Safety instructions
Electrical equipment may only be installed and
assembled by a qualied electrician in accord-
ance with the relevant installation standards,
guidelines, regulations, directives, safety and
accident prevention regulations of the country.
Failure to comply with these installation in-
structions may result in damage to the device,
re or other hazards.
Hazard due to electric shock. Disconnect be-
fore working on the device or load. Take into
account all circuit breakers that supply danger-
ous voltages to the device or load.
Connect one motor per output only. If several
motors are connected, motors or device might
be destroyed.
Use drives with mechanical or electrical nal
position switches only. Check nal position
switches for correct adjustment. Observe mo-
tor manufacturer's data. The device can be
damaged.
Do not connect any three-phase motors. The
device can be damaged.
Risk of injury. Use the device to control blind
and shutter drives or awnings only. Do not
switch any other loads.
Observe the motor manufacturer's data regard-
ing change-over time and max. switch-on time
(ED).
These instructions are an integral component
of the product and must be retained by the end
user.
Design and layout of the device
C1/C7 C3/C9 C5 /C11
C2/C8 C4/C10 C6/C1 2
3 4 5 6 7 8 9 101 2
N L
L L
230V 50/60 Hz
L L CC6C4C2
18 19 20 2 1 22 23 2 4 25 26
auto 1
auto 2
(1)
(2) (3)
(4) (5)
(6)
(3)
(7)
Figure 1: Device overview
(1) Slide switch / 1/ 2auto1/auto2
(2) KNX bus connection terminal
(3) Connections of loads
(4) Labelling eld with cover
(5) Illuminated programming button
(6) Operation button for manual operation per
output with status LED
(7) Mains power supply connection
Function
System information
This device is a product of the KNX system and
corresponds to the KNX guidelines. Detailed
specialised knowledge obtained from KNX training
courses
is required for understanding. The planning, instal-
lation and commissioning of the device is carried
out with the help of KNX-certied software.
Systemlink commissioning:
The function of the device is software-depend-
ent. The software is to be taken from the product
database. You can nd the latest version of the
product database, technical descriptions as well as
conversion and additional support programmes on
our website.
Easylink commissioning:
The function of the device is conguration-de-
pendent. The conguration can also be done using
devices developed specially for simple setting and
start-up.
This type of conguration is only possible with
devices of the easylink system. Easylink stands for
easy, visually supported start-up. Precongured
standard functions are assigned to the in/outputs
by means of a service module.
Functional description
The device is used to control motor-operated build-
ing ttings such as shutters and blinds via the KNX
bus. The device has 12 outputs from which each
output can be activated independently.
Correct use
- Switching electrically operated motors of 230 V
AC for blinds, shutters, awnings and similar
hangings
- Mounting on DIN rail according to DIN EN
60715 in the distribution box
Product characteristics
- independent outputs, activation via KNX bus
- Status display of the outputs on the device
- manual activation of the outputs on the device
possible, building site operation
- Position can be started directly
- 3 Alarms
- Scene function
- Forced position by higher-level controller
- Connection of various external conductors
possible
- Slat position directly controllable
Operation
Manual operation switch on/off
Bus and mains power supply are present.
zPush switch (1) to position 1/ 2.
Manual operation is switched on, the outputs
can be controlled using the operation buttons
(6) independently of each other.
1 switches on the control of the outputs
C1 C6 .. .
2 switches on the control of the outputs
C7 C12 .. .
During manual operation, the controller is deac-
tivated via the KNX bus.
Systemlink commissioning:
Depending on the programming, the manual
operation is activated permanently or for a time
period congured via the application software.
If the manual operation is blocked via the appli-
cation software, no activation takes place.
Or:
zMove switch (1) to position .auto1/auto2
The manual operation is switched off. Operation
takes place solely via the KNX bus. The output
adopts the position predened by the bus con-
troller. The switching status is displayed via the
status LED of the operation button (6).
auto 1 C1 displays the status of the outputs ..
C6.
auto 2 C7 displays the status of the outputs ..
C12.
Operating outputs in manual operation
Operation takes place per output by briey pressing
the operation button repeatedly (table1).
Status Behaviour when
button pressed briey
Output is in idle
state,
status LED of the
button (6) is off.
Movement operation starts.
Status LED of button (6)
lights up.
1)
Output active,
status LED of the
button (6) lights
up.1)
Movement operation stops,
LED goes out.
1)
The LED lights up red during upward travel and green
during downward travel.
Table 1: Manual operation
Information for electricians
Installation and electrical connection
DANGER!
Touching live parts can result in an
electric shock!
An electric shock can be lethal!
Disconnect the connecting cables
before working on the device and
cover all live parts in the area!
ç
CAUTION!
Risk of destruction if parallel connec-
tion of several motors on one output!
Final position switches could fuse
together. Motors, hangings and the
device may be destroyed!
Only connect one motor per
output!
ç
P
P
z
2 Hager 12.16 - 6LE002527AHager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com
