min ºC 165/70
Flue gas temperature at 40/30ºC max/min ºC 135/60
Flue gas quantity max/min* m3/h 2578/645 2825/706 3227/807 3631/908 4035/1009
CO2 level main burner natural gas H/E/L/LL max/min % 10.0/9.3
CO2 level main burner liguid gas P max/min % 11.0/11.0
CO2 level pilot burner natural gas H/E/L/LL max/min % 10.0/10.2
CO2 level pilot burner liguid gas P max/min % 11.0/11.2
NOx level max/min mg/kWh 61.4/22.0
CO level max/min mg/kWh 9.8/3.3
Max. permissible flue resistance max/min Pa 150
Water volume l 85 97 109 116 123
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 51,6 56,1 64,1 72,1 80,1
Hydraulic resistance at nominal water flow kPa 58 91 60 130 165
Electrical connection V 400
Frequency Hz 50
Mains connection fuse A 20 C25
IP class - IP20
Power consumption boiler (excl. pump) W 1270 1910 2330 2520 2770
Power consumption 3-step pump (optional) W 1500 4000 7500
Weight (empty) kg 1200 1210 1525 1665 1745
Noise level at 1 meter distance dB(A) 64
Ionisation current minimum µA 6
PH value condensate - 3.2
CE certification code - CE-0063AR3514
Water connections - DN80 PN16 DN80 PN16
Gas connection - DN65 PN16
Flue gas connection mm 400 450 500
Air intake connection (for room sealed use) mm 355 -
Condensate connection mm 40
DN80 PN16
Technical data
Dimensions R3401 - R3406
7
Dimensions R3401 R3402 R3403 R3404 R3405 R3406
L mm 2265 2265 2653 2653 2658 2658
L1 mm 595 595 610 615 615 770
L2 mm 700 700 1166 1166 1166 1166
L3 mm 108 108 88 88 88 88
H mm 1355 1355 1355 1355 1355 1355
H1 mm 1125 1125 1570 1420 1155 1377
B mm 1330 1330 1130 1130 1330 1330
B1 mm 1160 1210 1003 1053 1203 1253
B2 mm 665 665 565 565 665 665
B3 mm 170 120 127 77 127 77
B4 mm 1146 1146 946 946 1146 1146
B5 mm 115 65 115 65 115 65
D mm 300 350 350 400 400 400
W DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" R 2" DN65 PN16 DN65 PN16
Technical data
Dimensions R3407 - R3410
8
R3407 - R3408
R3409 - R3410
Dimensions R3407 R3408 R3409 R3410
L mm 2755 3265 3265 3265
L2 mm 1120 1630 1630 1630
B mm 1530 1330 1530 1530
B2 mm 1407 1207 1357 1407
B3 mm 765 665 765 765
B4 mm 126.5 126.5 176.5 126.5
B5 mm 1406 1206 1406 1406
B6 1140 940 1140 1140
D mm 450 450 500 500
W1 DN DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
W2 DN DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16
Technical data
Technical data R3501 - R3505
9
R3501 R3502 R3503 R3504 R3505
Nominal heat output at 80-60ºC max/min kW 613/175 717/204 811/231 906/258 1000/285
Nominal heat output at 75-60ºC max/min kW 613/175 717/204 812/231 907/258 1001/285
Nominal heat output at 40/30ºC max/min kW 624/195 730/228 826/258 923/288 1018/319
Nominal heat input Hi max/min* kW 653/187 764/218 865/247 966/276 1066/305
Efficiency at 80/60ºC % 93.8
Efficiency at 40/30ºC % 95.5
Annual efficiency (NNG 75/60ºC) % 102.2
Annual efficiency (NNG 40/30ºC) % -
Standstill losses (Twater = 70ºC) % 0.3
Max. condensate flow l/h -
Gas consumption H-gas max/min (10,9 kWh/m3) m3/h 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gas consumption L-gas max/min (8,34 kWh/m3) m3/h 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gas consumption LPG. max/min (12,8 kWh/kg) kg/h 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gas pressure H-gas mbar 20
Gas pressure L/LL-gas mbar 25
Gas pressure LPG mbar 30/50
Maximum gas pressure mbar 100
Flue gas temperature at 80/60ºC max/min ºC 155/65
Flue gas temperature at 40/30ºC max/min ºC 120/55
Flue gas quantity max/min* m3/h 1287/368 1505/430 1703/487 1901/543 2099/600
CO2 level main burner natural gas H/E/L/LL max/min % 10.0/9.3
CO2 level main burner liguid gas P max/min % 11.0/11.0
CO2 level pilot burner natural gas H/E/L/LL max/min % 10.0/10.2
CO2 level pilot burner liguid gas P max/min % 11.0/11.2
NOx level max/min mg/kWh 11.5/19.5
CO level max/min mg/kWh 27.3/6.5
Max. permissible flue resistance max/min Pa 150
Water volume l 53 70 75 80 85
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 26,4 30,8 34,9 39,0 43,0
Hydraulic resistance at nominal water flow kPa 37 25 30 35 40
Electrical connection V 400
Frequency Hz 50
Mains connection fuse A 16 20
IP class - IP20
Power consumption boiler max/min (excl. pump) W 900 1270
Power consumption 3-step pump (optional) W
Power consumption speed controlled pump (optional) W 394 375 523 557 708
Weight (empty) kg 740 840 950 1070 1200
Noise level at 1 meter distance dB(A) 64
Ionisation current minimum µA 6
PH value condensate - 3.2
CE certification code - CE-0063AR3514
Water connections - DN65 PN16 DN80 PN16
Gas connection - R 2” DN65 PN16
Flue gas connection mm 300 350 400
Air intake connection (for room sealed use) mm 250 300 355
Condensate connection mm 40
960 1000 1020 1400 1500
Technical data
Dimensions R3501 - R3505
10
Dimensions R3501 R3502 R3503 R3504 R3505
L mm 2265 2653 2653 2658 2658
L1 mm 595 610 610 615 615
L2 mm 700 1166 1166 1166 1166
L3 mm 108 88 88 88 88
H mm 1355 1355 1355 1355 1355
H1 mm 1125 1400 1400 1155 1155
B mm 1330 1130 1130 1330 1330
B1 mm 1210 1003 1053 1203 1253
B2 mm 665 565 565 665 665
B3 mm 120 127 77 127 77
B4 mm 1146 946 946 1146 1146
B5 mm 65 115 65 115 65
D mm 300 350 350 400 400
W DN DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" DN65 PN16 DN65 PN16
Technical data
Technical data R3600 - R3605 Standard
11
R3600 R3601 R3602 R3603 R3604 R3605
Nominal heat output at 80-60ºC max/min kW 572/142 639/182 747/212 846/241 945/269 1043/297
Nominal heat output at 75-60ºC max/min kW 576/144 643/184 753/215 852/243 952/272 1050/300
Nominal heat output at 40/30ºC max/min kW 602/159 672/203 786/237 890/268 994/300 1097/331
Nominal heat input Hi max/min* kW 585/146 653/187 764/218 865/247 966/276 1066/305
Efficiency at 80/60ºC % 97.8
Efficiency at 40/30ºC % 102.9
Annual efficiency (NNG 75/60ºC) % 105,1
Annual efficiency (NNG 40/30ºC) % 109,8
Standstill losses (Twater = 70ºC) % 0,3
Max. condensate flow l/h -
Gas consumption H-gas max/min (10,9 kWh/m3) m3/h 53.7/13.4 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gas consumption L-gas max/min (8,34 kWh/m3) m3/h 70.3/17.6 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gas consumption LPG. max/min (12,8 kWh/kg) kg/h 45.7/11.4 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gas pressure H-gas mbar 20
Gas pressure L/LL-gas mbar 25
Gas pressure LPG mbar 30/50
Maximum gas pressure mbar 100
Flue gas temperature at 80/60ºC max/min ºC 85/65
Flue gas temperature at 40/30ºC max/min ºC 59/36
Flue gas quantity max/min* m3/h 969/242 1076/307 1258/359 1424/407 1590/454 1756/502
CO2 level main burner natural gas H/E/L/LL max/min % 10.0/9.3 10.0/9.3
CO2 level main burner liguid gas P max/min % 11.0/11.0 11.0/11.0
CO2 level pilot burner natural gas H/E/L/LL max/min % - 10.0/10.2
CO2 level pilot burner liguid gas P max/min % - 11.0/11.2
NOx level max/min mg/kWh 32.3/18.8 11.5/19.5
CO level max/min mg/kWh 8.2/10.9 27.3/6.5
Max. permissible flue resistance max/min Pa 100 150
Water volume l 69 73 97 104 110 117
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 24,7 27,6 32,2 36,5 40,8 45,0
Hydraulic resistance at nominal water flow kPa 48 56 38 45 53 60
Electrical connection V 400
Frequency Hz 50
Mains connection fuse A 10 16 20
IP class - IP20
Power consumption boiler (excl. pump) W 420 900 1270
Power consumption speed controlled pump (optional) W
Weight (empty) kg 810 890 1040 1150 1280 1410
Noise level at 1 meter distance dB(A) 64
Ionisation current minimum µA 6
PH value condensate - 3.2
CE certification code - CE-0063AR3514
Water connections - DN65 PN16 DN80 PN16
Gas connection - R 2” DN65 PN16
Flue gas connection mm 300 350 400
Air intake connection (for room sealed use) mm 250 300 355
Condensate connection mm 40
471 616 561 661 867 956
Power consumption 3-step pump (optional) W 940 980 1020 1400 1450 1500
Technical data
Dimensions R3600 - R3605 Standard
12
Dimensions R3601 R3602 R3603 R3604 R3605
L mm 2265 2653 2653 2658 2658
L1 mm 595 610 610 615 615
L2 mm 590 1166 1166 1166 1166
L3 mm 198 88 88 88 88
H mm 1405 1405 1405 1405 1405
H1 mm 1175 1450 1450 1205 1427
B mm 1330 1130 1130 1330 1330
B1 mm 1210 1003 1053 1203 1253
B2 mm 665 565 565 665 665
B3 mm 120 127 77 127 77
B4 mm 1146 946 946 1146 1146
B5 mm 65 115 65 115 65
D mm 300 350 350 400 400
W1 DN DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" DN65 PN16 DN65 PN16
R3600
1958
595
700
108
1355
970
1230
1110
615
120
1046
100
300
DN65 PN16
R 2"
D1 mm 250 250 300 300 355 355
W2 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
Technical data
Technical data R3600 - R3605 Split system
13
R3600 R3601 R3602 R3603 R3604 R3605
Nominal heat output at 80-60ºC max/min kW 572/142 639/182 747/212 846/241 945/269 1043/297
Nominal heat output at 75-60ºC max/min kW 576/144 643/184 753/215 852/243 952/272 1050/300
Nominal heat output at 40/30ºC max/min kW 602/159 672/203 786/237 890/268 994/300 1097/331
Nominal heat input Hi max/min* kW 585/146 653/187 764/218 865/247 966/276 1066/305
Efficiency at 80/60ºC % 97.8
Efficiency at 40/30ºC % 102.9
Annual efficiency (NNG 75/60ºC) % 105,1
Annual efficiency (NNG 40/30ºC) % 109,8
Standstill losses (Twater = 70ºC) % 0,3
Max. condensate flow l/h -
Gas consumption H-gas max/min (10,9 kWh/m3) m3/h 53.7/13.4 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gas consumption L-gas max/min (8,34 kWh/m3) m3/h 70.3/17.6 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gas consumption LPG. max/min (12,8 kWh/kg) kg/h 45.7/11.4 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gas pressure H-gas mbar 20
Gas pressure L/LL-gas mbar 25
Gas pressure LPG mbar 30/50
Maximum gas pressure mbar 100
Flue gas temperature at 80/60ºC max/min ºC 85/65
Flue gas temperature at 40/30ºC max/min ºC 59/36
Flue gas quantity max/min* m3/h 969/242 1076/307 1258/359 1424/407 1590/454 1756/502
CO2 level main burner natural gas H/E/L/LL max/min % 10.0/9.3 10.0/9.3
CO2 level main burner liguid gas P max/min % 11.0/11.0 11.0/11.0
CO2 level pilot burner natural gas H/E/L/LL max/min % - 10.0/10.2
CO2 level pilot burner liguid gas P max/min % - 11.0/11.2
NOx level max/min mg/kWh 32.3/18.8 11.5/19.5
CO level max/min mg/kWh 8.2/10.9 27.3/6.5
Max. permissible flue resistance max/min Pa 100 150
Water volume l 73 73 97 104 110 117
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 24,7 27,6 32,2 36,5 40,8 45,0
Hydraulic resistance at nominal water flow kPa 48 56 38 45 53 60
Electrical connection V 400
Frequency Hz 50
Mains connection fuse A 10 16 20
IP class - IP20
Power consumption boiler (excl. pump) W 730 900 1270
Weight (empty) kg 810 890 1040 1150 1280 1410
Noise level at 1 meter distance dB(A) 64
Ionisation current minimum µA 6
PH value condensate - 3.2
CE certification code - CE-0063AR3514
Water connections - DN65 PN16 DN80 PN16
Gas connection - R 2” DN65 PN16
Flue gas connection mm 300 350 400
Air intake connection (for room sealed use) mm 250 300 355
Condensate connection mm 40
Technical data
Dimensions R3600 - R3605 Split system
14
Dimensions R3600 R3601 R3602 R3603 R3604 R3605
L mm 1958 2070 2443 2443 2443 2443
L2 mm 700 590 1166 1166 1166 1166
L3 mm 108 198 88 88 88 88
H mm 1355 1405 1405 1405 1405 1405
B mm 1230 1330 1130 1130 1330 1330
B1 mm 1110 1210 1003 1053 1203 1253
B2 mm 615 665 565 565 665 665
B3 mm 120 120 127 77 127 77
B4 mm 1046 1146 946 946 1146 1146
B5 mm 100 65 115 65 115 65
D mm 300 300 350 350 400 400
D1 mm 250 250 300 300 355 355
W1 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
W2 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
W3 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" R 2" DN65 PN16 DN65 PN16
Extent of delivery
Standard boiler
Accessories
15
Standard boiler
A boiler delivery package contains the
following components:
Accessories
On request it is possible to get various
options and/or accessories. Ask your
supplier for the possibilities.
Component Pcs. Package
R3400/R3500/R3600 Boiler fully assembled and tested 1 Mounted on wooden blocks with wooden border,
sealed in PE foil
Adjustable feet 4 Cardboard box on top of boiler
(on R3407-R3410 already fitted to boiler)
Syphon for condensate connection 1 Cardboard box on top of heatexchanger
(under casing)
Operation and Installation manual 1 Map attached to back panel of the boiler
Wiring diagram 1 Map attached to back panel of the boiler
16
Installation
Transport
Boiler transport
The R3400/R3500/R3600 boiler will be
supplied as a complete unit being fully
assembled and pre-tested. The boiler
can be transported with a pallet truck
(at least 1m wide), picking the boiler up
from the side.
Whenever necessary, the boiler can be
dismantled into smaller parts for easier
transport inside the building. The table
below shows the main dismantled parts
with their weight and dimensions.
When the R3400/R3500/R3600 boiler
has to be transported with a crane, it is
necessary to remove the casing before
connecting the boiler to the crane. Al-
ways connect the crane to the frame of
the boiler by using straps.
1
3
2
Component R3401
R3600
R3402
R3501
R3601
R3403
R3502
R3602
R3404
R3503
R3603
R3405
R3504
R3604
R3406
R3505
R3605
Burner m [kg]
L [mm]
W [mm]
H [mm]
135
1010
1150
420
135
1010
1150
420
140
1010
1310
500
210
1420
1010
500
215
1420
1110
500
220
1420
1210
500
225
1420
1310
500
1st Heat exchanger m [kg]
L [mm]
W [mm]
H [mm]
120
1010
1150
160
120
1030
1150
150
135
1010
1310
160
180
1420
1010
160
185
1420
1110
160
190
1420
1210
160
195
1420
1310
160
2nd Heat exchanger
m [kg]
L [mm]
W [mm]
H [mm]
135
1010
1150
160
135
1030
1050
150
150
1010
1310
160
200
1420
1010
160
200
1420
1110
160
210
1420
1210
160
210
1420
1310
160
Frame
H for R3600 in ( )
m [kg]
L [mm]
W [mm]
H [mm]
50
1325
1165
460
50
1325
1165
360
60
1630
1266
500 (370)
70
2004
1066
500 (370)
70
2004
1066
500 (370)
70
2004
1266
500 (370)
70
2004
1266
500 (370)
Condensate receptacle m [kg]
L [mm]
W [mm]
H [mm]
< 25
1320
990
400
< 25
1320
990
275
< 25
1450
1070
400
< 35
1950
770
400
< 35
1950
870
400
< 35
1950
970
400
< 35
1950
1070
400
3rd Heat exchanger
(only R3600 series)
m [kg]
L [mm]
W [mm]
H [mm]
-
-
-
-
135
1030
1050
150
150
1010
1310
160
200
1420
1010
160
200
1420
1110
160
210
1420
1210
160
210
1420
1310
160
1 Hoisting belt (4x)
2 Wooden retaining beam (2x)
3 Hoisting belt position (4x)
Installation
Transport
17
Component R3407 R3408 R3409 R3410
Burner m [kg]
L [mm]
B [mm]
H [mm]
230
1510
1400
600
385
2050
1250
600
390
2050
1350
620
395
2050
1450
620
1st Heat exchanger m [kg]
L [mm]
B [mm]
H [mm]
200
1510
1425
150
325
2050
1250
150
330
2050
1350
150
335
2050
1450
150
2nd Heat exchanger
m [kg]
L [mm]
B [mm]
