Instrukcja obsługi Air King LEDAK100D


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Air King LEDAK100D (12 stron) w kategorii Niesklasyfikowane. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/12
IMPORTANT INSTRUCTIONS -
OPERATING MANUAL
SAVE THESE INSTRUCTIONS
www.airkinglimited.com
A210952014 Rev. O 11-18 1 of 12
Exhaust Fan with Light
Models: AKF100D4,
LEDAK100D, LED100DH
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service
panel and lock the service disconnecting means to prevent power
from being switched on accidentally. When the service disconnecting
means cannot be locked, securely fasten a prominent warning
device, such as a tag, to the service panel.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualied
person(s) in accordance with all applicable codes and standards,
including fire-related construction.
b) Sufficient air is needed for proper combustion and exhausting of
gases through the flue (chimney) of fuel burning equipment to prevent
back drafting. Follow the heating equipment manufacturers guideline
and safety standards such as those published by the National Fire
Protection Association (NFPA) and the American Society for Heating,
Refrigeration, and Air Conditioning Engineers (ASHRAE), and the local
code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical
wiring and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) This unit must be grounded.
f) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
WARNING: IF FAN IS INTENDED FOR CONTINUOUS
OPERATION DO NOT POWER FAN UNTIL ALL CONSTRUCTION HAS
BEEN COMPLETED. THE FAN WILL DRAW IN AIRBORNE DUST THAT COULD
IMPAIR OPERATION AND REDUCE THE LIFE OF THE MOTOR. USAGE OF
FAN DURING CONSTRUCTION PROCESS WILL VOID ALL WARRANTIES.
g) Read all instructions before installing or using exhaust fan.
h) If this unit is to be installed over a tub or shower, it must be marked
as appropriate for the application and be connected to a GFCI (Ground
Fault Circuit Interrupter) – protected branch circuit.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, DO NOT USE THIS FAN WITH
ANY SOLID-STATE SPEED CONTROL DEVICE.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT
ON THE AIR FLOW, NOISE AND ENERGY USE OF THE FAN. USE
THE SHORTEST, STRAIGHTEST DUCT ROUTING POSSIBLE FOR
BEST PERFORMANCE, AND AVOID INSTALLING THE FAN WITH
SMALLER DUCTS THAN RECOMMENDED. INSULATION AROUND
THE DUCTS CAN REDUCE ENERGY LOSS AND INHIBIT MOLD
GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY NOT
ACHIEVE THEIR RATED AIRFLOW.
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
1 - Grill
1 - Light Assembly
1 - Damper Assembly (attached)
4 - Mounting Rails
1 - Lamp
1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it
is recommended that the length of ducting and the number of elbows be kept to a
minimum, and that insulated hard ducting be used Larger duct sizes will reduce noise
and airflow restrictions. This fan will require at least 8 of clearance in the ceiling or wall, "
and will mount through drywall up to 3/4" thick. The
fan mounts between 16 or 24 on center joists using " "
the 4 provided mounting rails.
3. Select the most convenient electrical knockout and
remove using a straight-blade screw driver and install
an approved electrical connector (Figure 1).
4. No additional vibration deadening materials are needed
for this fan.
SECTION 2
New Construction
1. Install the rails into the mounting channel on the housing. Center the mounting channel in
the slots on the housing, then from inside the housing tighten the mounting channel screws
so the channel is securely in place. Position the housing next to the joist. Line up housing
so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or
nails (not included) to the joists and slide the housing into the final position (Figure 2).
SECTION 3
Existing Construction
1. Set housing in position between the joist and trace an outline onto the ceiling material
(Figure 3). Set housing aside and cut opening, being careful not to cut or damage any
electrical or other hidden utilities. Install the rails into the mounting channel on the
housing. Center the mounting channel in the slots on the housing, then from inside
the housing tighten the mounting channel screws so the channel is securely in place.
Position the housing in the previously cut hole so that it is flush with the finished ceiling.
Secure the ends of the rails to the joists (Figure 2).
www.airkinglimited.com
A210952014 Rev. O 11-18 2 of 12
SECTION 4
Ducting
NOTE: 4" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND
NATIONAL BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible
for best performance, and avoid installing the fan with smaller ducts than recommended.
Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed
with existing ducts may not achieve their rated air flow.
1. Connect the ducting to the fan’s duct collar Secure in place using tape (Figure 4).
or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is
recommended that low restriction termination fittings be used.
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar
material to create an air-tight path to minimize building heat loss or gain and to reduce
the potential for condensation. Place/wrap insulation around duct and/or fan in order to
minimize possible condensation buildup within the duct, as well as building heat loss or
gain (Figure 5).
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL
WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of
the fan’s blower assembly. If you choose to wire the unit from the inside, you will need to
remove the blower assembly and internal wiring compartment. Both methods are equally
effective.
1a. Remove the wire compartment cover screw and place External Wire Compartment:
cover in a secure place .(Figure 6)
Figure 1
Figure 2
Housing
Joist
Mounting Rails
Ducting
Duct
Collar
Figure 4
Figure 5