Installing the appliance
Observe temperature range. Provide sufcient
cooling.
zMount device onto DIN rail in accordance with
DIN EN 60715.
Connecting the device (Figure 2)
The installation circuit must be protected via circuit
breaker 10 A.
zConnect bus cable via connecting terminal (2).
zConnect mains voltage (7).
zConnect motors.
Start-up
Systemlink: Loading physical address and
application software
The switch (1) is in .auto1/auto2
zSwitch on bus voltage.
zPress programming button (5).
The button lights up.
If the button does not light up, no bus voltage is
present.
zLoad the physical address into the device.
Status LED of the button goes out.
zLoad application software.
zNote down the physical address on the labelling
eld (4).
Easylink:
Information on the system conguration can be
taken from the extensive description of the service
module easylink.
Starting up the device
zSwitch on mains voltage on the outputs.
zSwitch on mains supply.
P
P
Determine operation time and slat adjusting
time
In blind/roller shutter operation, the operation time
for positioning the sunshade is important. The posi-
tion is calculated based on the operation time. The
slat adjusting time for slat blinds, determined by
the design, is part of the total operation time. The
opening angle of the slats is therefore set as oper-
ation time between opened and closed position.
The operation time for UP is normally longer
than the operation time for DOWN and must be
measured separately if necessary.
zMeasure UP and DOWN operation time of the
hanging.
zMeasure slat adjusting time between OPEN
and CLOSED.
zEnter measured values into the parameter set-
ting – ... or .running time slat step time
Functional test
The functionality of the outputs is displayed via the
status LED of the operation button (6).
Appendix
Technical data
KNX medium TP 1
Conguration mode S-Mode, E-controller
easy link
Rated voltage KNX 30 V SELVs
Own consumption on the KNX bus:
- typical 7 mA
- in standby 5 mA
Auxiliary voltage 230V~ +10%/-15%
240V~ +/-6%
Mains frequency 50/60 Hz
Power dissipation maximum 3 W
Own consumption on mains:
- maximum 5 W
- in standby 0.2 W
P
Breaking capacity µ 4A AC1 230V~
Switching current at cos Φ = 0.6 max. 4 A
Upstream protection: circuit breaker 10 A
Operating altitude max. 2000 m
Degree of contamination 2
Surge voltage 4 kV
Degree of protection of housing IP 20
Degree of protection of housing
under front panel IP30
Impact protection IK 04
Overvoltage class III
Operating temperature -5°C à + 45°C
Storage/transport temperature -20°C à + 70°C
Maximum switching cycle
rate at full load 6 switching cycle/minute
Connection capacity 0.5 mm² … 6 mm²
Dimension 10 TE, 10 x 17.5 mm
Troubleshooting
Manual operation not possible
Cause 1: Switch (1) not moved to 1/ 2.
Move switch to 1/ 2.
Cause 2: Manual operation has not been enabled
(Systemlink).
Enable manual operation via application soft-
ware.
Bus operation is not possible
Cause: Bus voltage is not present.
Check bus connection terminal for correct
polarity.
Check bus voltage by briey pressing the pro-
gramming button (5), red LED lights up if bus
voltage is present.
If mains voltage is available without bus voltage
- red LED of the programming button (5) blinks.
Cause 2 : Manual operation is active. Switch (1) is
in position .1/ 2
Move switch (1) to position .auto1/auto1
Shutters/blinds do not move to the nal
position
Cause: Operation time for the shutters/blinds set
incorrectly.
Check operation times. Measure again and
reprogram if necessary.
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment).
(Applicable in the European Union and other European
countries with separate collection systems).
This marking shown on the product or its literature
indicates that it hould not be disposed with other
household wasted at the end of its working life. To prevent
possible harm to the environment or human health from
uncontrolled waste disposal, please separate this from
other types of wastes and recycle it responsibly to
promote the sustainable reuse of material resources.
Household users should contact either the retailer where
they purchased this product, or their local government
oce, for details of where and how they can take this item
for environmentally safe recycling.
Business users should contact their supplier and check
the terms and conditions of the purchase contract. This
product should not be mixed with other commercial
wastes of disposal.
Usable in all Europe
å
and in Switzerland
C1/C7 C3/C9 C5/C11
C2/C8 C4/C10 C6/C12
3 4 5 6 7 8 9 10 11 12 13 14 15 16 171 2
N L
L L LC9 C11
230V 50/60 Hz
L L LC10 C12C8C6C4C2
18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
auto 1
auto 2
L3
L2
L1
N
L3
L2
L1
N
Fig 2: Device connection


Specyfikacje produktu

Marka: Hager
Kategoria: nieskategoryzowany
Model: TYM632C
Kolor produktu: Szary
Wysokość produktu: 90 mm
Głębokość produktu: 65 mm
Zakres temperatur (eksploatacja): -5 - 45 °C
Stopień ochrony IP: IP20
Liczba dołączonych produktów: 1 szt.

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager TYM632C, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Hager

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Meec Tools

Meec Tools 010-084 Instrukcja

6 Października 2024
Outwell

Outwell Scenic Road 250 Instrukcja

5 Października 2024
Impact

Impact QuikBalance Instrukcja

4 Października 2024
Impact

Impact CA-112 Instrukcja

4 Października 2024
Impact

Impact LS-BHA Instrukcja

4 Października 2024
Impact

Impact LKB-5C Instrukcja

4 Października 2024
Impact

Impact RST-001 Instrukcja

4 Października 2024