H [mm]
220
1510
1425
150
365
2050
1250
150
370
2050
1350
150
375
2050
1450
150
Frame
m [kg]
L [mm]
B [mm]
H [mm]
80
2010
1466
510
120
2525
1266
515
120
2525
1466
515
120
2525
1466
515
Condensate m [kg]
L [mm]
B [mm]
H [mm]
< 40
2075
1175
350
< 55
2600
975
350
< 55
2600
1075
350
< 55
2600
1175
350
Installation
Removing the casing
18
Boiler transport
Remove the casing before transporting
the boiler, in order to avoid damage to
the casing parts during transportation.
Removing the casing is done as fol-
lows:
1.
3.
5. 4. 2.
5.
4.
Installation
Boiler installation
Boiler installation
The boiler should be positioned in a
frost-proof boiler room. If the boiler
room is on the roof, the boiler itself may
never be the highest point of the instal-
lation.
When positioning the boiler, please
note the recommended minimum clea-
rance in the picture. When the boiler is
positioned with less free space, mainte-
nance activities will be more difficult.
Once the boiler is in the correct posi-
tion, the wooden blocks (1) should be
removed and the adjustable feet (2)
(with vibration absorption dampers)
should be adjusted to the right height.
Water and gas connections should be
done after mounting the feet, as they
effect the exact height of all connecti-
ons.
19
800
1000
The R3407- R3410 are not supplied on
wooden blocks, but on wheels. After
positioning the boiler, the adjustable
feet have to be set to the correct height.
The wheels have to be removed. The
connections to the boiler have to be
made after the feet have been ad-
justed, as the adjustment will effect the
exact height of all connections.
Installation
Connecting the boiler
20
Connecting the boiler
This chapter will explain how to make
all connections to the boiler with regard
to:
Hydraulic connections (1, 3)
Condensate drain connection (7)
Gas connection (6)
Flue gas connection (5)
Air intake connection (only when
using roomsealed, order seperately)
(2)
Electrical connection (4)
The boiler should always be connected
in such a way, that the system applies
to all relevant standards and regulati-
ons (European, national and local). It’s
the responsibility of the installer to en-
sure that all standards and regulations
are respected.
Hydraulic connections
The boiler should always be connected
in such a way, that water flow through
the boiler can be ensured at all times.
Connect the flow (3) and return (1) con-
nection of the system tension free to
the boiler connections. If the boiler is
used in a system with two return cir-
cuits (only R3600 series), the common
return becomes the low temperature
return, the 2nd return connection is the
high temperature return (remove cap/
flange before connecting).
Condensate connection (7)
After filling with water, the syphon
(included in delivery) should be in-
stalled to the connection at the bottom
of the condensate receptacle. The con-
nection to the draining system should
always be done with an open connec-
tion, in order to avoid a flooding of the
boiler in case of a blocked drain.
4 5 6
7
1 2 3
Installation
Connecting the boiler
21
Gas connection (6)
The gas connection must be made by
an authorized installer in accordance
with the applicable national and local
standards and regulations.
Connect the gas line from the system
tension free to the gas connection (6) of
the boiler. A gas cock should be
mounted directly behind the boiler.
A gas filter can be mounted directly on
the gas connection of the boiler.
Flue gas connection (5)
Regulations for the construction of flue
gas systems are very different for each
country. It should be ensured that all
national regulations with regard to flue
gas systems are respected.
Connect the flue gas system to the flue
gas connection (5) of the boiler, use
fluegas systems with seamless connec-
tions only. It’s not necessary to make a
separate condensate drain for the flue
gas system, as the condensate will be
drained via the syphon of the boiler.
Please note the following issues:
It’s recommended to use stainless
steel systems
The diameter of the flue gas system
must be chosen by calculation ac-
cording to the national regulations
Construct the flue gas system as
short as possible (for maximum
length see planner documentation)
Construct horizonal ways with a mini-
mum angle of 3º
Air intake connection (3)
When using the boiler roomsealed. The
air intake can be connected if the boiler
was ordered as roomsealed. The dia-
meter should be calculated according
to the national regulations, together
with the flue gas system. The total re-
sistance of both systems should never
overcome the maximum permissible
resistance of the fan inside the boiler
(see also chapter: Technical data).
.
Electrical connection (4)
The electrical connection must be ma-
de by an authorized installer in
accordance with the applicable national
and local standards and regulations.
For the power supply it’s necessary to
use a mains isolator switch with a con-
tact opening of at least 3 mm
within the boiler room. This switch can
be used to switch off the power supply
for maintenance purposes.
Cables can be inserted through the
cable trays and glands at the back of
the electrical panel at the front of the
boiler.
Connect all wires to the terminals ac-
cording to the wiring diagram of the
boiler (enclosed in map attached to
back panel of the boiler).
4
4
6
2
5
Commissioning
Water and hydraulic system
Water quality
The system should be filled with water
with a PH value between 8,0 and 9,5.
The chloride value of the water should
not exceed 50 mg/l. Entry of oxygene
by diffusion should be prevented at all
times. Damage to the heat exchanger
because of oxygene diffusion will not
be taken under warranty.
Boiler output
[kW]
Max. sum of alkaline earths
[mol/m3]
Max. total hardness
[dºH]
600 - 2000 1.5 8.4
Minimum operating
pressure
[bar]
Flow tem-
perature
[ºC]
> 1.5 90
> 1.0 80
Water pressure
Open the valves to the system. Check
the water pressure in the system. If the
water pressure is too low (see table
below), increase the pressure up to at
least the minimum required water
pressure in the table.
Filling can be done via the fill and drain
valve (2) on the return connection (1) of
the boiler.
Hydraulic system
Check if the boiler is hydraulically con-
nected to the system in such way, that
water flow can be secured at all times
during burner operation. The water flow
is supervised by the water flow switch
in the boiler and a lack of flow will lead
to a direct burner stop and lockout of
the boiler.
Commissioning of the boiler should be
carried out by authorized personnel
only. Failure to respect this condition
makes the guarantee void. A protocol
of the commissioning should be filled
out (see end of this chapter for example
of commissioning protocol).
This chapter explains the commissio-
ning of the boiler with the standard boi-
ler controller. When an additional sys-
tem controller is installed, please refer
to its manual for commissioning the
controller.
In installations with higher water volu-
mes, it’s necessary to respect the maxi-
mum filling and additional volumes with
corresponding hardness values as sta-
ted in the german VDI2035 standard. In
the table you can find the nominal va-
lues for filling and additional water for
the R3400/R3500/R3600 according to
the the VDI2035.
The table at the left gives an indication
of the relation between the water quali-
ty and the maximum water filling volu-
me during the lifetime of the boiler.
Consult the original text of the VDI2035
for more detailed information.
Concentrate
Ca(HCO3)2
Capacity of installation Q (kW)
600 800 1000 1200 1400 1600 1800
mol/
m3
dºH Maximum water (re)fill volume Vmax [m3]
0.5 2.8 - - - 75.1 87.6 100.2 122.7
1.0 5.6 - - - 37.6 43.8 50.1 56.3
1.5 8.4 12.0
16.7 20.9 25.0 29.2 33.4 37.6
2.0 11.2 9.4
12.5 15.7 18.8 21.9 25.0 28.2
2.5 14.0 7.5
10.0 12.5 15.0 17.5 20.0 22.5
3.0 16.
8
6.3 8.3 10.4 12.5 14.6 16.7 18.8
2000
125.2
62.6
41.7
31.3
25.0
20.9
22
1
2
Commissioning
Gas supply
Condensate connection
Flue and air intake connections
23
Gas supply
Check the gas supply connection to the
boiler for tightness. If any leakage is
found, reseal the leakage before star-
ting the boiler!
Remove any air between the gas valve
and the gas line. This can be done at
the test point (1) at the gas pressure
switch. Don’t forget to close the test
point afterwards!
Check the gas type and values with the
local gas company, in order to know for
which gas type the boiler should be
commissioned.
Condensate connection
Remove the syphon (2) from the con-
densate connection. Fill it with water
and place it back in the original posi-
tion. Make sure the syphon is filled
before starting the boiler, in
order to prevent flue gases dischar-
ging through the condensate connec-
tion!
Flue and air intake connections
Check whether the flue and air intake
systems are made according to the
national and local regulations. Installati-
ons which don’t comply with the regula-
tions, are not allowed to be commissio-
ned.
Make sure that all connections are free.
The size of flue gas and air intake con-
nections may not be reduced.
2
1
Commissioning
Prepare boiler for first startup
24
Prepare boiler for first startup
Open gas connection;
Switch on mains isolator switch for
power supply to the boiler;
Switch on boiler with on/off switch (1)
Make sure the boiler remains in
standby operation K (2)
use rotational switch (3);
Check the pump operation: make
sure that the direction of the rotation
is correct;
Remove any air from the pump by
removing the end cap of the pump
motor housing.
It’s recommended to keep the boiler at
50% load for a while after the first
startup, as this is the easiest base for
starting the combustion analysis. This
can be assured as follows:
Open the lid of the boiler controller;
Use rotational switch (3) for going to
parameter P9
in the menu;
Change P9 (5) into 50% (push
programming button (4), change
value with rotational switch (3), push
programming button (4) to confirm);
Close the lid of the boiler controller.
2
3
3
4
5
1
Commissioning
Combustion analysis
25
Combustion check at full load
Start the boiler at service mode for full
load operation (W2). When you have
reduced P9 to 50% (see previous
chapter), the boiler will operate at 50%
load. Allow the boiler to stabilise the
combustion for 3 minutes. Then
increase P9 step by step up to 100%.
Check the gas pressure on the inlet of
the gas valve while increasing the
boiler load: the gas pressure should
never go below the minumum required
value see technical data. Set the
minimum gas pressure switch (1) at
50% of the required gas pressure.
First check the combustion values of
the pilot burner using the measuring
tube on the back of the boiler (3). If
required the values can be corrected
with the adjustment screw on the pilot
gas valve (2).
Then check the combustion values of
the main burner using a measuring
point in the flue (4). If required the va-
lues can be corrected with the adjust-
ment screw (V) on the main gas valve
(5).
Combustion check at minimum load
Switch the boiler to service mode for
minimum load operation (W1). Check
the combustion settings the same way
as described for full load. The
combustion settings for the pilot burner
can be adjusted using the adjustment
screw on the pilot gas valve (6). The
combustion settings for the main burner
can be adjusted using the adjustment
screw (N) on the main gas valve (7).
Combustion check at 50% load
An additional reference check of com-
bustion values at 50% load is recom-
mended in order to check if the gas
valve is set in such way, that the modu-
lating behaviour is normal. The CO2
value should be in between the settings
of full load and minumum load. CO
value should be equal to full load and
minimum load values.
Make sure parameter P9 is set back to
100 and switch the boiler to automatic
operation (F) after the combustion test
is finished.
1
Combustion settings
for natural gas G20 / G25
All boilers
CO2, max % 10.0 ± 0.2
COmax ppm < 1000
Pilot burner
CO2, min % 10.2 ± 0.2
COmin ppm < 1000
Combustion settings
for LPG G31
All boilers
CO2, max % 11.0 ± 0.2
COmax ppm < 1000
CO2, min % 11.2 ± 0.2
COmin ppm < 1000
Pilot burner
Parameter change required
P19 : 100% 86%
Combustion settings
for natural gas G20 / G25
All boilers
CO2, max % 10.0 ± 0.2
COmax ppm < 30
Main burner
CO2, min % 9.3 ± 0.2
COmin ppm < 30
Combustion settings
for LPG G31
All boilers
CO2, max % 11.0 ± 0.2
COmax ppm < 30
CO2, min % 11.0 ± 0.2
COmin ppm < 30
Main burner
Parameter change required
P19 : 100% 86%
2
6
5 7
4
3
Commissioning
Air pressure switch
26
Adjustment Air pressure switch
Connect a pressure gauge to the indi-
cated measuring points on the switch
(1). Start the boiler at service mode for
minimum load operation (W1). Measure
the pressure differential across the
switch, this should be 0.8 mbar. Turn
the dial on the switch (2) counter-
clockwise until the end. Reduce the
setting on parameter P17 step by step
until the pressure differential is 0.4
mbar. Slowly turn the dial on the switch
clockwise until the boiler goes to lock-
out. Set P17 back to its original setting!!
Reset the lockout. Restart the boiler
and check if the switch contact closes
at 0.4 mbar (indicator at DW in display
of the boiler controller (3). If required,
repeat the above procedure.
1
2
3
Commissioning
Check water flow
27
qactual = (Tnominal / Tmeasured) * qnominal [m3/h]
qactual = (pmeasured / pnominal) * qnominal [m3/h]
Check water flow
The water flow through the boiler can
be checked with two different methods
shown below.
T measurement
Check the temperature difference over
the boiler (T flow-return) when the
boiler is running on 100% load. The
nominal T is 20K and must be at least
between 15K and 25K for secure boiler
operation. An indication of the actual
flow rate can be found with the follo-
wing calculation (see table below for
nominal data):
p measurement
Check the pressure difference over the
boiler (p flow-return) when the boiler
pump is running (burner on is not requi-
red). The nominal p for each boiler
type can be found in the table below,
actual p must be within:
0.35*pnom P 1.75*pnom . An indi-
cation of the actual flow rate can be
found with the following calculation (see
table below for nominal data):
Flow rate R3406 - R3410 at T 20K
R3406 R3407 R3408 R3409 R3410
Nominal flow [m3/h] 51,6 56,1 64,1 72,1 80,1
p at nom. flow [kPa]
58 91 60 130 165
Flow rate R3501 - R3505 at T 20K
R3501 R3502 R3503 R3504 R3505
