Instrukcja obsługi CyberPower Smart App OL3000RMXL2U

CyberPower UPS Smart App OL3000RMXL2U

Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla CyberPower Smart App OL3000RMXL2U (42 stron) w kategorii UPS. Ta instrukcja była pomocna dla 12 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/42
OL1000RMXL2U
OL1500RMXL2U
OL2000RMXL2U
OL3000RMXL2U
Paragon
Series
User Manual
Pr
eface
About this Manual
Thank you
for purchasing
a CyberPower Systems product to protect
your electrical equipment.
The
Paragon
series has been designed with
the
utmost care.
We
recommend that
you take the time
to read this manual to take full
advantage
of your UPS’s many features.
The
Paragon
UPS and
the optional battery packs
that
are
covered in
this
manual are listed
below:
-
UPS OL1000RMXL2U
(1000VA/700W).
-
UPS OL1500RMXL2U
(1500VA/1050W).
-
UPS OL2000RMXL2U
(2000VA/1400W).
-
UPS OL3000RMXL2U
(3000VA/2100W).
-
ABP36VRM-2U (36Vdc, 7Ah, for OL1000RMXL2U and
OL1500RMXL2U).
-
ABP72VRM-2U (72Vdc, 9Ah, for OL2000RMXL2U and
OL3000RMXL2U).
To learn
more about our entire line of CyberPower
Systems
products
and
the options available for the
Paragon
series, visit our web site at
www.cyberpowersystems.com
or contact your local CyberPower
Systems representative.
FCC Notice
This
equipment
has
been tested and
found
to comply with the limits
for a Class B digital
device,
pursuant to part 15 of the FCC
rules.
These limits are designed
to
provide reasonable
protection against
harmful interference in a residential
installation. This equipment
generates, uses,
and
can
radiate radio
frequency energy and, if not
installed
and used in accordance
with the instructions, may cause
harmful interference to radio communications. However,
there
is no
guarantee that interference
will not occur in a
particular installation. If
Preface i
this equipment does cause
harmful interference to radio or
television
reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or
more of
the following
measures:
Reorient or relocate
the
receiving antenna
Increase
the
separation between the equipment and receiver
Connect the equipment
into
an outlet
on a
circuit different
from that
to which the receiver
is connected
Consult the dealer or
an experience radio/TV technician
for help
Environment
The Paragon UPS models OL1000RMXL2U, OL1500RMXL2U,
OL2000RMXL2U, and OL3000RMXL2U
are
intended for
installation
in an environment within 0ºC to
40ºC and free
of conductive
contaminants.
CyberPower Systems pays
great
attention to
the environmental
impact of
its products. Environmental protection
measures for the
Paragon series include:
The eco-design approach used in product development.
Provisions for the recycling of the
Paragon
unit at
the
end
of its ser-
vice life.
ii Preface
Icon Usage
Read the following section to
familiarize yourself with the icons used
in this
manual:
Icon
Description
Indicates a hazard to personnel or equipment.
These
warnings must always be followed.
Indicates notes, useful tips,
and helpful
information.
Indicates essential information.
LED off.
LED on.
LED flashing.
Preface iii
Safety
Instructions
Read before installing
SAVE THESE INSTRUCTIONS. This
manual contains important
instructions that should be followed during
installation, operation,
and maintenance
of the
UPS and batteries.
CAUTION: Personal Safety
The UPS has its
own internal power source (the battery).
Consequently, the
power
outlets may be energized
even if
the
UPS is
disconnected from
the
AC power source.
Dangerous voltage levels
are present within
the
UPS. It
should be
serviced only
by qualified service personnel.
The UPS must
be properly grounded.
Measurements should be
taken
to
ensure that
the total leakage current
of the
UPS and
the
protected equipment does not
exceed
3.5mA (maximum leakage
current of the UPS
= 2mA).
The
battery supplied
with the UPS contains small amounts of
toxic
materials. The
safety warnings below
must be
followed:
- Never
burn the battery (risk
of explosion).
- Do not attempt to open the battery
(the electrolyte is dangerous
for the
eyes and skin).
- Comply with
all applicable
regulations
for the disposal
of a
battery.
- Batteries constitute a danger
(electrical shock, burns).
The
short-circuit current may be
very
high. Precautions
must be
taken when handling: remove watches, rings, bracelets and any
other metal objects; use tools with
insulated
handles.
- Do not lay tools
or metal parts on
top
of batteries.
iv Safety Instructions
Contents
Preface .............................................................................i
Safety Instructions
.............................................................
iv
Device Overview
.............................................................…
..
