GN4 N
high-efficiency cast iron boiler for liquid fuels and/or gas
OPERATING, INSTALLATION AND MAINTENANCE INSTRUCTIONS
caldaia di ghisa ad alto rendimento per combustibili liquidi e/o gassosi
ISTRUZIONI PER L’USO L’INSTALLAZIONE E LA MANUTENZIONE
chaudière en fonte a haut rendement pour combustibles liquides et/ou gazeux
INSTRUCTIONS POUR L’INSTALLATION ET L’ENTRETIEN
caldera de fundición, de alto rendimiento para combustibles líquidos y/o gaseosos
INSTRUCCIONES DE USO, INSTALACIÓN Y MANTENIMIENTO
verwarmingsketel in gietijzer met hoog rendement voor vloeibare en/of gasvormige brandstof
AANWIJZINGEN VOOR HET GEBRUIK, DE INSTALLATIE EN HET ONDERHOUD
sivi ve/veya gaz yakitli yüksek ver‹ml‹
DÖKÜM DÖLMLÖ KAZAN
GB
IT
FR
ES
NL
TR
co d. 35 41A511 - Re v . 01 - 03/20 1 5
EnglishItalianoFrançaisEspañol
Nederlands
Türkçe
2
GN4 N
Cod. 3541A511 - Rev. 01 - 03/2015
Dear Customer,
Thank you for having chosen the , an advanced-concept Ferroli boiler GN4 N
featuring cutting-edge technology, high reliability and constructional quality.
Carefully read this manual and keep it for future reference.
The is a high-efficiency heat generator for the production of hot water GN4 N
for heating purposes, suitable for operation with jet burners on gas or liquid
fuel.
The boiler body consists of cast-iron elements, the shape of which, together
with the careful design of the fins, ensure high heat exchange efficiency in all
operating conditions.
Important warnings
• This manual provides important indications on the
safety of operation, installation and maintenance, and
is an integral and essential part of the product. Read
this manual before installation and operation. It should
be carefully kept for future reference.
• This appliance must only be used for the purposes
it has been specifically designed for. This appliance
is used to heat water to below-boiling temperatures
at atmospheric pressure, and must be connected
to a heating and/or domestic hot water distribution
system, according to its characteristics, performance
and heating capacity. All other uses are considered
improper and thus dangerous.
• The appliance may not be opened nor its components
tampered with, except for the parts included in the
maintenance operations. The appliance may not be
modified to alter its performance or use.
• The installation and maintenance operations must be
performed according to the standards in force, the
instructions of the manufacturer and must be carried
out by professionally qualified personnel.
• Incorrect installation or poor maintenance may cause
damage to people, animals or things. The manufacturer
declines all liability for damage deriving from errors in
the installation and operation of the appliance, and in
any case from the failure to observe the instructions
provided.
• Before performing any cleaning or maintenance opera-
tions, disconnect the appliance from the mains power
supply using the system switch and/or the correspon-
ding on-off devices.
• In the event of faults and/or poor operation of the
appliance, it should be deactivated. Do not attempt to
repair the appliance. Contact professionally qualified
personnel only.
• After having removed the packaging, check that the
contents are intact. The parts of the packaging must
not be left within the reach of children, as they are
potential sources of danger.
ENGLISH
Electrical power
supply
Max operating
pressure temperature
PIN
Serial number
Max operating
pressure
Heat output
Uselful heat output
Bar code
Water content
08/250
0085AS0589
0085
230V~50Hz IP X 0D
Ser. n. 0352L50349
Q
P
-
-
kW
kW
270
250
max
160
150
min
PMS
tmax
6
100
bar
¡C
PMW
D
bar
l/min
Appr. nr.
H
2
O
163 L
Certification
The CE Mark attests that Ferroli appliances
conform to the requirements specified in
the applicable European directives.
In particular, this appliance conforms to the
following EEC directives:
• Gas directive 90/396
• Efficiency directive 92/42
• Low voltage directive 73/23 (amended by
93/68)
• Electromagnetic compatibility directive
89/336 (amended by 93/68)
3
English Italiano Français Español
Nederlands
Türkçe
GN4 N
Cod. 3541A511 - Rev. 01 - 03/2015
1. OPERATING INSTRUCTIONS
1.1 Control panel
21 4 53
1.2 Ignition
Move the main switch 5 to position “I” to power the boiler and the burner. Refer to the burner manual for the operation of
this device.
1.3 Setting
Set the desired system temperature using the control thermostat . If the thermoregulation control unit (optional) is con-4
nected, refer to the corresponding instruction manual.
1.4 Shut-down
For brief periods of inactivity, simply move switch (Fig. 1) on the control panel to position “0”. 5
For extended periods of inactivity, as well as operating switch , the fuel on-off valve must also be closed. 5
For extended periods of inactivity during the winter period, to avoid damage from frost, add special antifreeze to the system
or drain the system completely.
