ACM4 Series
Access Power Controllers
Installation Guide
Models Include:
ACM4
- Four (4) Fuse Protected Outputs
ACM4E
- Four (4) Fuse Protected Outputs w/Enclosure
ACM4CB
- Four (4) PTC Protected Outputs
ACM4CBE
- Four (4) PTC Protected Outputs w/Enclosure
More than just power.TM
- 2 - ACM4 series
Overview:
These units convert one (1) 12 to 24 volt AC or DC input into four (4) independently controlled fused or PTC protected
outputs. These power outputs can be converted to dry form “C” contacts (ACM4/ACM4E only). Outputs are activated by
an open collector sink or normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push
Button, PIR, etc. The units will route power to a variety of access control hardware devices including Mag Locks, Electric
Strikes, Magnetic Door Holders, etc. All interconnecting devices must be UL Listed. Outputs will operate in both Fail-Safe
and/or Fail-Secure modes. Units are designed to be powered by one common power source which will provide power for
both the board operation and locking devices, or two (2) totally independent power sources, one (1) providing power for
board operation and the other for lock/accessory power. The FACP Interface enables Emergency Egress, Alarm Monitoring,
or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all
of the four (4) outputs.
Configuration Reference Chart:
*Install in Altronix Power Supply/Chargers AL300ULX, AL400ULX and AL600ULX only. Total output current when
ACM4/ACM4CB is utilized as a sub-assembly with power supply/chargers listed below (see Total Output Chart, below).
Note: The total for all outputs combined is not to exceed 8 amp for ACM4CBE and 10 amp for ACM4E.
Total Output Chart:
Note: ACM4/ACM4CB can only be utilized with the power supplies listed above.
Specifications:
olt 12 to 24v AC or DC operation (setting not required).
Input Ratings (ACM4/ACM4CB only):
- 12VDC @ .4 amp or 24VDC @ .2 amp.
Input Ratings (ACM4E/ACM4CBE only):
- 12VDC @ .4 amp or 24VDC @ .2 amp.
- 12VAC @ .4 amp or 24VAC @ .3 amp.
Power supply input options:
a) One (1) common power input (board and lock power).
b) Two (2) isolated power inputs (one (1) for board power and one (1) for lock/hardware power).
Four (4) Access Control System trigger inputs:
a) Four (4) normally open (NO) inputs.
b) Four (4) open collector sink inputs.
c) Any combination of the above.
Four (4) independently controlled outputs:
a) Four (4) Fail-Safe and/or Fail-Secure power outputs.
b) Four (4) dry form “C” 5 amp rated relay outputs (ACM4/ACM4E only).
c) Any combination of the above (ACM4/ACM4E only).
Four (4) auxiliary power outputs (unswitched).
Altronix
Model
Number
ACM4 4 x ---- 3 amp - * UL File # BP6714
UL Listed for Access Control
System Units (UL 294).
“Signal Equipment” Evaluated to
CSA Standard C22.2
No.205-M1983
ACM4E 4 x ---- 3 amp - x
ACM4CB 4 x---- 2 amp x *
ACM4CBE 4 x---- 2 amp x x
Number of
Outputs
Fuse Protected
Outputs
PTC Protected
Outputs
Output Ratings
(per output)
Enclosure
Agency Listings
UL Listings and
File Numbers
Class 2 Rated Power
Limited Outputs
UL Listed
Sub-Assembly.
UL Listed
Accessory.
UL Listed
Sub-Assembly.
UL Listed
Accessory.
Power Supply 12 volt DC Output 24 volt DC Output
AL300ULX 2.1 amp 2.3 amp
AL400ULX 2.8 amp 3.6 amp
AL600ULX 5.6 amp 5.8 amp
ACM4 series - 3 -
Output ratings:
- Fuses are rated 3 amp each.
- PTCs are rated 2.5 amp each.
Main fuse is rated at 10 amp.
Note: The total for all outputs combined is not to exceed 8 amp for ACM4CBE and 10 amp for ACM4E.
(For Models ACM4/ACM4CB refer to the Total Output Chart on Page 2).
Note: Operating temperature range should be 0 to +49
oC.
Red LEDs indicate outputs are triggered (relays energized).
Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the four (4) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) dry contact input.
b) Polarity reversal input from FACP signaling circuit.
FACP output relay (form “C” contact rated @ 1 amp 28VDC not evaluated by UL).
Green LED indicates when FACP disconnect is triggered.
