MODEL: OR1500LCDRM2U, OR2200LCDRM2U, OR1500LCDRTXL2U,
MODEL: PR1000LCD
MODEL: PR1500LCD
1. Remove the front panel of the UPS.
2. Remove two screws from the battery compartment cover and slide the cover completely off of
the unit.
3. Remove the batteries from the compartment. Disconnect the battery wires from the batteries.
4. Install the replacement batteries by connecting the wire bundle (composed of one red wire and
one black wire) to the connector from the battery pack.
5. Put the batteries back into the compartment. Re-install the battery compartment cover and
tighten the retaining screws. Put the front panel back on the UPS.
6. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge
MODEL: PR750LCDRM1U, PR1000LCDRM1U
1. Remove the right side front panel.
2. Remove the two retaining screws for the cable protection cover and remove the cover.
3. Disconnect the black and red cable.
4. Remove the one retaining screw holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
sequence of the above steps. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: PR1500SWRM2U, PR2200SWRM2U
1. Remove the right side front panel.
2. Remove the two retaining screws for the cable protection cover and remove the cover.
3. Disconnect the black and red cable.
4. Remove the four retaining screws holding the battery pack in place.
5. Remove the battery pack.
6. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: PR1000LCDRT2U, PR1000LCDRTXL2U, PR1500LCDRT2U,
PR2200LCDRT2U, PR3000SWRM2U
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: PR1000LCDRTXL2Ua, PR1500LCDRTXL2U, PR2200LCDRTXL2U,
PR3000LCDRT2U, PR3000LCDRTXL2Umart
1. Remove the six retaining screws, and remove the front panel from the UPS.
2. Remove the two retaining screws for the cable protection cover and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the three retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
MODEL: PR5000LCDRTXL5U, PR6000LCDRTXL5U
1. Remove the front panel.
2. Remove the two retaining screws of the cable protection cover and remove the cover.
3. Pull the plastic sticker out slowly to remove the battery module.
4. Put the new battery modules back into the compartment.
5. Tighten the screws and replace the cable protection cover and the front panel.
PFC SINEWAVE Series
MODEL: CP850PFCLCD, CP1000PFCLCD
1. Turn the UPS on its side. Remove the retaining screw located on the bottom of the UPS.
2. Slide the battery compartment cover completely off of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same
color connectors from the battery pack. Put the batteries back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screw. Recharge the UPS
for 8-16 hours to fully charge the battery.
MODEL: CP1350PFCLCD
1. Turn the UPS on its side. Remove the front panel retaining screws located on the bottom of the
UPS.
2. Slide the battery compartment cover (front panel) completely off of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the same
color connectors from the battery pack. Put the batteries back into the compartment.
6. Slide back the battery compartment cover and tighten the retaining screws. Recharge the UPS
for 8-16 hours to fully charge the battery.
MODEL: CP1500PFCLCD
1. Turn the UPS on its side. Remove the front panel retaining screws located on the bottom of the
UPS.
2. Slide the battery compartment cover (front panel) completely off of the unit.
3. Remove the batteries from the compartment.
4. Disconnect the battery wires from the batteries.
5. Install the replacement batteries by connecting the wire bundle (composed of one red wire and
one black wire) to the connector from the battery pack. Put the batteries back into the
compartment.
6. Slide back the battery compartment cover and tighten the retaining screws. Recharge the UPS
for 8-16 hours to fully charge the battery.
MODEL: OR1500PFCRT2U, OR2200PFCRT2U
1. Remove the right side front panel.
2. Remove the three retaining screws for the cable protection cover and remove the cover.
3. Remove the two retaining screws from the cable connectors.
4. Disconnect the black and red cable.
5. Remove the four retaining screws holding the battery pack in place.
6. Remove the battery pack.
7. Install the new battery pack. Assemble the screws, cover, cable and front panel in the reverse
order of the previous steps. Charge the unit for 4-8 hours to ensure the UPS performs expected
runtimes.
Specyfikacje produktu
Marka: | CyberPower |
Kategoria: | bateria |
Model: | RB1290X16 |
Wysokość produktu: | 378 mm |
Szerokość produktu: | 540 mm |
Głębokość produktu: | 400 mm |
Waga produktu: | 49305 g |
Szerokość opakowania: | 642 mm |
Wysokość opakowania: | 393 mm |
Głębokość opakowania: | 330 mm |
Pojemność baterii: | 9000 mAh |
Technologia baterii: | Ołowiany (VRLA) |
Zakres temperatur (eksploatacja): | 0 - 40 °C |
Zakres wilgotności względnej: | 0 - 90 % |
Waga wraz z opakowaniem: | 4132625 g |
Kompatybilność: | PR5000LCDRTXL5U, PR6000LCDRTXL5U |
Napięcie baterii: | 12 V |
Obsługiwane produkty: | PR5000LCDRTXL5U, PR6000LCDRTXL5U |
Liczba baterii włączone: | 16 szt. |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z CyberPower RB1290X16, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje bateria CyberPower
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
18 Czerwca 2024
Instrukcje bateria
- bateria Parkside
- bateria Berg
- bateria Crestron
- bateria Black & Decker
- bateria Fujifilm
- bateria Honeywell
- bateria Tripp Lite
- bateria Shure
- bateria Mestic
- bateria Deltaco
- bateria Cobra
- bateria Ansmann
- bateria Victron Energy
- bateria Hama
- bateria Watson
- bateria Impact
- bateria TOA
- bateria Arctic Cooling
- bateria Varta
- bateria Powerworks
- bateria Kress
- bateria E-flite
Najnowsze instrukcje dla bateria
4 Października 2024
28 Września 2024
21 Września 2024
13 Września 2024
7 Września 2024
8 Lipca 2024
8 Lipca 2024
8 Lipca 2024
8 Lipca 2024
8 Lipca 2024