1.5 Anomalies
Two lockout conditions may occur that can be reset by the user:
a - Burner lockout signalled by the corresponding light 6 (Fig. 1). Refer to the burner manual.
b - Activation of the safety thermostat when the temperature in the boiler reaches the limit value above which a dangerous
situation may arise. To reset operation, unscrew cap and press the reset button. 3
If the problem occurs again, contact qualified personnel or the service centre. In the event of faults and/or poor operation
of the appliance, it should be deactivated. Do not attempt to repair the appliance. Contact professionally qualified and
authorised personnel only.
2. INSTALLATION
General instructions
This appliance must only be used for the purposes it has been specifically designed for. This appliance is used to heat
water to below-boiling temperatures at atmospheric pressure, and must be connected to a heating and/or domestic hot
water distribution system, according to its characteristics, performance and heating capacity. All other uses are considered
improper.
THE BOILER MUST ONLY BE INSTALLED BY QUALIFIED AND SPECIALIST PERSONNEL, IN COMPLETE COM-
PLIANCE WITH ALL THE INSTRUCTIONS REPORTED IN THIS TECHNICAL MANUAL, THE LEGAL STANDARDS IN
FORCE, THE PRESCRIPTIONS OF ANY NATIONAL AND LOCAL STANDARDS, AND ACCORDING TO THE RULES
OF GOOD PRACTICE.
Incorrect installation may cause damage to people, animals and things. The manufacturer will not be held liable in such
events.
Place of installation
The room in which the boiler is installed must have ventilation openings to the outside according to the standards in force.
If the same room features a series of burners or exhaust devices that can operate at the same time, the ventilation openings
must be large enough for the simultaneous operation of all the appliances.
The place of installation must be free of flammable objects or materials, corrosive gas, dust
or volatile substances that, sucked in by the burner’s fan, may block the internal tubing of
the burner or the combustion head. The environment must be dry and not exposed to rain,
snow or frost.
Positioning the boiler
The minimum spaces shown in the figure must be complied with. Specifically, make sure
that after assembling the boiler with the burner on the front door, the latter can be opened
without the burner hitting against the wall or any other boiler. Leave a free space of at least
100mm on the side that the door swings towards.
6
100
mm
550==
Key
1 Ready for electronic control unit
2 Thermometer
3 Safety thermostat
4 Control thermostat, 2 Stages
5 Line switch “0 - I - TEST”
6 Burner lockout indicator light
fig. 1
fig. 2
Burner
Specyfikacje produktu
Marka: | Ferroli |
Kategoria: | kocioł centralnego ogrzewania |
Model: | GN4 N |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Ferroli GN4 N, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje kocioł centralnego ogrzewania Ferroli
5 Października 2024
21 Września 2024
10 Września 2024
10 Września 2024
9 Września 2024
3 Września 2024
30 Sierpnia 2024
28 Sierpnia 2024
27 Sierpnia 2024
26 Sierpnia 2024
Instrukcje kocioł centralnego ogrzewania
- kocioł centralnego ogrzewania Morco
- kocioł centralnego ogrzewania Bosch
- kocioł centralnego ogrzewania Remeha
- kocioł centralnego ogrzewania Truma
- kocioł centralnego ogrzewania Ariston Thermo
- kocioł centralnego ogrzewania Intergas
- kocioł centralnego ogrzewania Buderus
- kocioł centralnego ogrzewania Viessmann
- kocioł centralnego ogrzewania Vaillant
- kocioł centralnego ogrzewania Baxi
- kocioł centralnego ogrzewania Atag
- kocioł centralnego ogrzewania Junkers
- kocioł centralnego ogrzewania ACV
- kocioł centralnego ogrzewania De Dietrich
- kocioł centralnego ogrzewania Nefit
- kocioł centralnego ogrzewania A.O. Smith
- kocioł centralnego ogrzewania AGPO
- kocioł centralnego ogrzewania Itho
- kocioł centralnego ogrzewania Stiebel Eltron
- kocioł centralnego ogrzewania Elco
- kocioł centralnego ogrzewania Masterwatt
- kocioł centralnego ogrzewania Nibe
- kocioł centralnego ogrzewania Itho-Daalderop
- kocioł centralnego ogrzewania Saunier Duval
- kocioł centralnego ogrzewania Vokèra
- kocioł centralnego ogrzewania Bulex
- kocioł centralnego ogrzewania AWB
- kocioł centralnego ogrzewania Fantini Cosmi
- kocioł centralnego ogrzewania Wolf
- kocioł centralnego ogrzewania Daalderop
- kocioł centralnego ogrzewania Tzerra
- kocioł centralnego ogrzewania Weishaupt
- kocioł centralnego ogrzewania Mikoterm
- kocioł centralnego ogrzewania Brink
- kocioł centralnego ogrzewania Oertli
- kocioł centralnego ogrzewania Ygnis
- kocioł centralnego ogrzewania ROC
- kocioł centralnego ogrzewania Thermona
Najnowsze instrukcje dla kocioł centralnego ogrzewania
15 Października 2024
10 Października 2024
8 Października 2024
7 Października 2024
7 Października 2024
7 Października 2024
6 Października 2024
5 Października 2024
4 Października 2024
3 Października 2024