Removable terminal blocks facilitate ease of installation.
Board Dimensions (approximate): 5.125”L x 3.625”W x 1.25”H (ACM4 and ACM4CB).
Enclosure Dimensions (approximate): 8.5”H x 7.5”W x 3.5”D (ACM4E and ACM4CBE).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Product is intended for indoor use only.
1. For ACM4/ACM4CB sub-assembly boards, use stand-offs to mount only in AL300ULX, AL400ULX or
AL600ULX enclosures (Figs. 8-9, pg. 8). For ACM4E/ACM4CBE units, mount in desired location.
The enclosure door for the ACM4E/ACM4CBE can be fastened by using either a cam lock or screws (both supplied).
Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install three upper
fasteners and screws in the wall with the screw heads protruding. Place the enclosures upper keyholes over the two
upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower
holes and install the two fasteners. Place the enclosures upper keyholes over the two upper screws. Install the
two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7).
Carefully review:
Typical Application Diagram (pg. 4) Terminal Identification Table (pg. 5)
LED Dia Hook-up Diagnostics (pg. 5) grams (pg. 6)
2. Power supply input:
The units can be powered with one (1) Listed Access Control Power Supply which will provide power for both
board operation and the locking devices or two (2) separate Listed Access Control Power Supplies, one (1) to provide
power for the board operation and the other to provide power for the locking devices and/or access control hardware.
Note: The input power can be either 12 to 24 volts AC or DC operation.
Input Ratings (ACM4/ACM4CB only):
- 12VDC @ .4 amp or 24VDC @ .2 amp.
Input Ratings (ACM4E/ACM4CBE only):
- 12VDC @ .4 amp or 24VDC @ .2 amp.
- 12VAC @ .4 amp or 24VAC @ .3 amp.
(a) Single power supply input:
If the unit and the locking devices are to be powered using a single Listed Access Control Power Supply, connect
the output (12 to 24 volts AC or DC) to the terminals marked [- Control +].
(b) Dual power supply inputs (Fig. 1, pg. 4):
When the use of two Listed Access Control Power Supplies is desired, jumpers J1 and J2 (located to the left
of the power/control terminals) must be cut. Connect power for the unit to the terminals marked [- Control +]
and connect power for the locking devices to the terminals marked [- Power +].
Note: When using DC Listed Access Control Power Supplies polarity must be observed. When using AC Listed
Access Control P
ower Supplies polarity need not be observed.
Note: For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories.
3. Output options (Fig. 1, pg. 4):
The ACM4/ACM4E will provide either four (4) switched power outputs, four (4) dry form “C” outputs, or
any combination of of both switched power and form “C” outputs, plus four (4) unswitched auxiliary power outputs.
The ACM4CB/ACM4CBE will provide four (4) switched power outputs or four (4) unswitched auxiliary power outputs.
(a) Switched Power outputs:
Connect the negative (-) input of the device being powered to the terminal marked [COM]. For Fail-Safe operation


Specyfikacje produktu

Marka: Altronix
Kategoria: Listwa zasilająca
Model: ACM4CBE

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Altronix ACM4CBE, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Listwa zasilająca Altronix

Altronix

Altronix PDS8 Instrukcja

1 Października 2024
Altronix

Altronix ACM4CBE Instrukcja

1 Października 2024
Altronix

Altronix AL802ULADAJ Instrukcja

1 Października 2024

Instrukcje Listwa zasilająca

Najnowsze instrukcje dla Listwa zasilająca

Bauhn

Bauhn AP5W-0624 Instrukcja

15 Października 2024
Bauhn

Bauhn AP6W-0324 Instrukcja

15 Października 2024
Hama

Hama PowerCube 00223195 Instrukcja

9 Października 2024
CyberPower

CyberPower P0420SUD0-DE Instrukcja

9 Października 2024
CyberPower

CyberPower B0520SC0-DE Instrukcja

9 Października 2024
GoGen

GoGen SP16A5 Instrukcja

7 Października 2024
Bachmann

Bachmann Desk 2 Instrukcja

1 Października 2024