Nominal flow [m3/h] 26,4 30,8 34,9 39,0 43,0
p at nom. flow [kPa]
37 25 30 35 40
Flow rate R3600 - R3605 at T 20K
R3600 R3601 R3602 R3603 R3604
Nominal flow [m3/h] 24,7 27,6 32,2 36,5 40,8
p at nom. flow [kPa]
48 56 38 45 53
R3605
45,0
60
Flow rate R3401 - R3405 at T 20K
R3401 R3402 R3403 R3404 R3405
Nominal flow [m3/h] 28.5 31.6 37.0 41.8 46.8
p at nom. flow [kPa]
46 53 36 43 50
Commissioning
Check functionality of safety devices
Gas tightness check
Boiler shut down
28
Water flow temperature sensor (1)
Disconnect the plug from the sensor
while the boiler is switched on. This
should result in a lockout no. 12.
The lockout should disappear as soon
as the plug is placed back in position,
the boiler will restart.
Water flow switch (2)
Close (slowly!) the valve in the flow
connection to the system while the boi-
ler is running on minimum load.
When the valve is almost closed and
the water flow is insufficient, the water
flow switch will switch off and the
boiler will go in lockout 40. Open the
valve. A manual reset is necessary.
Minimum gas pressure switch (4)
Close the gas cock when the boiler is in
standby position (K). Open the test
point on the gas valve (3) while meas-
uring the gas pressure on the test point
of the gas pressure switch (5).
The boiler will go in lockout no. 2 when
the switch off setting is achieved. Close
both test points and open the gas cock.
Check functionality of safety devices
All safety devices have to be checked
on good functioning. Safety devices on
a standard boiler are a water flow tem-
perature sensor, water flow switch,
minimum gas pressure switch and ioni-
sation electrode. These devices can be
checked as described below.
Ionisation electrode (6)
Remove electrical connection from the
ionisation electrode while the boiler is
running, the boiler will go in lockout
no.5. The boiler will try to restart. With
the electrical connection removed, the
restart will result in lockout no. 4. When
the connection is already mounted, the
restart will be successful.
Measuring the ionisation current can
be done by mounting a multi-meter (set
to µA) in between the ionisation elec-
trode and its electrical connection. The
ionisation current should always be
above 1.2 µA, in normal conditions it
will be 6 µA and above.
Gas tightness check
Check the gas tightness of all sealed
connections with an approved soap or
electronic gas analyzer, for example:
Test points
Bolt connections
Gaskets of mixing system, etc.
Boiler shut down
When the boiler will not be used for
longer periods, shut down the boiler by
following procedure:
Switch the boiler in standby operation
(K)
Switch off the boiler with the on/off
switch (7)
Disable power supply to the boiler by
deactivating the mains isolator switch
in the boiler room
Close the gas supply to the boiler.
7
1 2
6
5
4
3
Commissioning
Commissioning protocol
29
Commissioning Protocol R3400/R3500/R3600
Project
Boiler type Project
Serial number Address
Year City
Nominal load (Hi) [kW] Date
Nominal output (Hi) [kW] Engineer
System
Water pressure [bar] Installati-
on:
Roof top
Water pH [-] Ground floor
Water hardness [dºH] Basement
Water chloride [mg/l] Other: .........................
Water T full load [ºC] Low velocity header
Water pboiler [kPa] Plated heat exchanger
Water flow [m3/h] Bypass boiler
Pump setting [-] Other: .........................
Safety devices
High limit setting [ºC] Water flow sensor checked
Temp. limiter setting [ºC] Water flow switch checked
Min. gas pressure switch setting [mbar]
Ignition time burner [sec]
Combustion analysis
100% load 50% load Min. load
Gas consumption [m3/h] [m3/h] [m3/h]
Gas pressure [mbar] [mbar] [mbar]
CO2 pilot burner [%] [%] [%]
O2 pilot burner [%] [%] [%]
CO pilot burner [ppm] [ppm] [ppm]
NOx pilot burner [ppm] [ppm] [ppm]
Tatmospheric [ºC] [ºC] [ºC]
Tfluegas [ºC] [ºC] [ºC]
Twater, flow [ºC] [ºC] [ºC]
Twater, return [ºC] [ºC] [ºC]
Ionisation current [µA] [µA] [µA]
pfan [mbar] [mbar] [mbar]
ptop panel [mbar] [mbar] [mbar]
pcombustion chamber [mbar] [mbar] [mbar]
Parameter settings
P1 Setpoint temperature heating C] P12 Boiler hysteresis [ºC]
P2 Setpoint temperature DHW [ºC] P17 Fan speed min. load [%]
P11 Maximum boiler setpoint [ºC] P19 Fan speed 100% load [%]
Remarks
Hydrau-
lics:
CO2 main burner [%] [%] [%]
O2 main burner [%] [%] [%]
CO main burner [ppm] [ppm] [ppm]
NOx main burner [ppm] [ppm] [ppm]
Operating instructions
Main menu (operating mode)
Parameter menu (information/programming mode)
Changing parameter values
30
The boiler controller has two menus: the main menu (operating mode) when the lid is closed, and the parameter menu
(information/programming mode) when the lid is open. Both menus and possibilities are explained in the next paragraphs.
Main menu (operating mode) lid closed
With the lid closed and by using the rotational switch (1) clockwise or anticlockwise
the boilers’ operating mode (2) can be set. The available modes are:
K Standby mode (only frost protection)
F Automatic operation mode (heating and DHW)
F Summer mode (only DHW, no heating)
W1 Service mode minimum load
W2 Service mode full load (limited by P9)
Besides the operating mode, the display also shows the actual water flow tempera-
ture (3) and, in case of a lockout, a warning triangle (4) combined with a lockout
code (5). The explanation of the lockout codes can be found in chapter
“Lockouts”.
Parameter menu (information/programming mode) lid open
With the lid open and by using the rotational switch (1) clockwise or anticlockwise
it’s possible to read/change certain values/parameters from the boiler controller.
An arrow at the bottom of the display (2) indicates which parameter has been se-
lected. The available values/parameters are:
P1 Actual / setpoint water flow temperature [ºC]
P2 Actual / setpoint DHW temperature [ºC]
P3 Actual temperature/capacity setpoint for boiler [ºC]*
P4 --
P5 Actual outside temperature [ºC] (if sensor is connected)
P6 Actual fluegas temperature [ºC]
P7 --
P8 Actual low velocity header temperature [ºC] (if sensor is connected)
P9 Actual / Limit boiler output [%]
P10 Password for advanced settings
Press the reset/programming button
to select (the LED lights up)
Turn the rotational switch until the
desired DHW setpoint value has been
reached
Press the reset/programming button
to confirm (the LED goes out)
Close the lid.
Output indications
Power to main gas valve
Power to ignition transformer
Fan control signal
Z Power to primary boiler pump
F Power to DHW pump/diverter valve
Behind the lid you find an optical I/O
connection (6), a reset/programming
button (7) and an alarm/programming
LED (8). Besides the parameter values/
settings, the display also shows additio-
nal information with regard to input and
output indications to and from the boi-
ler:
Input indications
H Flame ionisation detected
SW Water flow switch active
DW Air pressure switch active
RT Boiler enabled**
Bus Bus communication active
Changing parameter values
For changing any parameters, in the
example parameter P2 (DHW setpoint),
the following procedure should be car-
ried through:
Open the lid (the arrow at the bottom
of the display indicates parameter P1)
Turn the rotational switch clockwise
until the arrow indicates parameter P2
The new value is now activated. All
parameters can be changed by follo-
wing the same procedure as described
above.
**The boiler enable signal is equipped with a jumper in the standard delivery and therefore the boiler will normally be enabled. If a building
management system is connected to provide the enable signal to the boiler (jumper should be removed), check the building management
system if the boiler remains disabled.
* P3 shows the actual temperature setpoint of the boiler, either coming from P1/P2 or from an additional (weather compensated) controller or
building management system (2-10V). When the boiler capacity is controlled via a cascade manager or building management system (2-10V),
P3 shows the actual capacity setpoint of the boiler.
2 5 3 4 1
2 1
6 7 8
Maintenance
Checklist
Replacing the electrodes
31
Maintenance of the boiler should be
carried out by authorized personnel
only.
In order to ensure continued good and
safe operation of the boiler, it should be
inspected at least once per year. A
maintenance protocol should be filled
out (see end of this chapter for example
of maintenance protocol).
Checklist
The following activities must be carried
out, see following paragraphs for an
extensive description of the main activi-
ties:
Replace the ignition and ionisation
electrodes;
Clean the condensate receptacle;
Clean and refill the syphon;
Check the water pressure of the sys-
tem;
Check the water quality of the system
water as well as supply water;
Check the water flow rate through the
boiler;
Check/correct the combustion values
at full and mimimum load with a com-
bustion analyzer;
Check the gas pressure to the boiler;
Check the tightness of all sealed con-
nections and test points;
Check the functionality of all safety
devices;
Fill out a maintenance protocol.
Replacing the electrodes
The electrodes are positioned on the
right hand side of the boiler. Replace
the ignition elektrode (1) and ionisation
electrodes (2) as shown on the picture.
2
1
Maintenance
Cleaning the condensate receptacle
Cleaning and refilling the syphon
32
Cleaning the condensate receptacle
Remove the inspection hatch (2) to
access the inside of the condensate
receptacle;
Clean the receptacle;
Mount the inspection hatch.
Cleaning and refilling the syphon
Remove the syphon (3) from the con-
densate connection;
Clean and fill it with fresh water;
Mount the syphon back in the original
position.
1
2
3
Water pressure and quality
Check if the water pressure and quality
meet the requirements. Consult the
chapter “commissioning: water and
hydraulic system” for more detailed
information.
Water flow rate
Check if the water flow rate through the
boiler is within the limits. Consult the
chapter “commissioning: check water
flow” for more detailed information.
Combustion analysis
Check the combustion at full load and
minumum load, correct the settings if
necessary. An additional reference
check at 50% load is recommended.
Consult the chapter “commissioning:
combustion analysis” for more detailed
information.
Gas pressure
Check the dynamic pressure of the gas
supply to the boiler, when the boiler is
running at full load. In case of a boiler
cascade, all boilers should be running
at full load. See technical data for re-
quired values.
Combustion analysis
Check the combustion at full load and
minumum load, correct the settings if
necessary. An additional reference
check at 50% load is recommended.
Consult the chapter “commissioning:
combustion analysis” for more detailed
information.
Gas pressure
Check the dynamic pressure of the gas
supply to the boiler, when the boiler is
running at full load. In case of a boiler
cascade, all boilers should be running
at full load. See technical data for re-
quired values.
Maintenance
Maintenance Protocol
33
Maintenance Protocol R3400/R3500/R3600
Project
Boiler type Project
Serial number Address
Year City
Nominal load (Hi) [kW] Date
Nominal output (Hi) [kW] Engineer
System
Water pressure [bar]
Water pH [-]
Water hardness [dºH]
Water chloride [mg/l]
Water T full load [ºC]
Water pboiler [kPa]
Water flow [m3/h]
Pump setting [-]
Safety devices
High limit setting [ºC] Water flow sensor checked
Temp. limiter setting [ºC] Water flow switch checked
Min. gas pressure switch setting [mbar]
Ignition time burner [sec]
Combustion analysis
100% load 50% load Min. load
Gas consumption [m3/h] [m3/h] [m3/h]
Gas pressure [mbar] [mbar] [mbar]
CO2 Pilot burner [%] [%] [%]
O2 Pilot burner [%] [%] [%]
CO Pilot burner [ppm] [ppm] [ppm]
NOx Pilot burner [ppm] [ppm] [ppm]
Tatmospheric [ºC] [ºC] [ºC]
Tfluegas [ºC] [ºC] [ºC]
Twater, flow [ºC] [ºC] [ºC]
Twater, return [ºC] [ºC] [ºC]
Ionisation current [µA] [µA] [µA]
pfan [mbar] [mbar] [mbar]
ptop panel [mbar] [mbar] [mbar]
pcombustion chamber [mbar] [mbar] [mbar]
Parameter settings
P1 Setpoint temperature heating C] P12 Boiler hysteresis [ºC]
P2 Setpoint temperature DHW [ºC] P17 Fan speed min. load [%]
P11 Maximum boiler setpoint [ºC] P19 Fan speed 100% load [%]
Remarks
CO2 Main burner [%] [%] [%]
O2 Main burner [%] [%] [%]
CO Main burner [ppm] [ppm] [ppm]
NOx Main burner [ppm] [ppm] [ppm]
34
In case of a lockout, a warning triangle (E) and a flashing error code appears on the display. The cause of a fault should first
be determined and eliminated before the boiler is being reset. In case the lockout appears more than twice within 6 minutes or
maintains for longer than 6 minutes, the error code is added with a “3”. The table below shows all possible lockouts and an
indication of possible cause.
No. Error type Explanation Possible solution
1 Lockout Water flow temperature has exceeded the high
limit temperature setting (100ºC).
Check if boiler is in automatic mode (K), Check if water
flow through the boiler is sufficient, check if (P11+P12)
< High limit setting (V9).
2 Interlock Gas pressure has dropped below minimum value
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during startup).
Check gas supply pressure / check function of additio-
nal safety device on interlock input.
3 Interlock Gas pressure has dropped below minimum value
of minimum gas pressure switch or additional
safety device connected to the interlock input has
been interrupted (during operation).
Check gas supply pressure / check function of additio-
nal safety device on interlock input.
4 Lockout No flame ionisation signal detected during burner
start.
Check phase/neutral of power supply (phase sensitivi-
ty!), check gas supply, check ignition spark, increase
gas valve setting min. load (alan key screw).
5 Lockout Flame ionisation signal lost during operation. Check gas supply pressure during operation, check
gas valve setting via combustion analysis.
6 Interlock Water flow temperature has exceeded the tem-
perature limiter setting (97ºC). Check if boiler is in automatic mode (F), check if water
flow through the boiler is sufficient, check if (P11+P12)
< Temp. limiter setting (V10).
7 Lockout External safety device connected to the lockout
input has been interrupted.
Check the external safety devices (water pressure
switches, safety thermostat, etc.)
11 Lockout Flame ionisation signal detected before burner
start.
Check ionisation electrode, measure ionisation current
when boiler is off, check wiring between ionisation
