Instrukcja obsługi Haier HSU19EH-TXS3BE-INV

Haier klimatyzacja HSU19EH-TXS3BE-INV

Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Haier HSU19EH-TXS3BE-INV (2 stron) w kategorii klimatyzacja. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
Please read this operation manual before using the air conditioner.
Keep this operation manual for future reference.
SPLIT TYPE ROOM AIR CONDITIONER OPERATION MANUAL
Loading of the battery
1
2
3
4
Remove the battery cover;
2 R-03 batteries, resetting key
(cylinder);
Be sure that the loading
is in line with th
e" + "/"-";
Load the battery,then put on the cover again.
The distance between the signal transmission head and the rece-
iver hole should be within 7m without any obstacle as well.
When electronic-started type fluorescent lamp or change- over
wireless telephone is installed in the
ver is apt to be disturbed in receiving the signals,
so the distance to the indoor unit should be shorter.
type fluorescent lamp or
room, the recei
Note:
Full display or unclear display during operation indicates the
ries have been used up. Please change batteries.
If the remote controller can't run normally during operation, please
reload several minutes later.
batte
remove the batteries and
Parts and Functions
Indoor Unit and Outdoor Unit
4
OUTLET
INLET
CONNECTING PIPING
AND ELECTRICAL WIRING
DRAIN HOSE
Actual inlet grille may vary from the one shown in the
manual according to the product purchased
Base OperationRemote controlle
Operation
Remote controller
Press button
Every time the button is pressed, temp.setting
increase 1o
C,if kept depressed, it will increase
rapidly
Every time the button is pressed, temp.setting
decrease 1
oC,if kept depressed, it will
decrease rapidly
Select a desired temperature.
3.Select temp.setting
1. Unit start
/
2. Select operation mode
COOL button:Cooling mode
Press ON/OFF
on the remote controller,
unit starts.
Use remote control to turn on
and display setting
temperature 24.
NV)
Healthy function is not available for some units.
2. Mode display
DRY
SLEEP
TIMER
Quiet
SWING
3. Signal sending display
5.FAN SPEED display
6. LOCK display
1.TIMER OFF display/TIMER ON display
8. TEMP display
4. SWING display
L O MED HI AUTO
Display
circulated
7.Additional functions display
Operation mode
Remote controller
QUIET TURBOSLEEP HEALTH
10. EXTRA FUNCTION button
11. CANCEL/CONFIRM button
Function: Setting and cancel to the
timer and other additional functions.
12. RESET button
When the remote controller appears
abnormal, use a sharp pointed
article to press this button to reset
the remote.
Turbo
SELF
CLEAN
EXTRA
FUNCTION
4
3
9. Energy Control button
HEATCOOL
+
_
Operation mode
AUTO FAN
COOL DRY
Remote controller
HEAT
Function:
airflow position1--- Healthy airflow
--- A-B yard --- AUTO
--- 10
o
C
Heating heating mode( )
--- Healthy
position2 --- Air sending
Health
COOL
PressFAN button. For each press, fan speed
follows:
Remote controller:
4.Fan speed selection
Air conditioner is running under displayed fan speed.
When FAN is set to AUTO, the air conditioner
automatically adjusts the fan speed according to room
temperature.
changes as
LOW MED HI AUTO
Display
circulated
Operation
Mode
Remote
Controller Note
In DRY mode, when room temperature becomes lower
than temp.setting+2 oC, unit will run intermittently at LOW
speed regardless of FAN setting.
Under the mode of auto operation, air conditioner will
automatically select Cool or Heat operation according to
room temperature. When FAN is set to AUTO the air
conditioner automatically adjusts the fan speed according
to room temperature.
In FAN operation mode , the unit will not operate in COOL or
HEAT mode but only in FAN mode, AUTO is not available in
FAN mode. And temp. setting is disabled. In FAN mode,
sleep operation is not available.
DRY
COOL
AUTO
HEAT
FAN
In HEAT mode, warm air will blow out after a short
period of the time due to cold - draft prevention function.
When FAN is set to AUTO,the air conditioner automatically
adjusts the fan speed according to room temperature.
Cooling only unit do not have displays and functions
related with heating
Display board
(adjust left and
ow)
Vertical blade
right air fl
Air Purifying FilterInlet
(inside)
Emergency
Switch
Horizontal flap
(adjust up and down air flow
Don't adjust it manually)
Outlet
Inlet grille
(inside)
2
Display board
3
Signal receiver hole
1
Temp.display
2
3
WIFI(Optional)
1
+
HEAT
HEAT button:Heating mode
Load the batteries as illustrated.
HSU19EH-TXG3BE-INV
HSU19EH-TXS3BE-INV
HSU19EH-TXB3BE-INV
HSU19EH-TXW3BE-INV
0011526222
Operation
Emergency operation and test operation
Sleep Operation Turbo/Quiet Operation
Press the
cancel
( )TURBO ( )QUIET
When you need fast cool or fast
dehumidification,you can choose
the Turob function; when you sleep,
read, you can choose Quiet function
bu on, you can switch the “Turbo” and
swith as
When running in Turbothe fan speed is the highest,
when running in Quiet, the fan speed is super slow
below
“Quiet” will
Air Flow Direction Adjustment
Emergency Operation:
Use this operation only when the remote controller is defective
or lost, and with function of emergency running, air conditoner
can run automatically for a while.
When the emergency operation switch is pressed, the " Pi "
sound is heard once, which means the start of this operation.
When power switch is turning on for the first time and
emergency operation starts, the unit will run automatically in
the following modes:
It is impossible to change the settings of temp. and fan speed,It
is also not possible to operate in timer or dry mode.
temperature is below 16oC, do not use it in the
Test operation:
Use this switch in the test operation when the room
normal operation.
your finger from the switch: the cooling
Continue to press the test operation
switch for more than 5 seconds . After
you hear the "Pi" sound twice, release
