990-3486A 01/2009
Smart-UPS® RC
External Battery Pack
Tower/Rack-Mount 4U
SRC96XLBP
SRC96XLBP2S
English
SRC96XLBP / SRC96XLBP2S User Manual 3
Introduction
Overview
The American Power Conversion (APC
®) SRC96XLBP external battery pack (XLBP) connects to an
APC Smart-UPS® RC. Together these units provide extended protection for electronic equipment (load)
from utility power blackouts, brownouts, sags and surges. The UPS and the XLBP together provide
continuous power from the batteries until utility power returns to safe levels or the batteries are fully
discharged.
Inventory
Read the Safety Guide before installing the unit.
Inspect the battery pack upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the battery pack package contents:
NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an
additional label is located on the chassis under the front bezel.
Accessories
Install accessories prior to connecting power to the UPS.
Refer to the APC Web site, www.apc.com for available accessories.
Optional accessories
Additional external battery packs (XLBP)
Additional battery strings
4-post rail kit
External Battery Pack (XLBP)
Front bezel
Stabilizer/rack-mount brackets
XLBP connector cable
Hardware supplied listed in table below
Literature kit containing:
Product documentation
– Smart-UPS® RC User Manuals CD
Safety information
Warranty information
8
2
2
su0211a
8
Hardware supplied Rack-mount configuration:
Pan head screws for securing rack-mount brackets to unit
Tower configuration:
Flat head screws for securing stabilizer brackets unit
Rack-mount configuration brackets
Tower configuration stabilizer brackets
Rack-mount configuration:
Washers for securing rack-mount brackets to unit
SRC96XLBP / SRC96XLBP2S User Manual 4
Specifications
Environmental Specifications
Physical Specifications
Temperature Operating 0° to 40° C (32° to 104° F) This unit is intended for indoor use
only. Select a location sturdy
enough to handle the weight.
Do not operate unit where there is
excessive dust or temperature or
humidity are outside specified
limits.
Environmental factors impact
battery life. High temperatures, poor
utility power, and frequent, short
duration discharges will shorten
battery life.
Storage -15° to 30° C (5° to 86° F)
charge UPS battery every six months
30° to 70° C (86° to 158° F)
charge UPS battery every three months
Maximum
Elevation
Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity 0 to 95% relative humidity,
non-condensing
Weight - Refer to Safety Guide supplied with this unit for lifting guidelines.
XLBP
model
SRC96XLBP2S
without batteries
with two 48 V battery modules
15 kg (32 lbs)
35 kg (76 lbs)
SRC96XLBP
without batteries
with six 48 V battery modules
15 kg (32 lbs)
75 kg (164 lbs)
each 48 V battery module 10 kg (22 lbs)
Each 96 V battery string consists of two
48 V battery modules.
Maximum number of external battery packs
(XLBPs) supported by Smart-UPS RC
10
Combined weights of UPS and all XLBPs installed in a
rack must not exceed rack weight limits.
Dimensions
Length x Width x Height: 48 cm (19 in) x 43 cm (17 in) x 18 cm (7 in)
su0265a


Specyfikacje produktu

Marka: APC
Kategoria: Akumulator
Model: SRC96XLBP

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z APC SRC96XLBP, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Akumulator APC

APC

APC Symmetra LX Instrukcja

16 Września 2024
APC

APC RBC108 Instrukcja

12 Września 2024
APC

APC RBC63 Instrukcja

10 Września 2024
APC

APC SRC96XLBP Instrukcja

6 Września 2024
APC

APC RBC43 Instrukcja

20 Sierpnia 2024
APC

APC SMX48RMBP2U Instrukcja

19 Sierpnia 2024
APC

APC UXABP48 Instrukcja

8 Sierpnia 2024
APC

APC RBC109 Instrukcja

6 Sierpnia 2024
APC

APC RBC118 Instrukcja

6 Sierpnia 2024
APC

APC RBC136 Instrukcja

4 Lipca 2024

Instrukcje Akumulator

Najnowsze instrukcje dla Akumulator