electrode and boiler controller.
12 Interlock Water flow temperature sensor is defective. Check resistance of sensor (see chapter “sensor
values”), check wiring between water flow temperature
sensor and boiler controller.
14 Interlock DHW temperature sensor (optional) is defective. Check resistance of sensor (see chapter “sensor
values”), check wiring between DHW temperature
sensor and boiler controller.
15 Interlock Outside temperature sensor (optional) is defecti-
ve.
Check resistance of sensor (see chapter “sensor
values”), check wiring between outside temperature
sensor and boiler controller.
18 Interlock Header temperature sensor (optional) is defecti-
ve.
Check resistance of sensor (see chapter “sensor
values”), check wiring between header temperature
sensor and boiler controller.
Lockouts
35
No. Error type Explanation Possible solution
20 Lockout Error gas valve V1, flame ionisation signal detec-
ted longer than 5 seconds after burner stop.
Check closing position of valve V1 within gas combi
valve, replace gas valve.
21 Lockout Error gas valve V2, flame ionisation signal detec-
ted longer than 5 seconds after burner stop.
Check closing position of valve V2 within gas combi
valve, replace gas valve.
22 Lockout APS contact does not close during prepurge. Check setting APS, check if fan is running.
23 Lockout APS contact remains closed when fan is off. Check setting APS
27 Lockout APS contact opens during operation. Check setting APS
30 Lockout CRC error in control system parameters (P11-
P40).
Check parameter settings of P11-P40, change value of
one parameter within P11-P40 (lockout disappears),
change all parameters back to original settings.
31 Lockout CRC error in boiler safety parameters (V1-V16). Check parameter settings of V1-V16, change value of
one parameter within V1-V16 (lockout disappears),
change all parameters back to original settings.
32 Interlock Power supply voltage to boiler controller is too
low.
Check fuse of boiler controller, check power supply to
boiler controller.
40 Lockout Water flow switch has been interrupted when
pump being enabled.
Check pump operation, check water flow through the
boiler, check functionality of water flow switch.
x.y. Lockout (all lockout codes which are not listed above)
Internal lockout of boiler controller.
Press reset. Change boiler controller when lockout can
not be reset or occurs more frequently.
Lockouts
Sensor values
36
The diagrams show the sensor values
for all boiler sensors and optional sen-
sors available in accessory kits.
The diagrams contain average values,
as all sensors are liable to tolerances.
When measuring the resistance values,
the boiler should always be switched
off. Measure close to the sensor, in
order to avoid value deviations.
Water flow and fluegas temperature sensor (5k NTC)
DHW, outside and header temperature sensor (1k PTC)
Declaration of Conformity
37
Declaration of Conformity
Rendamax BV, Hamstraat 76, 6465 AG Kerkrade (NL),
declares that the products
R3400/3500/3600
are in conformity with the following standards:
EN 656
EN 15417
EN 13836
EN 55014-1 / -2
EN 61000-3-2 /-3
EN 60 335-1/ -2
and in accordance with the guidelines of directives:
92 / 42 / EEC (boiler efficiency directive)
90 / 396 / EEC (gas appliance directive)
73 / 23 / EEC (low voltage directive)
89 / 336 / EEC (EMC directive)
These products are designated with CE nr.:
CE – 0063AR3514
Kerkrade, 10-06-2013
A.J.G. Schuiling
Plant Manager
Betriebsanleitung
für die autorisierte Fachkraft
R3400/R3500/R3600
05/2014 420010582400
Inhalt
2
Inhalt ......................................................................................................................... 2
Sicherheitsbestimmungen Allgemeine Bestimmungen ............................................................................. 3
Verwendungszweck ........................................................................................ 3
Normen und Vorschriften ................................................................................. 3
Konstruktion Produktbeschreibung ....................................................................................... 4
Funktionsbeschreibung .................................................................................... 4
Technische Daten ......................................................................................................................... 5
Lieferumfang Standard Ausführung .................................................................................... 15
Zubehör ......................................................................................................... 15
Installation Transport ........................................................................................................ 16
Demontage Verkleidung ................................................................................. 18
Installation ...................................................................................................... 19
Anschlüsse ..................................................................................................... 20
Inbetriebnahme Wasser- und Hydrauliksystem ....................................................................... 22
Gasversorgung ............................................................................................. 23
Kondensatanschluss ..................................................................................... 23
Abgas- und Zuluftanschlüsse ........................................................................ 23
Vorbereitung für 1. Inbetriebnahme .............................................................. 24
Verbrennungswerte ....................................................................................... 25
Luftdruckwächter ........................................................................................... 26
Wasserdurchsatz prüfen ............................................................................... 27
Sicherheitseinrichtungen prüfen .................................................................... 28
Gasdichtheitsprüfung .................................................................................... 28
Kessel außer Betrieb setzen ......................................................................... 28
Inbetriebnahme Protokoll .............................................................................. 29
Bedienungs-/Parametereinstellungen
Hauptmenü
.................................................................................................. 30
Parametermenü ............................................................................................. 30
Parametereinstellungen verändern ................................................................ 30
Wartung Checkliste ................................................................................................................... 31
Ersetzen der Elektroden ............................................................................... 32
Reinigung der Kondensatwanne ................................................................... 32
Reinigen und Auffüllen des Siphons ............................................................. 32
Wasserdruck und -qualität ............................................................................ 32
Wasserdurchsatz .......................................................................................... 32
Verbrennungswerte ....................................................................................... 32
Gasdruck ....................................................................................................... 32
Gasdichtheitsprüfung .................................................................................... 32
Sicherheitseinrichtungen ............................................................................... 32
Wartungsprotokoll ......................................................................................... 33
Störungen ....................................................................................................................... 34
Fühlerkennwerte ....................................................................................................................... 36
Konformitätserklärung ....................................................................................................................... 37
Sicherheitsbestimmungen
Allgemeine Bestimmungen
Verwendungszweck
Normen und Vorschriften
3
Allgemeine Bestimmungen
Diese Dokumentation enthält wichtige
Hinweise bezüglich Sicherheit und Zu-
verlässigkeit von Installation, Inbetrieb-
nahme und Betreibung des R3400/
R3500/R3600 Kessels. Alle beschrie-
benen Tätigkeiten sind ausschließlich
durch die autorisierte Fachkraft auszu-
führen.
Es dürfen nur Original Bauteile des
Kesselherstellers verwendet werden,
ansonsten schließen wir unsere Ge-
währ- und Garantieleistungsbedingun-
gen aus.
Verwendungszweck
Der R3400/R3500/R3600 Heizkessel
ist ausschliesslich für geschlossene
Warmwasserheizungsanlagen zu ver-
wenden. Die maximale Temperatur des
Kesselsollwerts beträgt 90ºC, sowie
100ºC des Systems
(Sicherheitstemperatur Limit).
Normen und Vorschriften
Bei Installation und Betreibung des
R3400/R3500/R3600 Kessels müssen
alle maßgebenden Normen
(europäische und nationale) eingehal-
ten werden:
Lokale Gebäudevorschriften über die
Installation von Heizungsanlagen und
Abgassysteme
Vorschriften über den Anschluss an
das elektrische Versorgungsnetz
Vorschriften der lokalen Gasversor-
gungsunternehmen
Normen und Vorschriften betreffend
Sicherheitseinrichtungen für Hei-
zungsanlagen
Zusätzliche lokale Gesetze/Vorschrif-
ten bezüglich Installationen und Be-
treibung von Heizungsanlagen.
Der R3400/R3500/R3600 Kessel ist
CE geprüft und beinhaltet die folgen-
den europäischen Normen:
92 / 42 / EEC (Wirkungsgrade von
Warmwasserheizungsanlagen)
90 / 396 / EEC
(Gasverbrauchseinrichtungen)
73 / 23 / EEC (Sicherheit von elektri-
schen Betriebsmitteln)
89 / 336 / EEC (EMV Verträglichkeit)
EN 656 (Anforderungen an Gasfeue-
rungsanlagen – Type B Kessel 70 kW
– 300 kW)
EN 15417 (Spezielle Anforderungen
für kondensierende Gasheizkessel 70
kW – 1000 kW)
EN 13836 (Anforderungen an Gas-
feuerungsanlagen – Type B Kessel
300 kW – 1000 kW)
EN 15502-1 (Anforderungen an Gas-
feuerungsanlagen – Part 1: allgemei-
ne Anforderungen und Tests)
EN 55014-1 EMV – Anforderungen
an Haushaltgeräte, elektrische Werk-
zeuge und ähnliche Apparate – Teil 1:
Emissionen
EN 55014-2 EMV – Anforderungen
an Haushaltgeräte, elektrische Werk-
zeuge und ähnliche Apparate – Teil 2:
Sicherheit - Produktefamilienstandard
EN 61000-3-2 Elektromagnetische
Kompatibilität (EMC) - Teil 3-2: Rah-
menbedingungen - Rahmenbedingun-
gen für Stromschwankungen
(Stromaufnahme 16 A pro Phase)
EN 61000-3-3 Elektromagnetische
Kompatibilität (EMC) - Part 3-3: Rah-
menbedingungen für Spannungs-
schwankungen, Spannungsverluste
und –Flicker in öffentlichen Nieder-
spannungsnetzen, für Equipment mit
Nennstrom 16 A pro Phase, die kei-
ner Sonderanschlussbedingung un-
terliegen.
EN 60335-1 Haushalt und ähnliche
elektrische Geräte - Sicherheit-Teil 1:
Allgemeine Anforderungen
EN 50165 Haushalt und ähnliche
elektrische Geräte - Sicherheit - Teil 2
-102: Besondere Anforderungen für
Gas, Öl und Festbrennstoff gefeuerte
Geräte mit elektrischen Anschlüssen
Darüber hinaus sind die nationalen
Normen zu beachten:
Deutschland:
RAL - UZ 61 / DIN 4702-8
Schweiz:
SVGW
EKAS-Form. 1942: Flüssiggas-
Richtlinie Teil 2
Vorschriften der kantonalen Instanzen
(z.B. Feuerpoilizeivorschriften)
Holland:
(gilt nur für
R3401-R3406 und R3600-R3605)
GASKEUR BASIS
GASKEUR SV
GASKEUR HR107
Belgien:
HR TOP
Konstruktion
Produktbeschreibung
Funktionsbeschreibung
4
Der R3400/R3500/R3600 Heizkessel
beinhaltet nachfolgende Hauptkompo-
nenten:
1 Rücklauf Anschluss
2 Abgas Anschluss
3 Strömungswächter
4 Sicherheitsventil
5 Vorlauf Anschluss
6 Befüll-/Entleerhahn
7 Topplatte
8 Verteilplatte
9 Brenner
10 1. Wärmetauscher
11 Gasfilter
12 2. Wärmetauscher
13 Gasrohr
14 Rahmen
15 Umlenkstück
16 Anti-Resonanz Rohr
17 Abgas Anschluss
18 Kondensatwanne
19 Abgassammelkasten
20 Brennerraum
21 Kabel Einführung
22 Kondensat Ablauf
23 Hauptgasventil
24 Gebläse
25 Schaltfeld
26 Bedienteil
27 Verkleidung
28 Verbrennungsluft Dämpfer
29 Drosselventil Gas
30 Hauptmischkanal
31 Zündgasventil
32 Zündmischkanal
33 Kesselkreispumpe
34 3. Wärmetauscher (nur R3600 Rei-
he)
A Luft
B Gas
C Abgas
D Kondensat
Funktionsbeschreibung
Der R3400/R3500/R3600 ist ein modu-
lierender Brennwertheizkessel. Der
Feuerungsmanager passt die Modula-
tion automatisch dem aktuellen Wärme-
bedarf des Heizsystems an. Dies ge-
schieht indem der Feuerungsmanager
die Gebläsedrehzahl laufend anpasst.
Hierbei passt die Verbundregelung die
Gasmenge der gewählten Geblä-
sedrehzahl an, um eine optimale Ver-
brennung und somit die bestmögliche
Effizienz zu erzielen. Die entstandenen
Abgase werden abwärts durch den
Heizkessel geleitet
Mit dem Feuerungsmanager KM628
können folgende Regelungsvarianten
realisiert werden:
Kesselregulierung
(stand alone);
Witterungsgeführt geregelt
(mit zusätzlichem Regler E8);
Externe Sollwertführung 0-10V
(Temperatur oder Leistung) von ei-
nem Gebäudeleitsystem.
und auf der Rückseite in den Kaminan-
schluss geführt. Der Rücklaufanschluss
ist im unteren Bereich des Heizkessels
angeordnet, dort wo die tiefste Abgas/
Kesseltemperatur im Heizkessel auftritt.
In diesem Bereich tritt Kondensation
auf. Das Wasser wird aufwärts durch
den ganzen Heizkessel transportiert, wo
es oben im Brennerbereich wieder aus-
tritt (Vorlaufanschluss). Somit kann eine
höchstmögliche Wärmeabgabe an das
System erfolgen. Dieses Prinzip bewirkt
eine bestmögliche und äußerst effizien-
te Verbrennung.
34
Technische Daten
Technische Daten R3401 - R3405
5
R3401 R3402 R3403 R3404 R3405
Nennwärmeleistung 80-60ºC max/min kW 656/164 733/183 857/213 971/242 1084/270
Nennwärmeleistung 75-60ºC max/min kW 657/164 734/183 858/213 972/242 1085/270
Nennwärmeleistung 40/30ºC max/min kW 663/181 741/202 867/236 981/268 1095/298
Feuerungswärmeleistung max/min kW 702/176 784/196 917/229 1038/260 1159/290
Wirkungsgrad 80/60ºC % 93.5
Wirkungsgrad 40/30ºC % 94.5
Normnutzungsgrad 75/60ºC % 100.0
Normnutzungsgrad 40/30ºC % -
Bereitschaftsverluste (T Wasser = 70ºC) % 0.2
Max. anfallendes Kondensat l/h -
Gasverbrauch H-Gas (G20) max/min (10,9 kWh/m3) m3/h 64.5/16.2 71.9/18.0 84.1/21.0 95.2/23.8 106.3/26.6
