User’s Guide
UPS 8 – 10 kVA,
230V 50/60 Hz output
(1-phase input)
&
UPS 8 – 15 kVA,
230V 50/60 Hz output
(3-phase input)
Copyright 2007
The contents of this manual are the copyright of the publisher and may not be
reproduced (even extracts)
unless permission granted.
Every care has been taken to ensure the accuracy of
the information contained in this manual, but no liability
can be accepted for any errors or omission. The right
to make design modifications is reserved.
UPS 8 – 10 kVA, 230V 50/60 Hz output (1-phase input)
UPS 8 – 15 kVA, 230V 50/60 Hz output (3-phase input)
User’s Guide 1022403 revision D
Contents
1. Safety instructions ............................................................................................................................................................. 4
Audience .............................................................................................................................................................................. 4
CE marking ........................................................................................................................................................................... 4
User precautions ................................................................................................................................................................. 4
Environment ......................................................................................................................................................................... 5
Inquiries ................................................................................................................................................................................ 5
2. Mechanical installation .................................................................................................................................................... 6
Delivery check ..................................................................................................................................................................... 6
Unpacking and visual inspection ..................................................................................................................................... 6
3. Planning before installation ............................................................................................................................................. 8
4. Cabinet installation ........................................................................................................................................................... 9
Maiantenance bypass switch ........................................................................................................................................... 9
Transformer option ............................................................................................................................................................. 11
External battery cabinet option ........................................................................................................................................ 12
Battery racks ....................................................................................................................................................................... 12
5. Electrical installation ........................................................................................................................................................ 13
Power cables and protective fuses ................................................................................................................................. 14
Wiring procedure ................................................................................................................................................................ 15
External Battery Cabinet (EBC) installation procedure ................................................................................................ 21
6. Software and connectivity ................................................................................................................................................ 24
Communication cables ....................................................................................................................................................... 24
Connection to the standard RS-232 port (X53) ............................................................................................................... 24
LanSafe software ........................................................................................................................................................... 25
External control connections ............................................................................................................................................ 25
Emergency Power Off (EPO) ......................................................................................................................................... 26
Relay outputs ................................................................................................................................................................... 26
Programmable signal inputs ......................................................................................................................................... 27
XSlot communication (option) ........................................................................................................................................... 28
Web/SNMP Module (optional) ..................................................................................................................................... 28
AS400 Relay Module (optional) .................................................................................................................................... 29
Single Serial Port Module (optional) ........................................................................................................................... 29
Modus/Jbus Module (optional) .................................................................................................................................... 29
7. User operations ................................................................................................................................................................... 30
Display functions ................................................................................................................................................................. 30
User Settings ....................................................................................................................................................................... 31
Configuring user settings .............................................................................................................................................. 33
Changing language ........................................................................................................................................................ 33
Changing charging current ........................................................................................................................................... 33
Using relay outputs ........................................................................................................................................................ 33
Normal start-up ................................................................................................................................................................... 34
Battery start-up ................................................................................................................................................................... 34
Start-up after EPO ............................................................................................................................................................... 34
Shutdown ............................................................................................................................................................................. 35
8. Maintenance ....................................................................................................................................................................... 36
Regular service/intervals ................................................................................................................................................... 36
Batteries ........................................................................................................................................................................... 36
Cooling fan ....................................................................................................................................................................... 37
LED Indicators ..................................................................................................................................................................... 37
Maintenance bypass switch (MBS) operation .............................................................................................................. 37
Turn UPS from normal mode to mechanical bypass ................................................................................................ 38
Turn UPS from mechanical bypass to normal mode ................................................................................................ 39
9. Parallel systems ................................................................................................................................................................. 41
Overview ............................................................................................................................................................................... 41
Tie cabinets .......................................................................................................................................................................... 42
XSlot Hot Sync card: installing and wiring ..................................................................................................................... 46
Parallel operations .............................................................................................................................................................. 47
10 Recycling the used UPS or batteries .............................................................................................................................. 49
11. Dimensional drawings ...................................................................................................................................................... 50
12. Technical data ..................................................................................................................................................................... 52
Standards ............................................................................................................................................................................ 52
Environment ......................................................................................................................................................................... 52
Mechanical configuration ................................................................................................................................................. 52
Characteristics .................................................................................................................................................................... 52
AC input ................................................................................................................................................................................ 53
DC circuit .............................................................................................................................................................................. 53
AC output .............................................................................................................................................................................. 53
13. Warranty ............................................................................................................................................................................... 54
Specyfikacje produktu
Marka: | Eaton |
Kategoria: | UPS |
Model: | Powerware 9155-12-N-15-64x7Ah-MBS |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z Eaton Powerware 9155-12-N-15-64x7Ah-MBS, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS Eaton
11 Października 2024
15 Września 2024
12 Września 2024
12 Września 2024
11 Września 2024
11 Września 2024
10 Września 2024
9 Września 2024
29 Sierpnia 2024
28 Sierpnia 2024
Instrukcje UPS
- UPS Ikea
- UPS AEG
- UPS Voltcraft
- UPS LC-Power
- UPS APC
- UPS Tripp Lite
- UPS Block
- UPS V7
- UPS Digitus
- UPS FSP
- UPS Online USV
- UPS Equip
- UPS Emerson
- UPS CyberPower
- UPS JUNG
- UPS Adj
- UPS PowerWalker
- UPS Salicru
- UPS Energenie
- UPS Steren
- UPS East
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Furman
- UPS Minuteman
- UPS Riello
- UPS Maruson
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Approx
- UPS Altronix
- UPS Bxterra
- UPS Middle Atlantic
- UPS Atlantis Land
- UPS FSP/Fortron
Najnowsze instrukcje dla UPS
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
9 Października 2024
9 Października 2024