Installation Guide
APC™ Smart-UPS™ Ultra Isolation and
Step-Down Transformer SRTL5KTF
Important Safety Instructions
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during
installation and maintenance of the Smart-UPS Industrial UPS and batteries.
Read the user documentation to become familiar with the equipment before trying to install or operate it.
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install,
operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment
to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label indicates that an electrical
hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible injury or death.
Product Handling Guidelines
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in minor or moderate
injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
<18 kg
<40 lb
18-32 kg
40-70 lb
32-55 kg
70-120 lb
>55 kg
>120 lb
Isolation and Step-Down Transformer SRTL5KTF2
Safety Information
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by Schneider Electric could void the
warranty.
• This transformer is intended for indoor use only.
• Do not operate this transformer in direct sunlight, in contact with fluids, or where there is excessive dust or
humidity.
• Be sure the air vents on the transformer are not blocked. Allow adequate space for proper ventilation.
• For a transformer with a factory installed power cord, connect the transformer power cable directly to an
output receptacle of the UPS. Do not use surge protectors or extension cords.
• The equipment is heavy. Always practice safe lifting techniques adequate for the weight of the equipment.
• For rack mount transformers, always install the transformer directly above the UPS in rack-mount
configuration. The UPS must be installed below the transformer.
• Always install peripheral equipment above the transformer in rack-mount configuration.
• Additional safety information can be found in the Safety Guide supplied with this unit.
Electrical safety
• The protective earth conductor for the transformer carries the leakage current from the load devices
(computer equipment). An insulated ground conductor is to be installed as part of the branch circuit that
supplies the transformer. The conductor must have the same size and insulation material as the grounded
and ungrounded branch circuit supply conductors. The conductor will typically be green and with or
without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the service panel.
• If the UPS input power is supplied by a separately derived system, the ground conductor must be properly
bonded at the supply transformer or motor generator set.
• Be sure that all the covers and panels are installed before operating the transformer.
• Do not insert any metal object through the ventilation openings.
• Be sure to turn off the input to the transformer and check the voltage at the output terminals is zero before
attempting to service or maintain the transformer.
Hardwire safety
• Verify that all branch circuit (mains) and low voltage (control) circuits are deenergized, and locked out
before installing cables or making connections, whether in the junction box or to the transformer.
• Wiring by a qualified electrician is required.
• Check national and local codes before wiring.
• All openings that allow access to transformer hardwire terminals must be covered. Failure to do so may
result in personal injury or equipment damage.
• Select wire size and connectors according to national and local codes.
General information
• The model and serial numbers are located on a small, rear panel label.
• Recycle the package materials or save them for reuse.
FCC Class A Radio Frequency Warning
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are intended to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.
Isolation and Step-Down Transformer SRTL5KTF 3
Product Information
The APC Smart-UPS Ultra transformer is intended for use as a step-down transformer. This transformer can also
function as an isolation transformer.
The transformer can be installed as a tower or in a standard 19 inch rack. For rack-mount configuration use
rack-mount kit SRTRK2 only, which can be purchased separately.
Package Contents
Inspect the contents upon receipt. Notify the carrier and dealer if the unit is damaged.
Specifications
For additional specifications refer to our web site, www.apc.com.
Environmental
Physical
NOTE: The product is heavy. Follow lifting guidelines.
Front bezel Stabilizer foot 1 pair
Screws for securing the Stabilizer
foot to the transformer - 4x
1 screw for securing transformer
tie bracket
1 screw for securing on UPS
mount of tie bracket
Tie bracket to secure the UPS to
the transformer
Temperature Operating 0 to 40 ºC (32 to 104 ºF)
Storage -15 to 45 ºC (5 to 113 ºF)
Maximum Elevation Operating 0 - 3,000 m (0 - 10,000 ft)
Storage 0 - 15,000 m (50,000 ft)
Humidity 0% to 95% relative humidity, non condensing
International Protection Code IP20
Unit weight, without packaging 51.7 kg
(113.979 lbs)
Unit weight, with packaging 56 kg
(123.459 lbs)
Unit dimensions without packaging
Height x Width x Depth
130 x 432 x 660 mm
(5.12 x 17.01 x 25.98 in)
Unit dimensions with packaging
Height x Width x Depth
255 x 591 x 785 mm
(10.03 x 23.26 x 30.90 in)
The model and serial numbers are on a small label located on the rear panel.
Specyfikacje produktu
Marka: | APC |
Kategoria: | UPS |
Model: | Smart-UPS Ultra SRTL5KTF |
Potrzebujesz pomocy?
Jeśli potrzebujesz pomocy z APC Smart-UPS Ultra SRTL5KTF, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą
Instrukcje UPS APC
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
12 Października 2024
9 Października 2024
9 Października 2024
Instrukcje UPS
- UPS Ikea
- UPS AEG
- UPS Voltcraft
- UPS LC-Power
- UPS Tripp Lite
- UPS Block
- UPS V7
- UPS Digitus
- UPS FSP
- UPS Online USV
- UPS Equip
- UPS Emerson
- UPS CyberPower
- UPS JUNG
- UPS Eaton
- UPS Adj
- UPS PowerWalker
- UPS Salicru
- UPS Energenie
- UPS Steren
- UPS East
- UPS Liebert
- UPS Avocent
- UPS Minute Man
- UPS Furman
- UPS Minuteman
- UPS Riello
- UPS Maruson
- UPS Phoenix Contact
- UPS Puls Dimension
- UPS Vanson
- UPS Approx
- UPS Altronix
- UPS Bxterra
- UPS Middle Atlantic
- UPS Atlantis Land
- UPS FSP/Fortron
Najnowsze instrukcje dla UPS
11 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024
9 Października 2024