Gasverbrauch L-Gas (G25) max/min (8,34 kWh/m3) m3/h 84.3/21.1 94.0/23.5 109.9/27.4 124.4/31.2 139.0/34.8
Gasverbrauch F-Gas (G31) max/min (12,8 kWh/kg) kg/h 54.9/13.8 61.2/15.3 71.6/17.9 81.1/20.3 90.5/22.6
Gasdruck H-Gas (G20) mbar 20 35
Gasdruck L/-Gas (G25) mbar 25 35
Gasdruck F-Gas (G31) mbar 30/50
Maximaler Gasdruck mbar 100
Abgastemperaturen bei 80/60ºC max/min ºC 165/70
Abgastemperaturen bei 40/30ºC max/min ºC 135/60
Abgas Durchsatz max/min m3/h 1423/356 1580/395 1848/462 2091/523 2334/584
CO2 Wert Hauptbrenner Erdgas H/L max/min % 10.0/9.3
CO2 Wert Hauptbrenner Flüssiggas P max/min % 11.0/11.0
CO2 Wert Zündbrenner Erdgas H/L max/min % 10.0/10.2
CO2 Wert Zündbrenner Flüssiggas P max/min % 11.0/11.2
NOx Wert max/min mg/kWh 61.4/22.0
CO Wert max/min mg/kWh 9.8/3.3
Förderdruck des Gebläses max/min Pa 150
Wasser Inhalt l 50 53 70 75 80
Wasserdruck max/min bar 8/1
Sicherheitsthermostat ºC 100
Maximaler Sollwert ºC 90
Nominaler Wasser Durchsatz bei dT=20K m3/h 28.5 31.6 37.0 41.8 46.8
Druckverlust Kessel kPa 46 53 36 43 50
Elektrischer Anschluss V 400
Frequenz Hz 50
Elek. Absicherung A 16 20
IP Klasse - IP20
El. Leistungsaufn. Kessel (o.Pumpe) W 900 900 1270 1270 1270
El. Leistungsaufn. Pumpen 3-stufig (opt.) W 980 1010 1020 1450 1500
Gewicht kg 675 740 840 950 1070
Schallpegel in 1m Abstand dB(A) 64
Min. Ionisationsstrom µA 6
PH Wert des Kondensates - 3.2
CE Nr. - CE-0063AR3514
Wasser Anschlüsse - DN65 PN16 DN80 PN16
Gas Anschluss - R 2” DN65 PN16
Abgas Anschluss mm 300 350 400
Zuluft Anschlüsse (raumluftunabhängig) mm 250 300 355
Kondensat Anschluss mm 40
Technische Daten
Technische Daten R3406 - R3410
6
R3600 R3601 R3602 R3603 R3604
R3605
Nennwärmeleistung 80-60ºC m
x/ in
kW
57
/142
639
182
747/
12
846/2
1
945/26
1043/297
Nennwärmeleistung 75-60
C ax/min
k
576/144
643/184
53/215
8
2/243
95
/272
1050/300
Nennwärmeleistung 4
/3 ºC max/m n
kW
602
159
672/
03
786/2
7
890/26
994/300
1097/331
Feuerungswär
el istung m x/min
kW
585/146
53/187
7
4/218
86
/247
966/276
irku
gsgrad 80/60ºC
%
97.
irku
gsgrad 40/30ºC
%
102.9
No
m utzun
sgrad 75/60ºC
%
105,1
m u
zungsgrad 40/30ºC
%
109,8
Bereitschaft
v rlu
te (T Wasser = 70ºC)
%
Max
nfallendes Kondensat
l/h
-
Gasverbrauch H-Gas
G20) max/min (1 ,9 kWh/m3) m3/h
53.7/
3.4
59.9/1
.1
70.1/20
0
79.4/22.7
88.6/25.3
97.8/27.9
Gasverbrauch L
Gas G25) max/m n (8,34 kW /m3)
m3/h
0.3/17.6
7
.3/22.4
91
6/26.2 rauc F-Gas
(
G1
)
max/min
(
12
,
8 kWh/
g)
7/11.4
Technische Daten
Abmessungen R3401 - R3406
7
Abmessung R3401 R3402 R3403 R3404 R3405 R3406
L mm 2265 2265 2653 2653 2658 2658
L1 mm 595 595 610 615 615 770
L2 mm 700 700 1166 1166 1166 1166
L3 mm 108 108 88 88 88 88
H mm 1355 1355 1355 1355 1355 1355
H1 mm 1125 1125 1570 1420 1155 1377
B mm 1330 1330 1130 1130 1330 1330
B1 mm 1160 1210 1003 1053 1203 1253
B2 mm 665 665 565 565 665 665
B3 mm 170 120 127 77 127 77
B4 mm 1146 1146 946 946 1146 1146
B5 mm 115 65 115 65 115 65
D mm 300 350 350 400 400 400
W DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" R 2" DN65 PN16 DN65 PN16
Technische Daten
Technische Daten R3501 - R3505
9
R3501 R3502 R3503 R3504 R3505
Nennwärmeleistung 80-60ºC max/min kW 613/175 717/204 811/231 906/258 1000/285
Nennwärmeleistung 75-60ºC max/min kW 613/175 717/204 812/231 907/258 1001/285
Nennwärmeleistung 40/30ºC max/min kW 624/195 730/228 826/258 923/288 1018/319
Feuerungswärmeleistung max/min kW 653/187 764/218 865/247 966/276 1066/305
Wirkungsgrad 80/60ºC % 93.8
Wirkungsgrad 40/30ºC % 95.5
Normnutzungsgrad 75/60ºC % 102.2
Normnutzungsgrad 40/30ºC % -
Bereitschaftsverluste (T Wasser = 70ºC) % 0.3
Max. anfallendes Kondensat l/h -
Gasverbrauch H-Gas (G20) max/min (10,9 kWh/m3) m3/h 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gasverbrauch L-Gas (G25) max/min (8,34 kWh/m3) m3/h 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gasverbrauch F-Gas (G31) max/min (12,8 kWh/kg) kg/h 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gasdruck H-Gas (G20) mbar 20
Gasdruck L/-Gas (G25) mbar 25
Gasdruck F-Gas (G31) mbar 30/50
Maximaler Gasdruck mbar 100
Abgastemperaturen bei 80/60ºC max/min ºC 155/65
Abgastemperaturen bei 40/30ºC max/min ºC 120/55
Abgas Durchsatz max/min m3/h 1287/368 1505/430 1703/487 1901/543 2099/600
CO2 Wert Hauptbrenner Erdgas H/L max/min % 10.0/9.3
CO2 Wert Hauptbrenner Flüssiggas P max/min % 11.0/11.0
CO2 Wert Zündbrenner Erdgas H/L max/min % 10.0/10.2
CO2 Wert Zündbrenner Flüssiggas P max/min % 11.0/11.2
NOx Wert max/min mg/kWh 11.5/19.5
CO Wert max/min mg/kWh 27.3/6.5
Förderdruck des Gebläses max/min Pa 150
Wasser Inhalt l 53 70 75 80 85
Wasserdruck max/min bar 8/1
Sicherheitsthermostat ºC 100
Maximaler Sollwert ºC 90
Nominaler Wasser Durchsatz bei dT=20K m3/h 26,4 30,8 34,9 39,0 43,0
Druckverlust Kessel kPa 37 25 30 35 40
Elektrischer Anschluss V 400
Frequenz Hz 50
Elek. Absicherung A 16 20
IP Klasse - IP20
El. Leistungsaufn. Kessel (o.Pumpe) W 900 1270
El. Leistungsaufn. Pumpe 3-stufig (opt.) W
El. Leistungsaufn. Pumpen drehzahlgesteuert (opt.) W 394 375 523 557 708
Gewicht kg 740 840 950 1070 1200
Schallpegel in 1m Abstand dB(A) 64
Min. Ionisationsstrom µA 6
PH Wert des Kondensates - 3.2
CE Nr. - CE-0063AR3514
Wasser Anschlüsse - DN65 PN16 DN80 PN16
Gas Anschluss - R 2” DN65 PN16
Abgas Anschluss mm 300 350 400
Zuluft Anschlüsse (raumluftunabhängig) mm 250 300 355
Kondensat Anschluss mm 40
960 1000 1020 1400 1500
Technische Daten
Abmessungen R3501 - R3505
10
Abmessung R3501 R3502 R3503 R3504 R3505
L mm 2265 2653 2653 2658 2658
L1 mm 595 610 610 615 615
L2 mm 700 1166 1166 1166 1166
L3 mm 108 88 88 88 88
H mm 1355 1355 1355 1355 1355
H1 mm 1125 1400 1400 1155 1155
B mm 1330 1130 1130 1330 1330
B1 mm 1210 1003 1053 1203 1253
B2 mm 665 565 565 665 665
B3 mm 120 127 77 127 77
B4 mm 1146 946 946 1146 1146
B5 mm 65 115 65 115 65
D mm 300 350 350 400 400
W DN DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" DN65 PN16 DN65 PN16
Technische Daten
Technische Daten R3600 - R3605 Standard
11
R3600 R3601 R3602 R3603 R3604 R3605
Nennwärmeleistung 80-60ºC max/min kW 572/142 639/182 747/212 846/241 945/269 1043/297
Nennwärmeleistung 75-60ºC max/min kW 576/144 643/184 753/215 852/243 952/272 1050/300
Nennwärmeleistung 40/30ºC max/min kW 602/159 672/203 786/237 890/268 994/300 1097/331
Feuerungswärmeleistung max/min kW 585/146 653/187 764/218 865/247 966/276 1066/305
Wirkungsgrad 80/60ºC % 97.8
Wirkungsgrad 40/30ºC % 102.9
Normnutzungsgrad 75/60ºC % 105,1
Normnutzungsgrad 40/30ºC % 109,8
Bereitschaftsverluste (T Wasser = 70ºC) % 0,3
Max. anfallendes Kondensat l/h -
Gasverbrauch H-Gas (G20) max/min (10,9 kWh/m3) m3/h 53.7/13.4 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gasverbrauch L-Gas (G25) max/min (8,34 kWh/m3) m3/h 70.3/17.6 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gasverbrauch F-Gas (G31) max/min (12,8 kWh/kg) kg/h 45.7/11.4 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gasdruck H-Gas (G20) mbar 20
Gasdruck L/-Gas (G25) mbar 25
Gasdruck F-Gas (G31) mbar 30/50
Maximaler Gasdruck mbar 100
Abgastemperaturen bei 80/60ºC max/min ºC 85/65
Abgastemperaturen bei 40/30ºC max/min ºC 59/36
Abgas Durchsatz max/min m3/h 969/242 1076/307 1258/359 1424/407 1590/454 1756/502
CO2 Wert Hauptbrenner Erdgas H/L max/min % 10.0/9.3 10.0/9.3
CO2 Wert Hauptbrenner Flüssiggas P max/min % 11.0/11.0 11.0/11.0
CO2 Wert Zündbrenner Erdgas H/L max/min % - 10.0/10.2
CO2 Wert Zündbrenner Flüssiggas P max/min % - 11.0/11.2
NOx Wert max/min mg/kWh 32.3/18.8 11.5/19.5
CO Wert max/min mg/kWh 8.2/10.9 27.3/6.5
Förderdruck des Gebläses max/min Pa 100 150
Wasser Inhalt l 69 73 97 104 110 117
Wasserdruck max/min bar 8/1
Sicherheitsthermostat ºC 100
Maximaler Sollwert ºC 90
Nominaler Wasser Durchsatz bei dT=20K m3/h 24,7 27,6 32,2 36,5 40,8 45,0
Druckverlust Kessel kPa 48 56 38 45 53 60
Elektrischer Anschluss V 400
Frequenz Hz 50
Elek. Absicherung A 10 16 20
IP Klasse - IP20
El. Leistungsaufn. Kessel (o.Pumpe) W 420 900 1270
El. Leistungsaufn. Pumpen 3-stufig W
Gewicht kg 810 890 1040 1150 1280 1410
Schallpegel in 1m Abstand dB(A) 64
Min. Ionisationsstrom µA 6
PH Wert des Kondensates - 3.2
CE Nr. - CE-0063AR3514
Wasser Anschlüsse - DN65 PN16 DN80 PN16
Gas Anschluss - R 2” DN65 PN16
Abgas Anschluss mm 300 350 400
Zuluft Anschlüsse (raumluftunabhängig) mm 250 300 355
Kondensat Anschluss mm 40
940 980 1020 1400 1450 1500
El. Leistungsaufn. Pumpen drehzahlgesteuert (opt.) W 471 616 561 661 867 956
Technische Daten
Technische Daten R3600 - R3605 Split system
13
R3600 R3601 R3602 R3603 R3604 R3605
Nennwärmeleistung 80-60ºC max/min kW 572/142 639/182 747/212 846/241 945/269 1043/297
Nennwärmeleistung 75-60ºC max/min kW 576/144 643/184 753/215 852/243 952/272 1050/300
Nennwärmeleistung 40/30ºC max/min kW 602/159 672/203 786/237 890/268 994/300 1097/331
Feuerungswärmeleistung max/min kW 585/146 653/187 764/218 865/247 966/276 1066/305
Wirkungsgrad 80/60ºC % 97.8
Wirkungsgrad 40/30ºC % 102.9
Normnutzungsgrad 75/60ºC % 105,1
Normnutzungsgrad 40/30ºC % 109,8
Bereitschaftsverluste (T Wasser = 70ºC) % 0,3
Max. anfallendes Kondensat l/h -
Gasverbrauch H-Gas (G20) max/min (10,9 kWh/m3) m3/h 53.7/13.4 59.9/17.1 70.1/20.0 79.4/22.7 88.6/25.3 97.8/27.9
Gasverbrauch L-Gas (G25) max/min (8,34 kWh/m3) m3/h 70.3/17.6 78.3/22.4 91.6/26.2 103.7/29.6 115.8/33.1 127.8/36.5
Gasverbrauch F-Gas (G31) max/min (12,8 kWh/kg) kg/h 45.7/11.4 51.0/14.6 59.7/17.1 67.6/19.3 75.5/21.6 83.3/23.8
Gasdruck H-Gas (G20) mbar 20
Gasdruck L/-Gas (G25) mbar 25
Gasdruck F-Gas (G31) mbar 30/50
Maximaler Gasdruck mbar 100
Abgastemperaturen bei 80/60ºC max/min ºC 85/65
Abgastemperaturen bei 40/30ºC max/min ºC 59/36
Abgas Durchsatz max/min m3/h 969/242 1076/307 1258/359 1424/407 1590/454 1756/502
CO2 Wert Hauptbrenner Erdgas H/L max/min % 10.0/9.3 10.0/9.3
CO2 Wert Hauptbrenner Flüssiggas P max/min % 11.0/11.0 11.0/11.0
CO2 Wert Zündbrenner Erdgas H/L max/min % - 10.0/10.2
CO2 Wert Zündbrenner Flüssiggas P max/min % - 11.0/11.2
NOx Wert max/min mg/kWh 32.3/18.8 11.5/19.5
CO Wert max/min mg/kWh 8.2/10.9 27.3/6.5
Förderdruck des Gebläses max/min Pa 100 150
Wasser Inhalt l 73 73 97 104 110 117
Wasserdruck max/min bar 8/1
Sicherheitsthermostat ºC 100
Maximaler Sollwert ºC 90
Nominaler Wasser Durchsatz bei dT=20K m3/h 24,7 27,6 32,2 36,5 40,8 45,0
Druckverlust Kessel kPa 48 56 38 45 53 60
Elektrischer Anschluss V 400
Frequenz Hz 50
Elek. Absicherung A 10 16 20
IP Klasse - IP20
El. Leistungsaufn. Kessel (o.Pumpe) W 730 900 1270
Gewicht kg 810 890 1040 1150 1280 1410
Schallpegel in 1m Abstand dB(A) 64
Min. Ionisationsstrom µA 6
PH Wert des Kondensates - 3.2
CE Nr. - CE-0063AR3514
Wasser Anschlüsse - DN65 PN16 DN80 PN16
Gas Anschluss - R 2” DN65 PN16
Abgas Anschluss mm 300 350 400
Zuluft Anschlüsse (raumluftunabhängig) mm 250 300 355
Kondensat Anschluss mm 40
Technische Daten
Abmessungen R3600 - R3605 Split system
14
Abmessung R3600 R3601 R3602 R3603 R3604 R3605
L mm 1958 2070 2443 2443 2443 2443
L2 mm 700 590 1166 1166 1166 1166
L3 mm 108 198 88 88 88 88
H mm 1355 1405 1405 1405 1405 1405
B mm 1230 1330 1130 1130 1330 1330
B1 mm 1110 1210 1003 1053 1203 1253
B2 mm 615 665 565 565 665 665
B3 mm 120 120 127 77 127 77
B4 mm 1046 1146 946 946 1146 1146
B5 mm 100 65 115 65 115 65
D mm 300 300 350 350 400 400
D1 mm 250 250 300 300 355 355
W1 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
W2 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
W3 DN DN65 PN16 DN65 PN16 DN80 PN16 DN80 PN16 DN80 PN16 DN80 PN16
G R R 2" R 2" R 2" R 2" DN65 PN16 DN65 PN16
Lieferumfang
Standardausführung
Zubehör
15
Standard Ausführung
Der Lieferumfang eines Heizkessels
enthält die folgenden Komponenten:
Zubehör
Auf Wunsch sind mehrere Optionen /
Zubehör ab Werk möglich.
Fragen Sie Ihren Lieferant nach die
Möglichkeiten.
Komponenten Verpackungsart
Heizkessel vollständig montiert und geprüft 1 Auf Holzpalette mit Holzrahmen, eingewickelt in
PE Folie
Höhenverstellbare Füße 4 In separatem Karton auf dem Kessel
(auf R3407-R3410 bereits am Kessel montiert)
Siphon für Kondensatanschluss 1 In separatem Karton auf dem Kessel
Bedienungs- und Installationsanleitung 1 In Dokumententasche auf der Kesselrückseite
E-Schemata 1 In Dokumententasche auf der Kesselrückseite
Installation
Transport
17
Komponente R3407 R3408 R3409 R3410
Brenner m [kg]
L [mm]
B [mm]
H [mm]
230
1510
1400
600
385
2050
1250
600
390
2050
1350
620
395
2050
1450
620
1. Wärmetauscher m [kg]
L [mm]
B [mm]
H [mm]
200
1510
1425
150
325
2050
1250
150
330
2050
1350
150
335
2050
1450
150
2. Wärmetauscher m [kg]
L [mm]
B [mm]
H [mm]
220
1510
1425
150
365
2050
1250
150
370
2050
1350
150
375
2050
1450
150
Rahmen
m [kg]
L [mm]
B [mm]
H [mm]
80
2010
1466
510
120
2525
1266
515
120
2525
1466
515
120
2525
1466
515
Kondensatwanne m [kg]
L [mm]
B [mm]
H [mm]
< 40
2075
1175
350
< 55
2600
975
350
< 55
2600
1075
350
< 55
2600
1175
350
Installation
Demontage Verkleidung
18
Vor Transport des Kessels die Ab-
deckungen demontieren um Beschädi-
gungen der Kesselverkleidung zu
vermeiden.
Die Demontage der Abdeckungen er-
folgt wie auf den Fotos dargestellt:
1.
3.
5. 4. 2.
5.
4.
Installation
Aufstellung
19
Installation
Der Kessel sollte in einem frostschutz-
sicheren Raum aufgestellt werden.
Wird der Kessel im Dachboden aufge-
stellt, darf dieser nicht der höchste
Punkt der Installation sein.
Bitte beachten Sie die empfohlenen
Abstände gemäss nebenstehender
Skizze beim Aufstellen des Kessels.
Bei kleineren Abständen werden die
Wartungsarbeiten erschwert.
Ist der Kessel richtig positioniert, sollten
die Holzklötze entfernt werden und die
höhenverstellbaren Füße (mit Vibra-
tions-Schalldämpfern ausgestattet)
müssen auf die richtige Höhe einge-
stellt werden. Wasser und Gasan-
schluss sollten nach fixieren der Füße
angeschlossen werden, dies gilt auch
für die exakte Höhe für alle anderen
Anschlüsse.
800
1000
Der R3407- R3410 wird nicht geliefert
auf Holzklötze, sondern auf Räder. Ist
der Kessel richtig positioniert, sollten
die Räder entfernt werden und die hö-
henverstellbaren Füße (mit Vibrations-
Schalldämpfern ausgestattet) müssen
auf die richtige Höhe eingestellt wer-
den. Wasser und Gasanschluss sollten
nach fixieren der Füße angeschlossen
werden, dies gilt auch für die exakte
Höhe für alle anderen Anschlüsse.
Installation
Kesselanschlüsse
Anschlüsse
Nachfolgendes Kapitel beschreibt wie
die verschiedenen Anschlüsse an den
Kessel vorzunehmen sind:
Hydraulische Anschlüsse (1, 3)
Kondensatabfluss Anschluss (7)
Gas Anschluss (6)
Abgas Anschluss (5)
Luftzufuhr Anschluss (nur als raum-
luftunabhängiges Gerät, muss sepa-
rat bestellt werden) (2)
Elektrischer Anschluss (4)

