Installation 990–91513 Release date: 02/2021
Easy Rack Accessory Short Shelf Kit ER7SHELFS
Kit Instructions
The 1U, Accessory Short Shelf can be installed to the vertical mounting rails in an
empty space in the Easy Rack to support your equipment.
ER7SHELFS Inventory Tools Required (not provided)
Shelf (1)
Torx® wrench
M6 x 12 Pan Head T30 Screw (8) Cage nut tool
Cage Nut M6 14/16 SWG (8)
Proper location in the rack for the cage nuts:
1U
7
6
5
ns0014a
1. Locate the top and bottom U space on the vertical
mounting rails. Every third hole on the mounting rails
is numbered to indicate the middle of a U space.
2. Install the cage nuts on the interior of the vertical
mounting rail; then install the shelf.
CAUTION
FALLING EQUIPMENT HAZARD
Do NOT install cage nuts vertically with the tabs engaging the top and bottom of
the square hole.
Failure to follow these instructions can result in injury or equipment
damage.
APC by Schneider Electric
70 Mechanic Street
02035 Foxboro, MA
USA
www.apc.com
As standards, specifications, and design
change from time to time, please ask for
confirmation of the information given in this
publication.
© – 2021 . All rightsAPC by Schneider Electric
reserved.
Easy Rack Accessory Short Shelf Kit ER7SHELFS
Proper installation position for the cage nuts:
ns1768a
Install cage nuts horizontally, with the tabs engaging
the sides of the square hole.
Install the cage nuts on the interior of the vertical
mounting rail.
Install the cage nut:
gen0188a
1. From the inside of the rack, insert the cage nut into the
square hole.
2. Hook one tab of the cage nut assembly through the far
side of the hole.
3. Place the cage nut tool on the other side of the cage
nut and pull to snap into position.
Remove the cage nut:
1. Remove any attached screw.
2. Grasp the cage nut, squeeze the tabs on the sides, and push to release it from the square hole.
Shelf Dimensions:
The Shelf has sliding rails which are adjustable from the minimum of 390mm (15.35 in.) when
retracted and maximum of 650mm (25.59 in.) when fully extended.
Adjust the rails:
To extend the adjustable rails of the shelf:
1. Remove the four (4) M6 x 12 pan head T30
screws.
2. Pull the rails out to the dimension you
require.
3. Install the four (4) M6 x 12 pan head T30
screws to secure the rails in their new
location to the shelf.
Install the shelf:
Install four (4) cage nuts to the front two vertical mounting rails as described above. Install four (4)
cage nuts to the inside of the rear vertical mounting rails as described above.
At the front of the rack, attach four (4) screws to the front of the shelf and into the four (4) cage nuts
you installed in the vertical mounting rails.
At the rear of the rack, install four (4) screws to the rails on the rear of the shelf and through the four
(4) cage nuts installed in the vertical mounting rails. The illustration below shows this installation
process.
ns3209a
Front of rack Rear of rack
The Easy Racks in the illustration above are shown without doors or side panels for clarity.
2 990–91513


Specyfikacje produktu

Marka: APC
Kategoria: Niesklasyfikowane
Model: ER7SHELFS

Potrzebujesz pomocy?

Jeśli potrzebujesz pomocy z APC ER7SHELFS, zadaj pytanie poniżej, a inni użytkownicy Ci odpowiedzą




Instrukcje Niesklasyfikowane APC

APC

APC SYNX-980214 Instrukcja

11 Grudnia 2024
APC

APC SYNX-3573406 Instrukcja

11 Grudnia 2024
APC

APC FS-AC-8002-U Instrukcja

15 Października 2024
APC

APC EVP1000 Instrukcja

14 Października 2024
APC

APC Switched Rack PDU Instrukcja

9 Października 2024
APC

APC C2C Instrukcja

9 Października 2024
APC

APC AP7868 Instrukcja

9 Października 2024
APC

APC P8VNTG Instrukcja

9 Października 2024
APC

APC P62 Instrukcja

9 Października 2024

Instrukcje Niesklasyfikowane

Najnowsze instrukcje dla Niesklasyfikowane