Insulation*
(place around and
over Fan Housing
Fan Housing
Power Cable*
Seal gaps
around Housing
Round
Duct*
Seal duct joints
with tape
Round
Elbows*
Wall Cap*
Roof Cap*
(with built-in
damper)
Keep duct
runs short
*Purchase separately
or
Figure 3
Joist
1b. Internal Wire Compartment: Remove the screw holding the blower assembly in place
and lift assembly out of housing . Remove the wire compartment cover screw (Figure 7)
and place the cover in a secure place (Figure 8).
NOTE: If the fan motor plug is connected to the fan housing receptacle, unplug so the
blower assembly can be completely removed.
2. Continuous Ventilation: For two speed fans wired for continuous ventilation, connect
the White wires of the fan to the White (Neutral) wire from the power source. Connect the
ground wire from the house to the green wire from the fan housing. Connect the Black
wire of the fan to the Black wire (Hot) from the power source. Using a properly grounded
standard duplex toggle switch (such as Leviton 5224-2W, not included) connect the Black
wire from the supply to one side of the top and bottom switch. Connect the Red wire (light)
from the fan housing to the other side of the top switch and connect the Purple wire (night
light) from the fan housing to the other side of the bottom switch. Using a second properly
grounded standard duplex toggle switch, connect the Hot Yellow wire from the fan to the
input of the switch. Connect the second Yellow wire from the fan to the output side of the
switch. Closing the switch will change from normal to high speed (Figure 9).
www.airkinglimited.com
A210952014 Rev. O 11-18 3 of 12
3. Intermittent Ventilation: For two speed fans wired for intermittent ventilation with a
standard duplex toggle switch (such as Leviton 5224-2W not included). Connect the
White wires of the fan to the White (Neutral) wire from the power source. Connect the
ground wire from the fan to the ground wire from the power source. Properly ground the
switches. Connect the black wire from the supply to one side of the top switch. Connect
the black wire from the fan to the other side of the top switch, Connect 1 yellow wire
from the fan to each side of the bottom switch. The top switch turns the fan On & Off, the
bottom switch changes speed between high and low. Using a second properly grounded
standard duplex toggle switch, connect the Black wire from the supply to one side of the
top and bottom switch. Connect the Red wire (light) from the fan housing to the other side
of the top switch and connect the Purple wire (night light) from the fan housing to the other
side of the bottom switch (Figure 10).
NOTE: The fan’s receptacle wires might need to be pulled outside compartment for connection.
Only pull the three loose wires outside of compartment. Additional wires will be present.
4. Carefully tuck wires back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
SECTION 6
Completing the Installation
1. Use a sealant appropriate for contact with the building materials present and for the
temperature requirements of the installation to prevent air leakage from unconditioned
spaces is recommended. If gaps between unit housing and ceiling are great, additional
material (backing rod, ceiling material) may be required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan
be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.
2. If the fan’s blower assembly was removed during the wiring process, reinstall the blower
by reversing the directions in in .Step 1b Section 5 Wiring
3. Plug the fan’s 5 pin quick connect motor cord into the receptacle on the side of the
wiring compartment cover and the lights 3 pin quick connect into the receptacle on
the top of the wiring compartment cover. These cords will only fit one way into the
receptacles (Figure 11).
4. Install the included lamp into the lamp holder by lining up the pins on the lamp base to the
socket of the lamp holder and turning the lamp body clockwise until the lamp snaps into
place and is firmly seated in the lamp holder. Install a 4 watt maximum type C7 (candelabra
base) night light (not included) into the side lamp holder (Figure 12).
Figure 6
Screw
Wire
Compartment
Cover
Figure 7
Screw
Plug
Venturi
Figure 8
Screw
Wire Compartment
Cover
NOTE: Wire compartment
configuration will be
dependent on model.
Figure 11 NOTE: Wire compartment configuration will be dependent on model.
Figure 9 Supply from house
Black
Yellow
Ground (Green
or Bare)
Fan
Black
Green
Switch
(by others) Yellow
Switch
(by others)
Black
Purple
Red
Neutral (White)
Neutral (White)
By others
Black
Figure 10 Supply from house
Black
Yellow
Ground (Green
or Bare)
Fan
Black
Green
Switch
(by others) Yellow
Switch
(by others)
Black
Purple
Red
Neutral (White)
Neutral (White)
By others


Specyfikacje produktu

Marka: Air King
Kategoria: Niesklasyfikowane
Model: LEDAK100D

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Air King LEDAK100D, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Air King

Air King

Air King EVD Instrukcja

22 Września 2024
Air King

Air King F130D Instrukcja

14 Września 2024
Air King

Air King EVLDGH Instrukcja

5 Września 2024
Air King

Air King MD624 Instrukcja

31 Sierpnia 2024
Air King

Air King R120 Instrukcja

31 Sierpnia 2024
Air King

Air King EVLD Instrukcja

29 Sierpnia 2024
Air King

Air King QFAM Instrukcja

20 Sierpnia 2024

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Stihl

Stihl HT 70 Instrukcja

15 Października 2024
Ernesto

Ernesto H14270 Instrukcja

15 Października 2024
Uniden

Uniden BT MIC KIT Instrukcja

15 Października 2024
Vaude

Vaude Omnis Bike 26 Instrukcja

15 Października 2024
ART

ART ProChannel II Instrukcja

15 Października 2024
Aukey

Aukey DR02J Instrukcja

15 Października 2024
Master Lock

Master Lock 653EURD Instrukcja

15 Października 2024
Roland

Roland FR-18 Diatonic Instrukcja

15 Października 2024