Der Kessel muss so angeschlossen
werden, dass das System den relevan-
ten Normen und Vorschriften
(Europäische, Nationale und Lokale)
entspricht. Es obliegt der installieren-
den Fachkraft dass diese Normen und
Vorschriften eingehalten werden.
Hydraulische Anschlüsse
Der R3400/R3500/R3600 muss so in
das System eingebunden werden, dass
eine dauerhafte Wasserzirkulation
(Zwangsumlauf-prinzip) zu jeder Zeit
gewährleistet ist.
Schließe den Vorlauf (3) und den Rück-
lauf (1) vom System leckfrei an die
entsprechenden Kesselanschlüsse an.
Bei einem hydraulischen System mit 2
Rückläufen (nur R3600 Split System)
ist der “normale” Rücklaufanschluss für
die tiefere Rücklauftemperatur vorgese-
hen, der zusätzliche Rücklaufanschluss
(1) ist für die höhere Rücklauftempera-
tur vorgesehen. (Flanschkappe erst bei
Anschluss entfernen)
Kondensat Anschluss (7)
Nach dem Befüllen mit Wasser, muss
der Siphon (im Lieferumfang enthalten)
unten am Kondensatabflussanschluss
an der Kondensatwanne angebracht
werden.
Der Anschluss an das Abflusssystem
wird immer „offen“ installiert um, im
Falle eines verstopften Abflusssystems,
ein Rückfluten in den Kessel zu vermei-
den .
20
4 5 6
7
1 2 3
Installation
Kesselanschlüsse
Gas Anschluss (6)
Der Gasanschluss erfolgt durch eine
ausgewiesene Fachkraft. Auch hier
gelten die nationalen und lokalen
Normen und Vorschriften.
Schließe die Gasleitung leckfrei an den
Gasanschluss (6) des Kessels an. Es
sollte eine Gasuhr hinter dem Kessel
installiert werden.
Ein Gas Filter kann direkt auf den Gas-
anschluss montiert werden.
Abgas Anschluss (5)
Vorschriften über die Ausführung und
Konstruktion von Abgassystemen sind
von Land zu Land unterschiedlich.
Es ist sicherzustellen, dass alle natio-
nalen Vorschriften bezüglich Abgas-
systeme eingehalten werden.
Beim Abgasanschluss (5) ist darauf zu
achten, dass passende Anschlussstük-
ke verwendet werden.
Es ist nicht notwendig einen separaten
Kondensatabfluss für das Abgassystem
zu installieren, da das Kondensat durch
den Kessel über den Syphon ausge-
spült wird.
Beachten sie folgende Empfehlungen:
Verwenden sie nur korrosionsbestän-
diges Material
Der Durchmesser muss berechnet
und gemäß den nationalen Vorschrif-
ten ausgewählt werden
Das Abgassystem so kurz als möglich
verlegen (Für maximal erlaubte Län-
gen siehe Planer Dokumentation)
Horizontale Abgasleitungen müssen
mindestens 3º Gefälle aufweisen
Zuluft Anschluss (2)
Der Zuluftanschluss kann im Fall einer
raumluftunabhängigen Betriebsweise
angeschlossen werden (wenn das Ge-
rät als raumluftunabhängig besteld wur-
de). Der Durchmesser muss zusam-
men mit dem Abgassystem gemäß den
nationalen Vorschriften berechnet wer-
den. Der Gesamtwiderstand von Zu-
luft– und Abgassystem darf zu keiner
Zeit den max. Förderdruck des Geblä-
ses überschreiten. Bei raumluftabhän-
giger Betriebsweise sollte ein vertikales
Anschlussstück mit Luftöffnung ober-
halb des
Kessels an die Zuluftöffnung ange-
schlossen werden.
Elektrischer Anschluss (4)
Die elektrischen Anschlüsse müssen
durch eine autorisierte Elektrofachkraft
ausgeführt werden in Übereinstimmung
mit den geltenden nationalen und loka-
len Normen und Vorschriften.
Für die Spannungsversorgung ist ein
isolierter Hauptschalter, mit minde-
stens 3mm Kontaktöffnungen, zu ver-
wenden. Dieser wird innerhalb des
Kesselraumes montiert. Der Haupt-
schalter dient für die Abschaltung der
Spannungsversorgung bei Wartungsar-
beiten.
Alle Kabel werden durch die Kabelka-
nalen und Einführungsbuchsen auf der
Rückseite des Schaltfelds in der Front
des Kessels geführt.
Bei den elektrischen Anschlussarbeiten
ist das Elektroschema zu beachten.
Dieses ist Bestandteil der Technischen
Dokumentation.
6
2
5
21
4
4
Inbetriebnahme
Wasser– und Hydrauliksystem
Wasserqualität
Das System ist mit Wasser mit einem
pH-Wert zwischen 8,0 und 9,5 zu befül-
len. Der Chloridwert des Wassers darf
50 mg/l nicht überschreiten. Der Eintritt
von Sauerstoff durch Diffusion muss in
jedem Fall vermieden werden. Schäden
am Wärmetauscher durch eindringen-
den Sauerstoff fallen nicht unter die
Garantie.
Bei Systemen mit größeren Wasser-
mengen ist es notwendig, den Höchst-
füllstand und die zusätzlichen Mengen
mit entsprechender Härte gemäß der
deutschen Norm VDI2035 zu beachten.
In nebenstehender Tabelle sind die
Nennwerte für die Befüllung und zu-
sätzliches Wasser für den R3400/
R3500/R3600 gemäß der VDI2035
angegeben.
In der nebenstehender Tabelle sind
Angaben zum Verhältnis zwischen der
Wasserqualität und dem Höchstfüll-
stand für Wasser während der Stand-
zeit des Kessels enthalten. Bitte schla-
gen Sie im Originaltext der VDI2035 für
genauere Informationen nach.
Mindestbetriebs-
druck
[bar]
Vorlauf-
temperatur
[ºC]
> 1.5 90
> 1.0 80
Wasserdruck
Öffnen Sie die Ventile zum System.
Prüfen Sie den Wasserdruck im Sy-
stem. Wenn der Wasserdruck zu nied-
rig
ist (siehe unten stehende Tabelle), er-
höhen Sie den Druck mindestens auf
den Mindestwasserdruck laut Tabelle.
Die Befüllung erfolgt über das Füll- und
Ablassventil (2) am Rücklaufanschluss
Hydrauliksystem
Prüfen Sie, ob der Kessel hydraulisch
so an das System angeschlossen ist,
dass der Wasserdurchsatz jederzeit bei
Brennerbetrieb gesichert ist. Der Was-
serdurchsatz wird über den Strömungs-
wächter im Kessel überwacht. Ein zu
niedriger Durchsatz führt dazu, dass
der Brenner sofort stoppt und der Kes-
sel abschaltet.
Der Kessel wird ausschließlich von
befugtem Personal in Betrieb genom-
men. Die Garantie erlischt bei Nichtein-
haltung dieser Bedingung. Zur Inbe-
triebnahme ist ein Protokoll auszufül-
len.
In diesem Kapitel wird die Inbetriebnah-
me des Kessels mit einer Standardkes-
selsteuerung beschrieben. Sollte eine
zweite Systemsteuerung installiert sein,
beachten Sie bitte das entsprechende
Handbuch zur Inbetriebnahme des
Kessels.
Kesselleistung
[kW]
Max. Summe Erdalkali
[mol/m3]
Max. Härte gesamt
[dºH]
600 - 2000 1.5 8.4
Konzentrat
Ca(HCO3)2
Kapazität der Anlage Q (kW)
600 800 1000 1200 1400 1600 1800
mol/
m3
dºH Max. (Nach-) Füllmenge Wasser Vmax [m3]
0.5 2.8 - - - 75.1 87.6 100.2 122.7
1.0 5.6 - - - 37.6 43.8 50.1 56.3
1.5 8.4 12.0
16.7 20.9 25.0 29.2 33.4 37.6
2.0 11.2 9.4
12.5 15.7 18.8 21.9 25.0 28.2
2.5 14.0 7.5
10.0 12.5 15.0 17.5 20.0 22.5
3.0 16.8 6.3 8.3 10.4 12.5 14.6 16.7 18.8
2000
125.2
62.6
41.7
31.3
25.0
20.9
22
1
2
Inbetriebnahme
Gasversorgung
Kondensatanschluss
Abgas- und Zuluftanschlüsse
23
Gasversorgung
Prüfen Sie den Anschluss zur Gasver-
sorgung zum Kessel auf Dichtheit. Evtl.
Lecks sind abzudichten, bevor der Kes-
sel gestartet wird.
Entlüften Sie Gasleitung und Gasventil.
Dies erfolgt an der Messstelle (1) am
Gasdruckwächter.
Die Messstelle anschließend wieder
schließen.
Fragen Sie Gastyp und Werte beim
Gasversorger vor Ort nach, um zu ge-
währleisten, dass der Kessel mit der
korrekten Gasart betrieben wird.
Kondensatanschluss
Entfernen Sie den Siphon (2) vom Kon-
densatanschluss. Befüllen Sie diesen
mit Wasser und setzen Sie ihn wieder
in der ursprünglichen Position ein. Stel-
len Sie vor Anlaufen des Kessels si-
cher, dass der Siphon gefüllt ist, um ein
Austreten von Abgasen aus dem Kon-
densatanschluss zu verhindern.
Abgas- und Zuluftanschlüsse
Prüfen Sie, ob die Anschlüsse für Ab-
gas und Zuluft den inländischen und
regionalen Vorschriften entsprechen.
Anlagen, die die Vorschriften nicht er-
füllen, dürfen nicht in Betrieb genom-
men werden.
Stellen Sie sicher, dass alle Anschlüsse
frei sind.
Die Abgas- und Zuluftanschlüsse dür-
fen nicht verkleinert werden.
2
1
Inbetriebnahme
Vorbereitung für 1. Inbetriebnahme
24
Vorbereitung für 1. Inbetriebnahme
Öffnen Sie den Gasanschluss;
Betätigen Sie den Netztrennschalter,
um den Kessel mit Strom zu versor-
gen;
Schalten Sie den Kessel mit dem Ein-
/Ausschalter (1) ein;
Stellen Sie sicher, dass der Kessel im
Standby-Betrieb (K) (2) bleibt, betäti-
gen Sie den Drehschalter (3);
Prüfen Sie die Pumpenfunktion: Stel-
len Sie sicher, dass die Drehrichtung
korrekt ist;
Lassen Sie alle Luft aus der Pumpe
ab, indem Sie die Verschlusskappe
am Pumpenmotorgehäuse entfernen.
Es wird empfohlen, den Kessel nach
der 1. Inbetriebnahme unter einer Aus-
lastung von 50 % zu betreiben, da die
Verbrennungsanalyse so am einfach-
sten initiiert werden kann. Dies kann
wie folgt sichergestellt werden:
Öffnen Sie den Deckel der Kessel-
steuerung;
Gehen Sie mit dem Drehschalter (3)
zu Parameter P9 im Menü;
Ändern Sie den P9 (5) auf 50 %
(Programmtaste drücken (4), Wert
mittels Drehschalter ändern (3), zur
Bestätigung Programmtaste (4) drük-
ken);
Schließen Sie den Deckel der Kessel-
steuerung.
2
3
3
4
5
1
Inbetriebnahme
Verbrennungswerte
25
Verbrennungswerte bei Volllast
Starten Sie den Kessel im Wartungsbe-
trieb unter Volllast (W2). Wenn Sie den
P9 auf 50 % gesenkt haben (siehe vor-
gehendes Kapitel), arbeitet der Kessel
unter einer Auslastung von 50 %. War-
ten Sie drei Minuten, sodass der Kessel
die Verbrennung stabilisieren kann.
Erhöhen Sie den P9 anschließend
schrittweise auf 100 %. Prüfen Sie den
Gasdruck am Zulauf des Gasventils,
während Sie die Kessellast steigern:
Der Gasdruck darf nicht unter den er-
forderlichen Mindestwert fallen 
siehe technische Daten. Setzen Sie
den Mindestgasdruckschalter (1) auf
50 % des erforderlichen Gasdrucks.
Prüfen Sie die Verbrennungseinstellun-
gen vom Zündbrenner an der Messstel-
le an der hintere Seite des Kessels (3).
Korrigieren Sie die Einstellungen ggf.
mit der Einstellschraube am Zündgas-
ventil (2)
Prüfen Sie die Verbrennungseinstellun-
gen vom Hauptbrenner an der Mess-
stelle im Kamin (4). Korrigieren Sie die
Einstellungen ggf. mit der V- Einstell-
schraube am Hauptgasventil (5).
Verbrennungswerte bei Min-Last
Schalten Sie den Kessel in Wartungs-
betrieb unter Mindestlast (W1). Prüfen
Sie die Verbrennungseinstellungen für
beide Brenner auf die gleiche Weise
wie bei Volllast. Korrigieren Sie die
Einstellungen vom Zündbrenner ggf.
mittels der Einstellschraube am
Zündgasventil (6). Korrigieren Sie die
Einstellungen vom Hauptbrenner ggf.
mit der Einstellschraube am Hauptgas-
ventil (7).
Verbrennungswerte bei Teillast
