Fire Alarm Systems | FLM‑I 420‑S Short Circuit Isolator
The Short Circuit Isolator isolates alarm zones in which a
short circuit has occurred. This means the functionality of
the remainder of the network remains preserved.
System Overview
b1+ a- b2+ N/A N/A N/A
LSN
9 1
6 4
7 3
8 2
0
5
8 2
0
5
6 4
9 1
7 3
CL 1
2
0
Description Connector
b1+ / a- / b2+ LSN
N/A (3 x) free terminals, e.g. for looping through ext. auxiliary volt-
age and for shielding
Functions
Features of improved LSN
The interface modules in the 420 series offer all the
features of improved LSN technology:
Flexible network structures including T‑tapping
without additional elements
Up to 254 LSN-improved elements per loop or stub
line
Unshielded cable can be used
Address switch (rotary switch)
The address of the Short Circuit Isolator is set using the
rotary switches.
The following settings are possible:
0 0 0 Loop/stub in LSN mode improved version with automatic
addressing (T-tap system not possible)
0 0 1 - 254 Loop/stub/T-tap system in LSN mode improved version
with manual addressing
CL 0 0 Loop/stub in classic LSN mode
Configuration
The Short Circuit Isolator isolates alarm zones in which a
short circuit has occurred. The following illustrations
show typical configurations of the isolator module.
FLM‑I 420‑S Short Circuit Isolator
Rotary switch for automatic and manual address
setting
Preservation of LSN loop functions in the event of a
short-circuit by two integrated isolators
Power supply via LSN
Three free screw terminals
www.boschsecurity.com
2 | FLM‑I 420‑S Short Circuit Isolator
Wiring example: Isolation of separate floors
1
LSN2
LSN1
a-
a-
b+
b+
b1+b1+b1+
a-a-a-
b2+b2+b2+
III
FLM-I 420-S
FLM-I 420-S
FLM-I 420-S
II
I
LSN
LSN
Pos. Description
1 Fire panel
I, II, III Floors
Typical wiring in a T‑Tap
b1+
b1+b1+
b1+
a-
a-a-a-
b2+
b2+b2+
b2+
FLM-I 420-SFLM-I 420-S
1
LSN
LSN
Pos. Description
1 Alarm zone / device group with LSN elements
Certifications and Approvals
Complies with EN54-17:2005
Region Certification
Germany VdS G 207045 FLM-I 420-S; FLM-I 420-D
Installation/Configuration Notes
National standards and guidelines must be taken into
account during the planning stage.
The surface-mounted housing has two cable ducts on
opposite sides:
-2 x 2 pre-punched for diameter up to 21 mm/to
34 mm (for conduits)
-2 x 4 rubber bushes for inserting cables with
diameters of up to 8 mm.
In addition, there are cable ducts on the base of the
surface-mounted housing:
-1 x pre-punched cable ducts for diameter up to
21 mm (for conduits)
-2 x 4 rubber bushes for inserting cables with
diameters of up to 8 mm.
Connectable to the fire panels FPA‑5000 Modular and
FPA‑1200 with LSN technology improved version.
Parts Included
Qty. Components
1 Short Circuit Isolator with surface-mounted housing.
1 DIN rail adapter
Note Alternatively to the use of the surface-
mounted housing, the Isolator can be
mounted on a DIN rail with the included
adapter.
Technical Specifications
Electrical
Input voltage 15 V DC to 33 V DC
Max. current consumption
During initialization < 0.4 mA
Following the initializa-
tion
< 0.25 mA
Mechanics
LSN/Address setting 3 rotary switches for
Mode LSN classic or LSN improved
version
Automatic or manual addressing
Connections 6 threaded clamps
Housing material
Isolator module PPO (Noryl)
Surface-mount hous-
ing
ABS/PC-Blend
Housing color
Isolator module Off-white, similar to RAL 9002
Surface-mount hous-
ing
Signal white, RAL 9003
Dimensions Approx. 126 x 126 x 71 mm
(4.96 x 4.96 x 2.8 in.)
Weight Approx. 150 g (5.3 ounces)
FLM‑I 420‑S Short Circuit Isolator | 3
Environmental conditions
Permitted operating tempera-
ture
-20 °C to 50 °C
(-4 °F to 122 °F)
Permitted storage tempera-
ture
-25 °C to 85 °C
(-13 °F to. 176 °F)
Permitted relative humidity < 96%
Classes of equipment as per
IEC 60950
Class III equipment
Protection class as per
IEC 60529
IP 54
Ordering Information
FLM‑I 420‑S Short Circuit Isolator
for the isolation of alarm zones in which a
short circuit has occurred.
FLM-I 420-S
Accessories
FLM‑IFB126‑S Surface-mounted Housing
as retainer for the interface modules ser-
ies 420 type DIN rail (-D) or spare housing for
type surface-mount (-S)
FLM-IFB126-S
www.boschsecurity.com


Specyfikacje produktu

Marka: Bosch
Kategoria: Niesklasyfikowane
Model: FLM-I 420-S

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z Bosch FLM-I 420-S, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane Bosch

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane

Stihl

Stihl HT 70 Instrukcja

15 Października 2024
Ernesto

Ernesto H14270 Instrukcja

15 Października 2024
Uniden

Uniden BT MIC KIT Instrukcja

15 Października 2024
Vaude

Vaude Omnis Bike 26 Instrukcja

15 Października 2024
ART

ART ProChannel II Instrukcja

15 Października 2024
Aukey

Aukey DR02J Instrukcja

15 Października 2024
Master Lock

Master Lock 653EURD Instrukcja

15 Października 2024
Roland

Roland FR-18 Diatonic Instrukcja

15 Października 2024