Test operation switch is the same as emergency switch.
operation starts with the air flow speed "Hi".
Under this operation mode,the fan motor of indoor
unit will run in high speed.
Room
temperature Designated
temperature
Timer
mode Fan
speed
Operation
mode
Above 23oC 26oC AUTO COOL
No
Press “DRY” Button, when the LCD displays ,
Dry Mode is set.
In Dry mode, compressor will stop to operate when the room
temperature is below the setting temperature. If the room
temperature is higher than the setting temperature, the logic
circuit will control the operation of compressor and indoor
fan speed, in order to cause dew formation on cooling coil to
obtain the effect of dehumification. In dry mode ,it is normal
Dry Operation
Timer Operation
Health airflow Operation
1. Set ON timer
.
Press set the duration (hour).
Press “CONFIRM/CANCEL”.
2. Set OFF timer
Press to close the screen
Healthy
airflow
upwarder
Healthy
airflow
downwarder
fixed
location
1.Press to starting
Setting the comfort work conditions.
Note:
1.After setting the healthy airflow function, the position
grill is fixed.
3.In cooling and dry , using the air conditioner for a long
time under the high air humidity, condensate water
may occur at the grille .
Notice: Do not direct the flap by hand. Otherwise, the
grille will run incorrectly. If the grille is not run correctly,
stop for a minute and then start, adjusting by remote controller.
2.In cooling, it is better to select the mode.
Operation
that the indoor fan speed is lower than other operation mode.
SELF
CLEAN
TIMER
Self Clean Operation
Functional description: the purpose of this function is to
clean the evaporator.
Entry and exit Press self clean button to enter this
function, then it will display "CL" on the panel of the indoor
unit and also on the remote controller. After running 18-21
minutes, this function will exit automatically with the " Pi "
sound is heard twice, then the unit return to original state.
Under operation process of self clean, press the button
repeatedly has no effect and cannot exit, but the power off
button and other mode button can make it exit.
Note:
1.It has no effect under the mode of timer/sleep.
2.After this mode starts, the air volume may reduce or
even have no airflow.
3.It is normal if the unit make some sound like expand with
heat and contract with cold
4. The “CL” display time may last differently on the remote
controller and panel.
5.It is normal if the temperature is below 0 outside, the
unit may display "F25"under this mode running.
Please turn off the unit for 10 seconds then restart.
6.The best condition to run this mode: the temperature is
15 ~27 and the humidity is 35 ~60 in the door,℃ ℃ % %
the temperature is 30 ~40 cooling season ℃ ℃(
7.It is hard to frost if the air is too dry(humidity 20%). and
if the humidity is too high(humidity 70%),
the condensate water may increase, which may move away
some frost.
2.The setting of healthy airflow function
Press button to enter additional options,Press this
button continuously, the louvers location will cycle between
in the following three locations, to choose the swing location
what you needed,and then press button to confirm.
Operation Mode
1. In COOL,DRY mode
SLEEP operation starts SLEEP operation stops
Approx.6hrs
1 hr Rises 1
O
C
Rises 1
O
C
Temp.setting Unit stop
In COOL, DRY mode
1 hr
Note:
When TIMER function is set, the sleeping function can’t be
set up .After the sleeping function is set up,
TIMER function, the sleeping function will be cancelled; the
machine will be in the state of timing-on.
1 hours after SLEEP mode starts,temp.will become
higher than temp.setting.After another 1 hours,temp.rises
by 1 futher.The unit will run for further 6 hours then stops
T
emp. is higher than temp.setting so that room temperature
won’t be too low for your sleep.
OC
1
O
C
if user resets
Before going to bed,you can simply press the SLEEP
button and unit will operate in SLEEP mode and bring
you a sound sleep.
SLEEP
Move the vertical blade by a knob on airconditioner
to adjust left and right direction referring to Fig.
4.Left and right air flow adjustment(manual)
When adjusting the flap by hand,turn off the unit.
When humidity is high,condensate water might occur
It is advisable not to keep horizontal flap at downward
position for a long time in COOLor DRY
otherwise, condensate water might occur.
adjusted to left or at air outlet if all vertical louvers are right.
mode ,
Pos.1
Pos.2
3.Press
button
to choose the and
1.Status display of air flow
For each press of button, remote controller
displays as follows :
remote controller:
Vertical flap
COOL/DRY:
HEAT:
No initial state disaplayed on remote controller,
the vertical flap will be fixed on the current position
SLEEP
operation starts
SLEEP
operation stops
1 hr
1 hr
3 hrs
3 hrs
Rises 1
O
C
Temp.setting Unit stop
In HEAT mode
Decreases 2OC
Decreases 2
OC
2.In HEAT mode
1 hours after SLEEP mode starts,temp will become 2
lower than temp.setting.After another 1 hours,temp
decrease by 2
rises by 1 futher.The unit will run for further 3 hours then
stops.Temp.is lower than temp. setting so that room
temperature won’t be too high for your sleep.
O
C futher.After more another 3 hours,temp.
O
C
O
C
3. In AUTO mode
The unit operaters in corresponding sleep mode
adapted to the automatically selected operation mode.
If the wind speed is high or middle before setting for the
sleep, set for lowing the wind speed after sleeping.
If it is low wind, no change.
5.Set the wind speed change when sleeping
4. In FAN mode
It has no SLEEP function.
PiPi
PiPi
Quiet
Turbo
Quiet
Turbo
TIMER
Press to activate the screen
Press set the duration (hour).
Press “CONFIRM/CANCEL”.
TIMER
Energy Control Operation
25
45
step
1.
2.
Note:
1 step : The strong air blows out to cool indoor air quickl y .
2 step : The power input is 100% of rated power.
3
4
5
3 4 5
+
+


