Instrukcja obsługi Hager 85121200


Przeczytaj poniżej 📖 instrukcję obsługi w języku polskim dla Hager 85121200 (4 stron) w kategorii nieskategoryzowany. Ta instrukcja była pomocna dla 2 osób i została oceniona przez 2 użytkowników na średnio 4.5 gwiazdek

Strona 1/4
Relay insert
1/4
07/2012
Relay insert
Order no.: 8512 12 0x
Operating instructions
1. Safety instructions
Electrical equipment may only be installed and assembled by a qualied electrician in
accordance with the relevant installation standards, guidelines, regulations, directives,
safety and accident prevention regulations of the country.
Failure to comply with these instructions may result in damage to the device, re or other
hazards.
Hazard due to electric shock. Do not operate device without application module.
Hazard of re. During operation with inductive transformers, protect each transformer on
the primary side according to manufacturer's data. Use safety transformers that comply
with EN 61558-2-6 (VDE 0570 Part 2-6) only.
These instructions are an integral component of the product and must be retained by the
end user.
2. Design and layout of the device
(1)
(2)
(3)
(4)
(5)
(6)
Figure 1: Switch insert
(1) Switch insert
(2) Frames
(3) Application module
(4) Screw for dismantling protection (not R.1/R.3)
(5) Button design cover
(6) Connecting terminals
Relay insert
2/4
07/2012
3. Function
Correct use
Only suitable for use in indoor areas with no drip and no spray water.
Switching of incandescent lamps, HV halogen lamps, uorescent lamps, compact
uorescent lamps, dimmable energy-saving lamps, 230 V LED lamps and electronic or
inductive transformers with low voltage halogen lamps
Installation into wall box according to DIN 49073
Operate with suitable application module (see Chapter 6.3, "Accessories")
Connection of extension unit push-button (NO contact), and motion detector extension unit
No mixed load operation of capacitive and inductive loads at the output.
4. Operation
These instructions describe the installation of the switch insert. The operation and function of
the application modules are described in the instructions of the respective application module.
The operation of extension units is only possible if a cover is attached to the main unit.
5. Information for electricians
5.1 Installation and electrical connection
DANGER!
Touching live parts can result in an electric shock.
An electric shock can be lethal.
Disconnect the connecting cables before working on the device and cover all live
parts in the area!
Circuiting and mounting the switch insert
µ
L
N
Figure 2: Basic circuit
Relay insert
3/4
07/2012
µ
L
N
5031
to additional
extension units
Figure 3: Circuiting diagram with extension unit
A MCB max. 10 A has been installed as device protection.
Circuit switch insert and optional extension units according to the circuiting diagram (Figure
3 or 4).
Mount the switch insert into a wall box. The connecting terminals must be at the bottom.
Attach frame and application module (see instructions for application module).
Illuminated mechanical push-buttons must be equipped with a separate N-terminal.
6. Appendix
6.1 Technical data
Rated voltage 230 V~, + 10 % /- 15 %
Mains frequency 50/60 Hz
MCB max. 10 A
Standby power consumption < 0.1 W
Degree of protection IP20
Relative humidity 0 ... 65 % (no condensation)
Operating temperature -5°C … +45°C
Storage/transport temperature -20°C … +60°C
Number of extension units and motion detector extension units unlimited
Extension unit cable length max. 50 m
Load cable length max. 100 m
Connecting terminal cross section 1 x 4 mm² or 2 x 2.5 mm²
Mounting orientation connecting terminals downwards
Housing installation depth 22 mm
Claw guide installation depth 32 mm
Incandescent lamps 2300 W
HV halogen lamps 2300 W
LV halogen lamps with electronic transformers or dual-mode transformers 1500 VA
LV halogen lamps with conventional transformers 1500 VA
Fluorescent lamps with lead-lag circuit 1000 W
Uncompensated uorescent lamps 1100 W
Parallel compensated uorescent lamps 1000 VA / 130 µF
Fluorescent lamps with electronic ballast 1000 W
Compact uorescent lamps with electronic ballast 22 x 20 W
Dimmable energy-saving lamps 440 W
230 V LED lamps (retrot LED) 440 W
Mixed loads possible to lowest maximum load
Type of contact µ-contact, NO contact


Specyfikacje produktu

Marka: Hager
Kategoria: nieskategoryzowany
Model: 85121200

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Hager 85121200, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje nieskategoryzowany Hager

Hager

Hager VS418PZF Instrukcja

15 Sierpnia 2024
Hager

Hager VS318PZF Instrukcja

15 Sierpnia 2024
Hager

Hager VS218PZF Instrukcja

15 Sierpnia 2024
Hager

Hager TN204S Instrukcja

15 Sierpnia 2024
Hager

Hager TN206S Instrukcja

15 Sierpnia 2024
Hager

Hager EH171A Instrukcja

15 Sierpnia 2024
Hager

Hager EG203 Instrukcja

14 Sierpnia 2024
Hager

Hager EG403E Instrukcja

14 Sierpnia 2024
Hager

Hager M-RG404020 Instrukcja

14 Sierpnia 2024
Hager

Hager 80262160 Instrukcja

14 Sierpnia 2024

Instrukcje nieskategoryzowany

Najnowsze instrukcje dla nieskategoryzowany

Asko

Asko DBI644MIB.S.TW/1 Instrukcja

28 Października 2024
Asko

Asko DFS233IB.S.TW/1 Instrukcja

28 Października 2024
Emko

Emko EZM-9920 Instrukcja

27 Października 2024
Emko

Emko ESM-3712-H Instrukcja

27 Października 2024
Emko

Emko ATS-10 Instrukcja

27 Października 2024
Emko

Emko EAOM-11.2 Instrukcja

27 Października 2024
Emko

Emko EPM-3790 Instrukcja

27 Października 2024
Emko

Emko EPM-7790 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux IAN 108340 Instrukcja

27 Października 2024
Livarno Lux

Livarno Lux HG06009A-BS Instrukcja

27 Października 2024