Wir empfehlen eine zusätzliche Refe-
renzprüfung der Verbrennungswerte
bei 50 % Auslastung, um sicherzustel-
len, dass das Gasventil so eingestellt
ist, dass das Regelverhalten normal ist.
Der CO2-Wert sollte zwischen den Ein-
stellungen bei Volllast und Mindestlast
liegen. Der CO-Wert sollte den Volllast-
und Mindestlastwerten entsprechen.
Stellen Sie sicher, dass Parameter P9
wieder auf 100 gestellt ist, und schalten
den Kessel nach Abschluss des Ver-
brennungstests in Automatikbetrieb
(F).
1
Verbrennungseinstellungen für
Erdgas G20 / G25
Alle ketels
CO2, max % 10.0 ± 0.2
COmax ppm < 1000
Zündbrenner
CO2, min % 10.2 ± 0.2
COmin ppm < 1000
Verbrennungseinstellungen für
Flüssiggas G31
Alle ketels
CO2, max % 11.0 ± 0.2
COmax ppm < 1000
CO2, min % 11.2 ± 0.2
COmin ppm < 1000
Zündbrenner
Parameteränderung erforderlich
P19 : 100% 86%
Verbrennungseinstellungen für
Erdgas G20 / G25
Alle ketels
CO2, max % 10.0 ± 0.2
COmax ppm < 30
Hauptbrenner
CO2, min % 9.3 ± 0.2
COmin ppm < 30
Verbrennungseinstellungen für
Flüssiggas G31
Alle ketels
CO2, max % 11.0 ± 0.2
COmax ppm < 30
CO2, min % 11.0 ± 0.2
COmin ppm < 30
Hauptbrenner
Parameteränderung erforderlich
P19 : 100% 86%
2
6
5 7
4
3
Inbetriebnahme
Luftdruckwächter
26
Einstellung Luftdruckwächter
Schliessen sie ein Differenzdruck-
Messgerät an auf die Messstellen des
Wächters (1). Schalten Sie den Kessel
in Wartungsbetrieb unter Mindestlast
(W1). Messen Sie den Differenzdruck
über den Wächter, dieser soll 0.8
mbar sein. Drehen Sie den Knopf am
Wächter (2) gegen den Uhrzeigersinn
bis zum Ende. Reduzieren Sie die Ein-
stellung auf Parameter P17 schrittweise
bis der Differenzdruck 0.4 mbar ist.
Drehen sie jetzt den Knopf am Wächter
langsam im Uhrzeigersinn bis der Kes-
sel auf Störung geht. Stellen Sie P17
wieder auf den orignalen Wert ein!!
Resettieren Sie die Störung. Schalten
Sie den Kessel wieder ein und kont-
rolieren Sie ob das Kontakt vom Wäch-
ter bei 0.4 mbar schliesst (Anzeige bei
DW im Display des Kesselreglers) (3).
Wenn notwendig, wiederholen Sie das
Verfahren.
1
2
3
Inbetriebnahme
Funktion der Sicherheitseinrichtungen prüfen
Gasdichtheitsprüfung
Kessel außer Betrieb setzen
28
Funktion der Sicherheitseinrichtun-
gen prüfen
Alle Sicherheitseinrichtungen sind auf
korrekte Funktion zu prüfen. Zu den
Sicherheitseinrichtungen an Standard-
kesseln zählen ein Vorlauftemperatur-
fühler, ein Strömungswächter, ein Min-
destgasdruckschalter und eine Ionisati-
onselektrode. Diese Vorrichtungen kön-
nen wie unten beschrieben geprüft wer-
den.
R600 Kesseltemperatursensor (1)
Nehmen Sie den Stopfen vom Sensor,
während der Kessel eingeschaltet ist.
Dies sollte zu einer Abschaltung Nr. 12
führen. Das System sollte die Abschal-
tung rückgängig machen, sobald der
Stopfen wieder eingesetzt wird.
Der Kessel läuft anschließend wieder
an.
Strömungswächter (2)
Schließen Sie das Ventil am Durchsatz-
anschluss zum System (langsam!),
während der Kessel unter Mindestlast
arbeitet. Wenn das Ventil fast geschlos-
sen ist und der Wasserdurchsatz unzu-
reichend ist, schaltet der Wasserdurch-
satzschalter wie auch der Kessel ab
(Abschaltung 40).
Öffnen Sie das Ventil. In diesem Fall
muss das System manuell zurückge-
setzt werden.
Mindestgasdruckwächter (4)
Schließen Sie den Gashahn, wenn der
Kessel in Standby ist (K). Öffnen Sie
langsam an der Messstelle (4) auf dem
Gasventil und messen gleichzeitig den
Gasdruck an der Messstelle des
Gasdruckschalters (5). Der Kessel
schaltet ab (Nr. 2), wenn der Abschalt-
wert erreicht wurde. Schließen Sie
beide Messstellen und öffnen Sie den
Gashahn.
Ionisationselektrode (6)
Entfernen Sie die elektrische Steckver-
bindung von der Ionisationselektrode,
während der Kessel läuft. Der Kessel
schaltet ab (Nr. 5).
Der Kessel versucht, wieder anzufah-
ren. Da die elektrische Steckverbin-
dung entfernt wurde, führt dieser Neu-
start zur Abschaltung Nr. 4.
Wenn die elektrische Verbindung wie-
der aufgesetzt wurde, ist der Neustart
erfolgreich.
Der Ionisationsstrom kann gemessen
werden, indem Sie ein Multifunktions-
messgerät (auf µA eingestellt) zwi-
schen der Ionisationselektrode und der
elektrischen Steckverbindung einbau-
en. Der Ionisationsstrom sollte immer
über 1,2 µA liegen, unter normalen
Bedingungen liegt dieser bei 6 µA und
höher.
Gasdichtheitsprüfung
Prüfen Sie alle Dichtverbindungen für
Gas mittels eines zugelassen Seifen-
oder elektronischen Gasanalysegeräts
auf Dichtheit, zum Beispiel:
Messstellen;
Anschlussverschraubungen;
Dichtringe am Mischsystem, usw.
Kessel außer Betrieb setzen
Wenn der Kessel für längere Zeit nicht
betrieben werden soll, setzen Sie den
Kessel in den folgenden Schritten au-
ßer Betrieb:
Schalten Sie den Kessel auf Standby-
Betrieb (K);
Schalten Sie den Kessel über den Ein
-/Ausschalter ab (7);
Unterbrechen Sie die Stromversor-
gung zum Kessel, indem Sie den
Haupttrennschalter im Kesselraum
betätigen;
Unterbrechen Sie die Gasversorgung
zum Kessel.
7
1 2
6
5
4
3
Inbetriebnahme
Inbetriebnahme-Protokoll
29
Inbetriebnahme-Protokoll R3400/R3500/R3600
Projekt
Kesseltyp Projekt
Seriennummer Adresse
Jahr Ort
Nennwärmebelastung (Hi) [kW] Datum
Nennwärmeleistung (Hi) [kW] Ingenieur
System
Wasserdruck [bar] Anlage: Dachgeschoss
Wasser pH [-] Erdgeschoss
Wasserhärte [dºH] Keller
Wasserchlorid [mg/l] Andere: .........................
Wasser-T Volllast [ºC] Hydraulik: Weiche
Wasser-pKessel [kPa] Beschichteter Wärmetauscher
Wasserdurchsatz [m3/h] Bypasskessel
Pumpeneinstellung [-] Andere: .........................
Sicherheitseinrichtungen
STB [ºC] Vorlauffühler geprüft
STW [ºC] Strömungswächter geprüft
Min.-Gasdruckschalter Einstell. [mbar]
Zündzeit Brenner [sec]
Verbrennungsanalyse
100% Last 50% Last Min. Last
Gasverbrauch [m3/h] [m3/h] [m3/h]
Gasdruck [mbar] [mbar] [mbar]
CO2 Zündbrenner [%] [%] [%]
O2 Zündbrenner [%] [%] [%]
CO Zündbrenner [ppm] [ppm] [ppm]
NOx Zündbrenner [ppm] [ppm] [ppm]
Tatmosphärisch [ºC] [ºC] [ºC]
TAbgas [ºC] [ºC] [ºC]
TVorlauf [ºC] [ºC] [ºC]
TRücklauf [ºC] [ºC] [ºC]
Ionisationsstrom [µA] [µA] [µA]
pVentilator [mbar] [mbar] [mbar]
pTopplatte [mbar] [mbar] [mbar]
pVerbrennungskammer [mbar] [mbar] [mbar]
Parametereinstellungen
P12 Kesselhysterese [ºC]
P2 Sollwerttemperatur Brauchwasser [ºC] P17 Gebläsedrehzahl Min.-Last [%]
P11 Max. Sollwerttemperatur Kessel [ºC] P19 Gebläsedrehzahl 100% Last [%]
Anmerkungen
P1 Sollwerttemperatur Heizung [ºC]
CO2 Hauptbrenner [%] [%] [%]
O2 Hauptbrenner [%] [%] [%]
CO Hauptbrenner [ppm] [ppm] [ppm]
NOx Hauptbrenner [ppm] [ppm] [ppm]
Bedienungs- und Parametereinstellungen
Hauptmenü (Bedienungsmenü)
Parametermenü (Information/Programmier Menü)
Parametereinstellungen verändern
30
Der Feuerungsmanager hat zwei Menüs: das Hauptmenü (Bedienungsmenü) [bei geschlossenem Deckel], und das Parame-
ter Menü (Information/Programmier Menü) [bei offenem Deckel]. Beide Menü - Einstellungsmöglichkeiten sind auf den näch-
sten Seiten aufgeführt.
Hauptmenü (Bedienungsmenü) Deckel geschlossen
Die Betriebsart (2) des Kessels wird bei geschlossenem Deckel und durch Betäti-
gen des Drehschalters (1) im und entgegen den Uhrzeigersinn eingestellt.
Verfügbare Betriebsarten sind:
K Standby-Betrieb (nur Frostschutz)
F Automatik-Betrieb (Heizung und Brauchwasser)
F Sommer-Betrieb (nur DHW, keine Heizung)
W1 Servicebetrieb Mindestlast
W2 Servicebetrieb Volllast (begrenzt durch P9)
Neben der Betriebsart wird in der Anzeige auch die tatsächliche Vorlauftemperatur
(3) und, im Fall einer Abschaltung, ein Warndreieck (4) zusammen mit dem Stö-
rungscode (5) angegeben.
Erläuterungen zu den Störungscodes finden Sie im Kapitel „Störungen“.
Parametermenü (Information/Programmier Menü) Deckel offen
Bestimmte Werte/Parameter können an der Kesselsteuerung bei offenem Deckel
und durch Betätigen des Drehschalters (1) im und entgegen den Uhrzeigersinn
abgelesen/geändert werden. Ein Pfeil im unteren Bereich der Anzeige (2) gibt an,
welcher Parameter ausgewählt wurde. Verfügbare Werte/Parameter sind:
P1 Istwert/Sollwert Vorlauftemperatur [ºC]
P2 Istwert/Sollwert Brauchwassertemperatur [ºC]
P3 Ist-Temperatur/Leistungssollwert für Kessel [ºC]*
P4 --
P5 Ist-Außentemperatur [ºC] (bei angeschlossenem Fühler)
P6 Ist-Abgastemperatur [ºC]
P7 --
P8 Ist-Weichetemperatur [ºC] (bei angeschlossenem Fühler)
P9 Ist-/Max. Kesselleistung [%]
P10 Passwort für Fachkraftebene
Drehen Sie den Drehschalter im Uhr-
zeigersinn, bis der Pfeil auf Parame-
ter P2 steht;
Drücken Sie zum Einstellen die Taste
Zurücksetzen/Programmierung (die
LED leuchtet auf);
Drehen Sie den Drehschalter, bis der
gewünschte Brauchwasser-Sollwert
erreicht ist;
Hinter dem Deckel befindet sich eine
optische Schnittstelle (6), ein Taster
zum Zurücksetzen/Programmieren (7)
und eine Alarm-/Programm-LED (8).
Neben den Parameter-Werten/-Ein-
stellungen kommen weitere Informatio-
nen in Bezug auf Eingänge und Aus-
gänge zum und vom Kessel zur Anzei-
ge:
Ausgangssymbole
Spannung zum Hauptgasventil
Spannung zum Zündtransformator
Signal Gebläsefreigabe
Z Spannung zur Kesselhauptpumpe
F Spannung zu DHW-Pumpe / Um-
schalterventil
Eingangssymbole
H Flammenionisation erkannt
SW Wasserdurchsatzschalter aktiv
DW Luftdruckwächter aktiv
RT Kesselfreigabe
(Raumthermostat)**
Bus Buskommunikation aktiv
Verändern von Parameter Einstellun-
gen
Gehen Sie wie folgt vor, um Parameter
zu ändern (im Beispiel Parameter P2
(Brauchwasser-Sollwert)):
Öffnen Sie den Deckel (der Pfeil im
unteren Bereich der Anzeige zeigt
den Parameter P1 an);
Drücken Sie die Taste Zurücksetzen/
Programmierung zum Bestätigen (die
LED erlischt);
Schließen Sie den Deckel.
Der neue Wert ist jetzt aktiviert. Alle
Parameter können nach der oben ge-
nannten Vorgehensweise geändert
werden.
**Das Signal „Kesselfreigabe“ ist bei Standardlieferung mit einer Brücke ausgestattet, sodass der Kessel gewöhnlich aktiviert ist. Wenn ein
Gebäudeleitsystem zur Meldung des Aktivierungssignals an den Kessel angeschlossen ist, (Brücke muss entfernt werden)
prüfen Sie das Gebäudeleitsystem, wenn der Kessel nicht aktiviert wird.
* P3 zeigt den tatsächlichen Temperatursollwert des Kessels an, der entweder vom P1/P2 oder von einer weiteren (Wetterausgleich) Steue-
