Instrukcja obsługi Hager JK208B


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Hager JK208B (2 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 8 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 1
Invicta 3 TP&N Distribution Board
250A
Invicta 3 250A
TP&N Distribution Boards
A range of Type B TPN Distribution boards
with high aesthetics ideal for commercial
ofces, healthcare and education projects
where the boards may be sited in public areas.
Features & Benefits
- High aesthetic glazed door option for siting in public areas
- Range of incomer options suitable for a wide range of building
applications
- Door locking kit with key for additional security
- Meter and surge protection options to meet application needs.
- Part of a wider range of Distribution boards
- Comprehensive solution for commercial building applications including
125A, Power & Lighting boards and Hybrid Distribution board
Description
Cat ref.
Plain door
Cat ref.
Glazed door
Cat ref.
Residential
Applications
8 Triple Pole Ways 250A TP&N Board JK208B JK208BG JK208BA3
12 Triple Pole Ways 250A TP&N Board JK212B JK212BG JK212BA3
16 Triple Pole Ways 250A TP&N Board JK216B JK216BG JK216BA3
18 Triple Pole Ways 250A TP&N Board JK218B JK218BG JK218BA3
24 Triple Pole Ways 250A TP&N Board JK224B JK224BG JK224BA3
Incomer Kits for 125A Boards Cat Ref.
3 Pole 250A MCCB Incomer Kit (Fits within distribution board) JK22503M
4 Pole 250A MCCB Incomer Kit (Fits within distribution board) JK22504M
3 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board) JK22503S
4 Pole 250A Switch Disconnector Incomer Kit (Fits within distribution board) JK22504MCS
4 Pole 250A Direct Connection Kit (Fits within distribution board) JK22504D
4 Pole 160A Contactor Incomer Kit includes Switch Disconnector (Fits below distribution board, 450mm high) JK21604C
3 Pole 125A MCCB Incomer Kit (Fits within distribution board) JK21253M
4 Pole 125A MCCB Incomer Kit (Fits within distribution board) JK21254M
Conforming the BS EN 61439-3, the Invicta boards are available with
glazed or solid steel doors to suit installation requirements. A wide range
of incoming options create a versatile solution. Metering and surge
protection options ensure efcient integration in to the buildings electrical
supply model. A 125A TP&N board range is also available for smaller load
applications.
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 2
Invicta 3 TP&N Distribution Board
250A
Technical Characteristics
Standards Designed, manufactured and tested to
BS EN 61439-3
Busbar Current Rating 25 A0
Busbar Type Fully shrouded copper
Busbar Rating 25kA Conditional
Incoming 250 3 or 4 Pole DisconnectorA Switch
125A 3 or 4 Pole Switch Disconnector
250 3 or 4 Pole MCCBA
160A Contactor AC3
Direct Connection
RCCB Incomers
Outgoing Ways 8, 12, 16, 18, 24 Triple pole outgoing ways
Outgoing Protection Type B MCB (6A to 63A, 1P & 3P)
Type C, D MCB, (0.5A to 63A, 1P & 3P)
1Mod and 2Mod RCBO
Voltage Rating in AC 230 / 415V
IP Protection IP3X to BS EN 60529
Enclosure Body Type Steel
Enclosure Paint Type Powder Coat Grey White BS4800 00A01
Cable Entry Obround protected cable entry points
Terminal Connection Capacity
Incoming Line Terminal 25mm ide lug connectionM8 W , 120mm Max Cable
Incoming Earth Terminal M8 stud
Incoming Neutral Terminal 50mm² cage or M6 stud
Outgoing Earth Terminals 16mm²
Outgoing Neutral Terminals 16mm²
Enclosure Earth Stud M8
Installation
Mounting 4 x key hole xing holes plus central top key hole for one xing hanging /
levelling
Surface Wall Mount
Gland Plate Top and bottom removable
Integrated Locking System Coin lock as standard, key lock as
accessory
Devices
MCB 10kA 0.5A to 63A NBN*** NCN*** NDN***
RCBO 10kA 6A to 45A ADB*** ADC*** ADA1** ACB*** ACC***
MCB 10kA / 15kA 80A to 125A HMC*** HMD***
250A Primary Boards
Dimensions (mm) Fixing Centres (mm)
Height Width Depth A B C
JK208B/BG/A3 950 465 165.5 365 100 750
JK212B/BG/A3 1100 465 165.5 365 100 900
JK216B/BG/A3 1250 465 165.5 365 100 1050
JK218B/BG/A3 1400 465 165.5 365 100 1200
JK224B/BG/A3 1550 465 165.5 365 100 1350
L1 L2 L3
L1
L2
L3
L1
L2
L3
IS OL E SU PPAT LY
BEFORE REM OVI NG COVER
UN
LOCK UN
LOCK
L1 L2 L3
Depth
B
C
A
Height
Width


Specyfikacje produktu

Marka: Hager
Kategoria: nieskategoryzowany
Model: JK208B
Wysokość produktu: 950 mm
Szerokość produktu: 465 mm
Głębokość produktu: 165.5 mm
Stopień ochrony IP: IP30
Natężenie znamionowe: 250 A

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager JK208B, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Hager

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Meec Tools

Meec Tools 010-084 Instrukcja

6 Października 2024
Outwell

Outwell Scenic Road 250 Instrukcja

5 Października 2024
Impact

Impact QuikBalance Instrukcja

4 Października 2024
Impact

Impact CA-112 Instrukcja

4 Października 2024
Impact

Impact LS-BHA Instrukcja

4 Października 2024
Impact

Impact LKB-5C Instrukcja

4 Października 2024
Impact

Impact RST-001 Instrukcja

4 Października 2024