1
System configurations
...............................................................
..
1
Rear panel
..............................................................................
2
Control panel .............................................................................
5
Installation ........................................................................…..6
Unpacking .................................................................................
6
Installing
the
UPS in a rack
.....................................................
.
7
Setting the UPS
in
the vertical position
.....................................
8
Connecting the RS232 or the
USB
communication port (optional)
...................................................................................................
..
9
Installing the optional
communication card
.............................
.
10
Connections ............................................................................
.
10
Operation .......................................................................…
12
Start-up ...................................................................................
..
12
LED indicators
.........................................................................
.
13
Operation on battery power (following
AC input power
failure) 14
Personalization (option)
..........................................................
15
UPS Shutdown ........................................................................
19
UPS Remote Power Off
...........................................................
19
Maintenance ...................................................................
21
Troubleshooting ......................................................................
21
Replacement
of the battery module .......................................
23
Appendix .........................................................................
25
Technical Characteristics
.......................................................
25
Technical Specifications
......................................................
25
Limited Warranty and
Connected Equipment Guarantee
................................
29
vi
1 Device Overview
1.1 System configurations
Rack setup
Model
Dimensions
(WxDxH)(inch)
Weight
(pound)
OL1000RMXL2U 17.24x18.66x3.41 43
OL1500RMXL2U 17.24x18.66x3.41 45.19
OL2000RMXL2U 17.24x25.69x3.41 70.11
OL3000RMXL2U 17.24x25.69x3.41 72.31
Tower setup
Device Overview 1
1.2 Rear panel
Paragon OL1000RMXL2U/OL1500RMXL2U
1
3
4
5
10
11
Paragon ABP36VRM-2U (optional)
4
12
8
8
NO
Description
1 USB communication port.
2 RS232 communication port.
3 Connector for remote power off (RPO).
4 Connector for automatic detection of an additional battery pack.
5 Expansion slot for optional communication card.
6 Button to test phase/neutral inversion of AC power source.
7 LED indicating Site Wiring Alarm enabled, with flashing and
periodic buzzer. Reset fault with rear panel button.
8 Connector for an additional battery pack.
9 NEMA 5-15P Input power plug for direct connection to AC
power source.
10 Six NEMA 5-15/20R receptacles for connection to AC power source.
11 Two programmable NEMA 5-15/20R receptacles.
12 Circuit breaker for battery ON/OFF and protection.
2 Device Overview
The compatibility of optional battery packs:
ABP36VRM-2U
is for OL1000RMXL2U and OL1500RMXL2U UPS units.
ABP72VRM-2U
is for OL2000RMXL2U and OL3000RMXL2U UPS units.
Refer to the tables in this chapter
for all illustration numbering throughout
this manual (unless specified otherwise).
4 Device Overview
2 Installation
2.1 Unpacking
The following
items are included in the box along with the UPS.
Users manual
Telescopic rails
for mounting in
19” rack with
mounting hardware
Quick Guide
USB communication
cable
Two tower supports for
the vertical position
RS232 communication
cable
CD with the
PowerPanel Business
Edition Agent
software
6 Installation
2.3 Setting the UPS in the vertical position
Attach the two
tower supports to the UPS as shown
below.
Pull out
the
CyberPower Logo plate,
rotate
it as shown, and replace it
in the
front of
UPS.
8 Installation
2.4 Connecting the RS232 or the USB communication
port
(optional)
Connect the UPS to a PC using the RS232
or USB communication
port as shown below.
1
2
OL1000RMXL2U/OL1500RMXL2U UPS shown.
1.
Connect
the RS232 or the USB communication cable to the
corresponding port
on the
computer.
2.
Connect the
other
end of the communication
cable
to the either
the
RS232
1
or USB
2
communication port
on the UPS.
The RS232 and USB communication ports cannot be used at the same
time.
Installation 9
2.5 Installing the optional communication card
5
OL1000RMXL2U/OL1500RMXL2U UPS shown.
It is not necessary to shut down the UPS to install the communication
card:
1.
Remove
the slot
5
cover secured by two screws.
2.
Insert the card in the slot.
3.
Secure the card with the
two screws.
2.6 Connections
Check
that the rating indicated
on
the back of the UPS corresponds to
your
AC-power system and to the actual
electrical
consumption of all the
equipment to be
connected to the UPS.