Specyfikacje produktu

Marka: Haier
Kategoria: klimatyzacja
Model: HSU19EH-TXS3BE-INV

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Haier HSU19EH-TXS3BE-INV, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje klimatyzacja Haier

Haier

Haier QPCA11YBMW Instrukcja

8 Października 2024
Haier

Haier QPFA08YBMW Instrukcja

8 Października 2024
Haier

Haier QHEC05AC Instrukcja

8 Października 2024
Haier

Haier QHEK12AC Instrukcja

8 Października 2024
Haier

Haier QHEK10AC Instrukcja

8 Października 2024
Haier

Haier QHEK14AC Instrukcja

8 Października 2024
Haier

Haier QHNG10AA Instrukcja

8 Października 2024
Haier

Haier QHNG08AA Instrukcja

8 Października 2024

Instrukcje klimatyzacja

Najnowsze instrukcje dla klimatyzacja

LG

LG HS-H076QPA0 Instrukcja

15 Października 2024
Klarstein

Klarstein Vita Pure 2G Instrukcja

15 Października 2024
Gree

Gree ETAC-15HP265V20B Instrukcja

15 Października 2024
Qlima

Qlima P 126 Instrukcja

14 Października 2024
Mitsubishi

Mitsubishi MSZ-CB22VA Instrukcja

14 Października 2024
Suntec

Suntec Motion 90+ Instrukcja

14 Października 2024
Danby

Danby DTAC120B1WDB Instrukcja

14 Października 2024
Amana

Amana PTC093K35AXXX Instrukcja

14 Października 2024
Amana

Amana AMAP121AB-2 Instrukcja

14 Października 2024