Instrukcja obsługi Hager JK102SPD


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Hager JK102SPD (2 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/2
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 1
Commercial Distribution
Surge Protection Kits
JK102SPD
Surge Protection Kit
Type 2 Surge Protection Kit for Hager 125A
TP&N Distribution Boards to aid compliance
with 18th Edition BS 7671.
- Combination of high capacity voltage limiting varistors and N-PE spark
gap
- Suitable for CT2 connection as per 534.4.3.2 BS7671 18th Edition
- Optical status indication for each cartridge
Neutral = Healthy, Red = Replace
- Pluggable surge protection modules for ease of replacement
- Each cartridge incorporates its own thermal disconnect mechanism
- Cartridges are mechanically coded to prevent mis-connection
- Cartridges can be routinely checked and changed if required without
interrupting supply to loads
- No secondary back-up protection required in distribution boards of 125A
In or less
JK102SPD
Product Description
A Surge protection device (SPD) kit specically developed
for Hager standard TPN (Type B) Distribution boards.
Developed to ensure optimal performance of SPD
technology within Hager distribution boards. SPD is CT2
type to ensure compatibility with all common UK Earthing
arrangements e.g. TN-C-S (PME), TN-S and TT earthing
arrangements. This is an IEC Type 2 / class II SPD for 3 –
phase power supply networks. A type 2 SPD is generally
used in sub-distribution boards, downstream of the primary
board which may incorporate a Type 1 SPD.
This SPD kit ts within the standard distribution board. Line,
Neutral and Earth connections are via copper busbar and
copper links, minimising SPD conductor losses, maximising
the effective performance of the SPD (Up effective). SPD
performance coordination with upstream Type 1 SPD within
Hager MCCB Panelboards has been veried.
Key Specifications
- Power Supply System -TN / TT
- Requirement class -SPD class II acc. to IEC 61643-11;
SPD Type 2 acc. to EN 61643-11
- Max. continuous operating voltage Uc -L-N: 275 V a.c. /
N-PE: 260 V a.c.
- Nominal voltage Un -230/400 V AC 50/60 Hz
- Nominal discharge current In (8/20) microseconds 20 kA
- Max. discharge current I max (8/20) microseconds 40 kA
SPD Protection level Up -L-N: < 1.35 kV/ N-PE: <1.5 kV
Solution Protection level Up (measured at the main effective
busbars on the TPN board) -L-N: <1.5kV/ N-PE: < 1.5kV
Short-circuit current rating lSCCR -25kA
Degree of protection - IP20
Tightening torque - see installation instructions.
89,8
44
7,56
71
Dimensional Drawing Circuit Diagram
Hager Ltd. Hortonwood 50, Hortonwood, Telford, TF1 7FT / 01952 675 675 2
Commercial Distribution
Surge Protection Kits
General Data
Standards/regulations IEC 61643-11 2011 EN 61643-11 2012
IEC test classication T2
EN type T2
Mode of protection L-N
L-PE
N-PE
Mounting type DIN rail: 35 mm
Degree of pollution 2
Overvoltage category III
Degree of protection IP20
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ± Y, ±Z)
Vibration (operation) 5g (10 ... 500 Hz/ 2.5 h / X, Y, Z)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) Permissible humidity
(operation)
-40 °C ... 80 °C
Electrical Data
Nominal voltage Un230 / 400 V AC (TN / TT)
Nominal frequency fn50 Hz (60 Hz)
Maximum continuous operating voltage Uc (L-N) 275 V AC
Maximum continuous operating voltage Uc (L-PE) 275 V AC
Maximum continuous operating voltage Uc (N-PE) 260V AC
Residual current l
PE 5 uA
Standby power consumption Pc 360 mVA
Nominal discharge current In (8/20) μs 20kA
Maximum discharge current lmax (8/20) μs 40kA
Follow current interrupt rating l
fI (N-PE) 100A
Short-circuit current rating lsccR 25kA
Voltage protection level Up (L-N) ≤ 1.35kV
Voltage protection level Up (L-PE) ≤1.6 kV
Voltage protection level UP (N-PE) 1.5kV
Max. backup fuse 125 A (gG)
Max. backup fuse with V-type through wiring 80 A (gG)


Specyfikacje produktu

Marka: Hager
Kategoria: nieskategoryzowany
Model: JK102SPD

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager JK102SPD, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Hager

Hager

Hager VS418PZF Instrukcja

15 Sierpnia 2024
Hager

Hager VS318PZF Instrukcja

15 Sierpnia 2024
Hager

Hager VS218PZF Instrukcja

15 Sierpnia 2024
Hager

Hager TN204S Instrukcja

15 Sierpnia 2024
Hager

Hager TN206S Instrukcja

15 Sierpnia 2024
Hager

Hager EH171A Instrukcja

15 Sierpnia 2024
Hager

Hager EG203 Instrukcja

14 Sierpnia 2024
Hager

Hager EG403E Instrukcja

14 Sierpnia 2024
Hager

Hager M-RG404020 Instrukcja

14 Sierpnia 2024
Hager

Hager 80262160 Instrukcja

14 Sierpnia 2024

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Asko

Asko DBI644MIB.S.TW/1 Instrukcja

28 Października 2024
Asko

Asko DFS233IB.S.TW/1 Instrukcja

28 Października 2024
Emko

Emko EZM-9920 Instrukcja

27 Października 2024
Emko

Emko ESM-3712-H Instrukcja

27 Października 2024
Emko

Emko ATS-10 Instrukcja

27 Października 2024
Emko

Emko EAOM-11.2 Instrukcja

27 Października 2024
Emko

Emko EPM-3790 Instrukcja

27 Października 2024
Emko

Emko EPM-7790 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux IAN 108340 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux HG06009A-BS Instrukcja

27 Października 2024