OL1000RMXL2U/OL1500RMXL2U UPS
B
C
5-15P or
5-20P
5-15P
A
10 Installation
OL2000RMXL2U/OL3000RMXL2U UPS
5-15P or
5-20P
5-20P(OL2000RMXL2U)
Input cable
A
L5-30P(OL3000RMXL2U)
Input cable
L5-20R/L5-30R(Receptacle)
Output cable
1.
Connect
the input power cord (A)
to the
AC-power
wall
receptacle.
2.
Connect
the protected equipment to
the UPS. It is advisable to
connect
priority
loads to the NEMA
5-15/20P outlets
(B)
and/or power cord (D)
and any
non-priority loads to
the
two
programmable outlets
(C).
If the UPS is connected to a computer running CyberPower Systems
communication software, it is possible to program the interruption of power
to the two programmable outlets (C) during operation on battery power,
thus
reserving
backup power for the priority loads.
The battery begins charging the instant
the UPS unit is connected to a
power
source.
Eight hours are required to charge to fully charge the
battery.
Installation 11
3.2 LED indicators
LEDs
21
to
24
provide
three different indications:
1.
Remaining backup
time
as a
percentage (during normal
operation).
2.
Percentage
of load drawn by
the protected equipment, when
button
20
is
pressed.
3.
Operating
faults
(alarmed by flashing LED and beep):
LED
Alarm Condition
21
Site wiring fault
22
Battery fault or end of life warning
23
UPS fault
24
Overload
Description
of
LEDs
17
and
18
indicator status
for programmable
outlets 1 and
2:
-
OFF:
The outlets are not
supplied with power.
-
Flashing: Status change in progress.
-
ON: The outlets
are
supplied with
power.
Outlets 1 and 2 can be
remotely
programmed and controlled.
They may be used for sequential
start-up of
the protected
applications, shedding of non-priority applications during
operation on
battery power, and priority
management at the end of battery backup
time
to reserve
the longest possible backup
time for the most
sensitive applications. These outlets are programmed
using
PowerPanel Business Edition Agent
software.
Operation 13
3.3 Operation on battery power
(following AC
input power
failure)
Transfer to battery power
14
The AC power source is
out of
tolerance,
LED
14
is ON,
the
buzzer sounds three times.
The AC power to equipment connected
to the
UPS
is supplied by
the battery.
Threshold for the low-battery warning
14
The low-battery warning
threshold can be set by the user,
with the
PowerPanel
Business Edition Agent
software
(see
Personalization (option)
on page
15). LED
sounds every three seconds.
14
flashes. The
buzzer
There is very little remaining battery backup time.
Close all
applications;
UPS automatic
shutdown is imminent.
14 Operation
End of backup time
19
The buzzer sounds
continuously.
Press button
OFF.
19
to turn the buzzer
The equipment
is no longer supplied
with power.
The UPS goes into sleep mode at the end of the battery backup time,
until complete
shutdown.
Make sure that the automatic-restart function has been enabled
(
Personalization (option)
on page
15) for the return of
AC input power.
3.4 Personalization
(option)
Function
Personalization
parameters can be
set and modified using the
PowerPanel Business Edition Agent
software installed on a
computer that is connected to the UPS (see
Connecting the
RS232
or the USB communication
port
(optional)
on page
9).
Check that the RS232 or USB communication cable is properly connected.
Operation 15
PowerPanel
Business Edition Agent
installation:
1.
Insert the provided CD containing the
PowerPanel Business
Edition Agent
software
into
the computers CD ROM drive.
2.
The installation software should load automatically. If not, open the
file manager and select
the CD-ROM drive.
3.
Launch "software\setup.exe".
4.
Follow the instructions
to install
the
software.
You can download the
PowerPanel Business Edition Agent
software
from the CyberPower Systems web site at www.cyberpowersystems.com,
or contact a CyberPower representative in your area. Once
PowerPanel
Business Edition Agent
has
been installed, the UPS parameters listed
below can be
modified.
Battery Backup Configuration
The
PowerPanel Business Edition
Agent
software provides the
following options
for battery backup configuration.
To enable
a function, check the
box
before the item.
To set
the
options with values, specify them
from the drop-down
menu or enter the new values
in
the blank
field.
When all the configurations are set, click the
Apply
button
on the
bottom
of the page.
Output
Wake up Battery Backup when utility power restored.
Options: Enabled / Disabled
Default: Enabled
Battery Backup will attempt to restore
power from a shorted circuit condition.
Options: Enabled / Disabled
Default: Disabled
Enter bypass mode once Battery Backup is overloaded.
Options: Enabled / Disabled
Default: Enabled
16 Operation