Instrukcja obsługi Tripp Lite SmartPro SMX1200XLHGL
Tripp Lite
UPS
SmartPro SMX1200XLHGL
Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Tripp Lite SmartPro SMX1200XLHGL (72 stron) w kategorii UPS. Ta instrukcja była pomocna dla 6 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek
Strona 1/72
1
Owner’s Manual
SMX
Medical-Grade UPS Systems
with Lithium Iron Phosphate Batteries
Models:
Important Safety Instructions 2
Package Contents 5
Connecting the Batteries 6
Quick Installation 7
Basic Operation 8
Guidance and Manufacturer’s Declaration 11
Storage & Service 13
Battery Warranty Information 14
Regulatory Compliance 14
Español 15
Français 29
Русский 43
Deutsch 57
SMX700HGL
(Series Number: AG-031B)
SMX1200XLHGL
(Series Number: AG-031C)
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved.
18-10-326-933821.indb 1 11/7/2018 11:17:04 AM
2
Important Safety Instructions
Statement of Intended Use
Tripp Lite Medical-Grade UPS Systems are intended to support and protect non-medical computer
equipment and medical devices that require leakage current reduction, surge protection, voltage
regulation, line noise filtering and battery backup during power outages and generator testing, both
inside and outside patient care areas. Tripp Lite’s Medical-Grade UPS Systems come with hospital-
grade plugs and receptacles that reduce leakage to below 100μA.
Product Information
SMX700HGL SMX1200XLHGL
AC Input Voltage 230V 230V
Input Amp(s) 3.6 5
Output Amp(s) 2 3.3
Rated Power (VA/Watts) 700VA, 450W 1000VA, 750W
Frequency 50/60 Hz 50/60 Hz
No. of Phases Single Single
Class Type Class I Class I
Plug/Connector Type Inlet C14 with dongle Inlet C14 with dongle
Operation Continuous Continuous
AC Input Protection (Qty/type/rating) Input breaker (2 x 5A) thermal Input breaker (2 x 6A) thermal
Max Leakage Current (uA) Less than 100uA Less than 100uA
Weight 14.3 kg 15.9 kg
Known Contraindication None None
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation,
operation and storage of all Tripp Lite UPS Systems. Failure to heed these warnings may affect
your warranty.
Note: Your UPS incorporates overcurrent protection in both the L1 and L2 input conductors.
UPS Location Warnings
Relevant Symbols
Denotes that information in the manual should be reviewed before use.
Used to signal as a warning that a statement is particularly important and could pose a safety
risk.
Warning-Dangerous Voltage No sitting
Denotes general warning sign No stepping on surface
Refer to Instruction Manual/Booklet No pushing
18-10-326-933821.indb 2 11/7/2018 11:17:05 AM
3
Important Safety Instructions
• Do not use this equipment within oxygen-enriched atmospheres, or within 0.3 m of a point at
which an oxygen-enriched atmosphere is intentionally vented.
• Use caution when lifting UPS. Because of the considerable weight of all UPS systems, at least
two people should assist in lifting and installing them.
• Install your UPS indoors, away from excess moisture or heat, dust or direct sunlight.
• For best performance, the UPS should be used in a location that meets the following conditions:
Temperature: 0 to 40° C; Humidity: 0 to 95% (non-condensing);
Elevation: <2,000 m above sea level; Pressure: >95kPa
• Leave adequate space around all sides of the UPS for proper ventilation. Do not obstruct its vents
or fan openings.
• Do not mount unit with its front or rear panel facing down (at any angle). Mounting in this manner
will seriously inhibit the unit’s internal cooling, eventually causing product damage not covered
under warranty.
• The UPS is not intended for patient contact. Avoid installations that will cause accidental patient
contact.
UPS Connection Warnings
• The UPS contains its own energy source (battery). The output terminals may be live even when
the UPS is not connected to an AC supply.
• Connect your UPS to a properly grounded AC power outlet. Do not modify the UPS’s plug in a
way that would eliminate the UPS’s connection to ground. Do not use adapters that eliminate the
UPS’s connection to ground.
• Do not plug your UPS into itself; this will damage the UPS and void your warranty.
• If you are connecting your UPS to a motor-powered AC generator, the generator must provide
filtered, frequency-regulated output.
• To remove the UPS from the supply mains, the appliance inlet serves as a disconnect device.
• Once connected, do not limit access to the input plug. The plug must be accessible to be used as
a means of disconnection.
• When connecting the UPS to a power outlet, ensure the power outlet is provided with suitable
overcurrent protection in accordance with national and local electrical codes. Ensure the
overcurrent protection has a minimum of 1500A breaking capacity.
CAUTION: Do not remove cover for 5 minutes after disconnecting all sources of
supply. Risk of electric shock—hazardous live parts inside. User must not remove
cover. No user serviceable parts inside. Refer servicing to qualified service
personnel. This UPS receives power from more DC sources; disconnection of the
AC and DC source is required to de-energize the unit before servicing.
CAUTION: To ensure proper grounding with supply mains power, the input cord must
be connected with an approved country-specific plug with a protective earth ground
connection.
CAUTION: If this product is operated on battery (not connected to mains power),
adequate safeguards should be employed to protect against accidental contact
with AC power conductors.
CAUTION: Do not exceed total rated output.
WARNING: No modification of this equipment is allowed.
18-10-326-933821.indb 3 11/7/2018 11:17:05 AM
Specyfikacje produktu
Marka: | Tripp Lite |
Kategoria: | UPS |
Model: | SmartPro SMX1200XLHGL |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Tripp Lite SmartPro SMX1200XLHGL, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS Tripp Lite
9 Października 2024
9 Października 2024
9 Października 2024
4 Października 2024
1 Października 2024
29 Września 2024
29 Września 2024
16 Września 2024
15 Września 2024
14 Września 2024
Instrukcje UPS
- UPS Ikea
- UPS AEG
- UPS Voltcraft
- UPS LC-Power
- UPS APC
- UPS Block
- UPS V7
- UPS Digitus
- UPS FSP
- UPS Online USV
- UPS Equip
- UPS Emerson
- UPS CyberPower
- UPS JUNG
- UPS Eaton
- UPS Adj
- UPS PowerWalker
- UPS Salicru
- UPS Energenie
- UPS Steren
- UPS East
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Furman
- UPS Minuteman
- UPS Riello
- UPS Maruson
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Approx
- UPS Altronix
- UPS Bxterra
- UPS Middle Atlantic
- UPS Atlantis Land
- UPS FSP/Fortron
Najnowsze instrukcje dla UPS
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
11 Października 2024
9 Października 2024