rung oder einem Gebäudeleitsystem (2-10V) gemeldet wird. Wenn die Kesselkapazität über einen Kaskadenmanager oder ein Gebäudeleit-
system (2-10V) gesteuert wird, zeigt P3 den tatsächlichen Leistungssollwert des Kessels an.
2 5 3 4 1
2 1
6 7 8
Wartung
Checkliste
Ersetzen der Elektroden
31
Der Kessel darf nur von befugtem Per-
sonal gewartet werden.
Um den korrekten und sicheren Betrieb
des Kessels sicherzustellen, sollte die-
ser mindestens einmal jährlich über-
prüft werden. Dazu ist ein Wartungs-
protokoll auszufüllen (siehe Ende die-
ses Kapitels für ein Beispiel eines War-
tungsprotokolls).
Checkliste
Folgenden Maßnahmen sind durchzu-
führen:
Austausch der Zünd- und Ionisations-
elektroden;
Reinigung der Kondensatwanne;
Reinigung und Befüllung des
Siphons;
des Wasserdrucks im System;
Prüfung der Wasserqualität des Sy-
stemwassers sowie des eingeleiteten
Wassers;
Ersetzen der Elektroden
Die Elektroden befinden sich an der
rechten Kesselseite. Tauschen Sie die
Zündelektrode (1) und die Ionisations-
elektroden (2) wie in den Abbildungen
dargestellt aus
Prüfung des Wasserdurchsatzes
durch den Kessel;
Prüfung/Korrektur der Verbrennungs-
werte bei Volllast und Mindestlast mit
einem Verbrennungsanalysegerät;
Prüfung des Gasdrucks zum Kessel;
Prüfung der Dichtverbindungen und
Messstellen auf Dichtheit;
Prüfung der Funktionsfähigkeit aller
Sicherheitseinrichtungen;
Ausfüllen des Wartungsprotokolls.
2
1
Wartung
Wartungs-Protokoll
33
Wartungs-Protokoll R3400/R3500/R3600
Projekt
Kesseltyp Projekt
Seriennummer Adresse
Jahr Ort
Nennwärmebelastung (Hi) [kW] Datum
Nennwärmeleistung (Hi) [kW] Ingenieur
System
Wasserdruck [bar] Anlage: Dachgeschoss
Wasser pH [-] Erdgeschoss
Wasserhärte [dºH] Keller
Wasserchlorid [mg/l] Andere: .........................
Wasser-T Volllast [ºC] Hydraulik: Weiche
Wasser-pKessel [kPa] Beschichteter Wärmetauscher
Wasserdurchsatz [m3/h] Bypasskessel
Pumpeneinstellung [-] Andere: .........................
Sicherheitseinrichtungen
STB [ºC] Vorlauffühler geprüft
STW [ºC] Strömungswächter geprüft
Min.-Gasdruckschalter Einstell. [mbar]
Zündzeit Brenner [sec]
Verbrennungsanalyse
100% Last 50% Last Min. Last
Gasverbrauch [m3/h] [m3/h] [m3/h]
Gasdruck [mbar] [mbar] [mbar]
CO2 Zündbrenner [%] [%] [%]
O2 Zündbrenner [%] [%] [%]
CO Zündbrenner [ppm] [ppm] [ppm]
NOx Zündbrenner [ppm] [ppm] [ppm]
Tatmosphärisch [ºC] [ºC] [ºC]
TAbgas [ºC] [ºC] [ºC]
TVorlauf [ºC] [ºC] [ºC]
TRücklauf [ºC] [ºC] [ºC]
Ionisationsstrom [µA] [µA] [µA]
pVentilator [mbar] [mbar] [mbar]
pTopplatte [mbar] [mbar] [mbar]
pVerbrennungskammer [mbar] [mbar] [mbar]
Parametereinstellungen
P12 Kesselhysterese [ºC]
P2 Sollwerttemperatur Brauchwasser [ºC] P17 Gebläsedrehzahl Min.-Last [%]
P11 Max. Sollwerttemperatur Kessel [ºC] P19 Gebläsedrehzahl 100% Last [%]
Anmerkungen
P1 Sollwerttemperatur Heizung [ºC]
CO2 Hauptbrenner [%] [%] [%]
O2 Hauptbrenner [%] [%] [%]
CO Hauptbrenner [ppm] [ppm] [ppm]
NOx Hauptbrenner [ppm] [ppm] [ppm]
34
Im Falle einer Abschaltung erscheint ein Warnzeichen (E) und ein blinkender Fehlercode auf dem Display. Die Störungsursa-
che muss behoben werden, bevor man den Kessel R600 zurücksetzen kann. Im Fall, dass die Abschaltung mehr als 2 x in-
nerhalb von 6 Minuten erscheint oder länger als 6 Minuten ansteht, wird dem Fehlercode das Zeichen “3” zugefügt. Die beige-
fügte Liste zeigt mögliche Abschaltungen mit Hinweisen auf die Störungsursache.
Nr. Fehler Beschreibung des Fehlers Mögliche Lösung
1 Verriegelnd Vorlauftemperatur übersteigt STB-Einstellung
(100ºC).
Prüfen Sie, ob der Kessel in Automatik-Betrieb läuft
(K). Prüfen Sie, ob der Wasserdurchsatz durch den
Kessel ausreichend ist, prüfen Sie, ob (P11+P12) <
Höchstwert (V9).
2 Blockierend Gasdruck ist unter Mindestwert für Mindest-
gasdruckschalter gefallen oder zusätzliche
Sicherheitseinrichtung zur Verriegelung wurde
unterbrochen (beim Anlaufen).
Prüfen Sie den Gasversorgungsdruck/prüfen Sie die
Funktionsfähigkeit der zusätzlichen Sicherheitseinrich-
tung am Verriegelungseingang.
3 Blockierend
Gasdruck ist unter Mindestwert für Mindest-
gasdruckschalter gefallen oder zusätzliche
Sicherheitseinrichtung zur Verriegelung wurde
unterbrochen (beim Betrieb).
Prüfen Sie den Gasversorgungsdruck/prüfen Sie die
Funktionsfähigkeit der zusätzlichen Sicherheitseinrich-
tung am Verriegelungseingang.
4 Verriegelnd
Während Brennerstart kein Flammenionisati-
onssignal erkannt.
Prüfen Sie den Phasen-/Nullleiter der Stromversor-
gung (Phasesensitivität!), prüfen Sie die Gasversor-
gung, prüfen Sie den Zündfunken, erhöhen Sie die
Gasdruckmindestlast (Inbusschraube).
5 Verriegelnd Flammenionisationssignal während Betrieb
ausgefallen.
Prüfen Sie den Gasversorgungsdruck während des
Betriebs, prüfen Sie die Gasventileinstellungen mittels
Verbrennungsanalyse.
6 Blockierend
Vorlauftemperatur übersteigt STW-Einstellung
(97ºC).
Prüfen Sie, ob der Kessel im Automatik-Betrieb läuft
(F). Prüfen Sie, ob der Wasserdurchsatz durch den
Kessel ausreichend ist, prüfen Sie, ob (P11+P12) <
Temp.-Grenzwert (V10).
7 Verriegelnd
Externe Sicherheit angeschlossen am Verrie-
gelender Eingang ist unterbrochen.
Prüfen Sie die angeschlossene externe Sicherheitsge-
räte (Wasserdruckschalter, Ext. STB., usw.)
11 Verriegelnd
Flammenionisationssignal vor Brennerstart
erkannt.
Prüfen Sie die Ionisationselektrode, messen Sie den
Ionisationsstrom, wenn der Kessel abgeschaltet ist,
prüfen Sie die Verkabelung zwischen Ionisationselek-
trode und Kesselsteuerung.
12 Blockierend
Vorlauffühler ist defekt Prüfen Sie den Fühlerwiderstand (siehe Kapitel
„Fühlerwerte“), prüfen Sie die Verkabelung zwischen
Vorlauffühler und Kesselsteuerung.
14 Blockierend
Brauchwasserfühler (optional) ist defekt Prüfen Sie den Fühlerwiderstand (siehe Kapitel
„Fühlerwerte“), prüfen Sie die Verkabelung zwischen
Brauchwasserfühler und Kesselsteuerung.
15 Blockierend
Außenfühler (optional) ist defekt Prüfen Sie den Fühlerwiderstand (siehe Kapitel
„Fühlerwerte“), prüfen Sie die Verkabelung zwischen
Außenfühler und Kesselsteuerung.
18 Blockierend
Weichefühler (optional) ist defekt Prüfen Sie den Fühlerwiderstand (siehe Kapitel
„Fühlerwerte“), prüfen Sie die Verkabelung zwischen
Weichefühler und Kesselsteuerung.
Störungen
35
Nr. Fehler Beschreibung des Fehlers Mögliche Lösung
20 Verriegelnd Fehler Gasventil V1, Flammenionisationssignal
für mehr als 5 Sekunden nach Brennerstopp
erkannt.
Prüfen Sie die Schließposition von Ventil V1 innerhalb
des Kombi-Gasventils, ersetze Gasventil.
21 Verriegelnd Fehler Gasventil V2, Flammenionisationssignal
für mehr als 5 Sekunden nach Brennerstopp
erkannt.
Prüfen Sie die Schließposition von Ventil V2 innerhalb
des Kombi-Gasventils, ersetze Gasventil.
22 Verriegelnd Luftdruckwächter schaltet nicht während das
Vorspülen.
Prüfen Sie die Einstellung vom LDW, prüfen Sie ob
das Gebläse anlauft.
23 Verriegelnd Lufdruckwächter öffnet niet nach abschalten
vom Gebläse.
Prüfen Sie die Einstellung vom LDW.
27 Verriegelnd Luftdruckwächter schaltet ab während Betrieb. Prüfen Sie die Einstellung vom LDW.
30 Verriegelnd CRC-Fehler bei Steuerungssystemparametern
(P11-P40).
Prüfen Sie die Parametereinstellungen für P11-P40,
ändern Sie den Wert eines Parameters bei P11-P40
(Abschaltung wird aufgehoben), setzen Sie alle Para-
meter auf die Ausgangswerte zurück.
31 Verriegelnd CRC-Fehler bei Kesselsicherheitsparametern
(V1-V16).
Prüfen Sie die Parametereinstellungen für V1-V16,
ändern Sie den Wert eines Parameters bei V1-V16
(Abschaltung wird aufgehoben), setzen Sie alle Para-
meter auf die Ausgangswerte zurück.
32 Blockierend Versorgungsspannung zur Kesselsteuerung ist
zu niedrig.
Prüfen Sie die Sicherung an der Kesselsteuerung,
prüfen Sie die Stromversorgung zur Kesselsteuerung.
40 Verriegelnd Strömungswächter bei aktivierter Pumpe unter-
brochen.
Prüfen Sie die Pumpenfunktion, prüfen Sie den Was-
serdurchsatz durch den Kessel, prüfen Sie die Funkti-
onsfähigkeit des Wasserdurchsatzschalters.
x.y. Verriegelnd (alle nicht oben aufgeführten Abschaltcodes)
Interne Abschaltung der Kesselsteuerung.
Drücken Sie Reset (Zurücksetzen). Tauschen Sie die
Kesselsteuerung aus, wenn die Abschaltung nicht be-
hoben werden kann oder der Kessel zu häufig ab-
schaltet.
Störungen
Fühlerkennwerte
36
In den nebenstehenden Diagrammen
sind die Sensorwerte für alle Kes-
selsensoren und in den Zubehörsätzen
enthaltenen, optionalen Sensoren an-
gegeben. Die Diagramme zeigen
Durchschnittswerte, da alle Sensoren
Schwankungen unterliegen.
Bei der Messung der Widerstandswerte
sollte der Kessel immer abgeschaltet
sein. Nehmen Sie die Messungen nahe
dem Sensor vor, um Abweichungen bei
den Werten zu vermeiden
Vorlauftemperatur– und Abgastemperaturfühler (5k NTC)
Brauchwasser-, Außen- und Sammlertemperaturfühler (1k PTC)
Konformitätserklärung
Konformitätserklärung
Rendamax BV, Hamstraat 76, 6465 AG Kerkrade (NL),
erklärt, dass die Produkte
R3400/3500/3600
mit folgenden Normen übereinstimmen:
EN 656
EN 15417
EN 13836
EN 55014-1 / -2
EN 61000-3-2 /-3
EN 60 335-1/ -2
Gemäß den Bestimmungen der Richtlinien:
92 / 42 / EWG (Wirkungsgrade von Heizkesseln)
90 / 396 / EWG (Gasverbrauchseinrichtungen)
73 / 23 / EWG (Niederspannungsrichtlinie)
89 / 336 / EWB (EMV-Richtlinie)
wirden diese Produkte wie folgt gekennzeichnet:
CE – 0063AR3514
Kerkrade, 10-06-2013
A.J.G. Schuiling
Plant Manager
37


Specyfikacje produktu

Marka: Elco
Kategoria: kocioł centralnego ogrzewania
Model: R3500

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Elco R3500, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje kocioł centralnego ogrzewania Elco

Elco

Elco LMS R600 Instrukcja

29 Sierpnia 2024
Elco

Elco R3600 Instrukcja

29 Sierpnia 2024
Elco

Elco Trigon L Instrukcja

24 Sierpnia 2024
Elco

Elco Thison L Evo Instrukcja

18 Sierpnia 2024
Elco

Elco Thision Mini Instrukcja

15 Sierpnia 2024
Elco

Elco Thision S Instrukcja

13 Sierpnia 2024
Elco

Elco R600 Instrukcja

9 Sierpnia 2024

Instrukcje kocioł centralnego ogrzewania

Najnowsze instrukcje dla kocioł centralnego ogrzewania